160/320/520kVA depending on model selected. Secondary UPS isolation breakers (2 to 6) are standard – must be determined pre-orderd. Includes: PM800 Meter for SBC System Level Metering.

E.42” Distribution Cabinet: Distribution Cabinets are an available option to the System Bypass Cabinets not individual UPS module. Available in 4 or 8 breaker combinations (225A only).

F.Remote Alarm Status Panel: A wall mounted panel, 17.5”Hx12”Wx4”D, with eight (8) indicating LED's shall display UPS status and any active alarms. The alarms shall be a latching type, such that if an alarm is triggered, the LED will stay ON (latch) even if the alarm is corrected. This feature will provide the operator the chance to verify the occurrence of the alarm.

Choose either: 2 Module, 3 Module, 4 Module, 5 Module, or 6 Module RASP model.

G.Seismic Anchors: Seismic Zone 4 anchors shall be available for all system cabinets.

H.Dual Input: Provided to accommodate a separate input source.

M.Bypass Input Fuses: Bypass input fuses are optionally provided on the bypass for current limiting of 65kAIC.

N.Top Entry Cabinet: 16” cabinet allows top power cable entry to UPS unit.

.

5.0FIELD QUAILTY CONTROL & SERVICE ORGANIZATION

5.1FIELD SERVICE ENGINEER QUALIFICATIONS

The manufacturer must employ a 7 X 24 nationwide (international where applicable) field service organization with rapid access to all regions of the nation. The responding service professionals must be factory-trained engineers with an accredited and proven competence to service three phase UPS.

5.2SPARE PARTS

Field Engineers must have immediate access to recommended spare parts with additional parts storage located in regional depots. Additional spare parts shall be accessible on a 7 x 24 basis from the national depot and must be expedited on a next available flight basis or via direct courier (whichever mode is quickest).

5.3MAINTENANCE TRAINING

The manufacturer shall make available to the customer various levels of training ranging from basic UPS operation to UPS maintenance.

5.4MAINTENANCE & SERVICE CONTRACTS

The manufacturer shall offer additional preventative maintenance and service contracts covering both the UPS and the battery bank. Accredited professional service engineers employed exclusively in the field of critical power systems service shall perform all maintenance and service. The manufacturer shall also offer extended warranty contracts.

APC – MGE Galaxy 5000 Specification (60Hz) 13

Effective: June 1, 2008 REV X0 JJG

Parallel Module

 

Image 13
Contents General Summary MGE GalaxyStandards SubmittalsFinal Submittals TemperatureQualifications & Quality Assurance DELIVERY, STORAGE, and HandlingService and Spare Parts WarrantyMAINTENANCE, Accessibility and Self Diagnostics AC Output Characteristics AC Input CharacteristicsSystem Description UPS Design RequirementsPFC Rectifier and Battery Charger BatteryModes of Operation Component DescriptionStatic Bypass 100% Rated, Continuous Duty InverterOutput Static Switch 100% Rated, Continuous Duty System Controls and IndicatorsMeasurements Status Indications and Events Mechanical Design and Ventilation Cabinet Weights and Dimensions The width of the UPS isOptional Accessories BatteryExternal Control and Communications Devices Page Maintenance & Service Contracts Maintenance TrainingSpare Parts END of Section 40 KVA 50 KVA 60 KVA 80 KVA 100 130 Configuration Battery 100 130 KVA111 150 182 120 156Weight Entry Battery80 KVA 100 KVA 130 KVA 109 137 164 219 273 355300 lbs 700 lbs