Schneider Electric 5000 Final Submittals, Qualifications & Quality Assurance, Temperature

Page 2

outline, connection diagram for external cabling, internal wiring diagram, and written instruction for installation.

1.4FINAL SUBMITTALS

Upon delivery of the UPS system the following submittals shall be included:

A.A complete set of installation drawings showing all the information stated in section 1.3.

B.An installation and users manual showing safe and correct operation of all UPS functions.

1.5QUALIFICATIONS & QUALITY ASSURANCE

A.Manufacturer’s Certification: The manufacturer shall specialize in manufacturing of on-line, double conversion three phase UPS modules specified in this document with a minimum of twenty years documented experience, and with a nationwide first party service organization. The manufacturer shall be ISO 9001 certified and shall design to internationally accepted standards.

B.Factory Testing: Prior to shipment the manufacturer shall complete a documented test procedure to test all functions of the UPS module and batteries (via a discharge test), when supplied by the UPS manufacturer, and guarantee compliance with the specification. The factory test shall be performed in the presence of the customer providing the manufacturer receives adequate prior notice. The manufacturer shall provide a copy of the test report upon request.

C.Materials and Assemblies: All materials and parts comprising the UPS shall be new, of current manufacture, and shall not have been in prior service, except as required during factory testing. All active electronic devices shall be solid state and not exceed the manufacturer’s recommended tolerances for temperature or current to ensure maximum reliability. All semiconductor devices shall be sealed. All relays shall be provided with dust covers. The manufacturer shall conduct inspections on incoming parts, modular assemblies, and final products.

1.6DELIVERY, STORAGE, AND HANDLING

A.All products shall be packaged in a manner to prevent penetration by debris and to allow safe delivery by all modes of ground transportation and air transportation where specified.

B.Prior to shipping all products shall be inspected at the factory for damage.

C.Equipment shall be protected against extreme temperature and humidity and shall be stored in a conditioned or protected environment.

D.Equipment containing batteries shall not be stored for a period exceeding three months without powering up the equipment for a period of eight hours to recharge the batteries.

1.7ENVIRONMENTAL REQUIREMENTS

The UPS shall operate under the following environmental conditions:

A.Temperature:

APC – MGE Galaxy 5000 Specification (60Hz) 2

Effective: June 1, 2008 REV X0 JJG

Parallel Module

 

Image 2
Contents Standards MGE GalaxyGeneral Summary SubmittalsQualifications & Quality Assurance TemperatureFinal Submittals DELIVERY, STORAGE, and HandlingMAINTENANCE, Accessibility and Self Diagnostics WarrantyService and Spare Parts System Description AC Input CharacteristicsAC Output Characteristics UPS Design RequirementsModes of Operation BatteryPFC Rectifier and Battery Charger Component DescriptionInverter Static Bypass 100% Rated, Continuous DutySystem Controls and Indicators Output Static Switch 100% Rated, Continuous DutyMeasurements Status Indications and Events Cabinet Weights and Dimensions The width of the UPS is Mechanical Design and VentilationExternal Control and Communications Devices BatteryOptional Accessories Page Spare Parts Maintenance TrainingMaintenance & Service Contracts END of Section 111 150 182 Configuration Battery 100 130 KVA40 KVA 50 KVA 60 KVA 80 KVA 100 130 120 15680 KVA 100 KVA 130 KVA Entry BatteryWeight 109 137 164 219 273 355300 lbs 700 lbs