Schneider Electric 5000 specifications Modes of Operation, Component Description, Battery

Page 5

+ 1% for loss or return of AC input power or manual transfer at full load

6.Voltage Recovery Time: Return to within 1% of nominal value within 16.67 milliseconds (one cycle)

7.Phase Angle Displacement: 120° + 1° for balanced load; 120° + 3° for 100% unbalanced load

8.Non-Linear Load Capability: Output voltage total harmonic distortion shall be less than 3% when connected to a 100% non-linear load with a crest factor not to exceed 3%.

9.Slew Rate: 1 Hz/second maximum (or selectable up to 2.0 Hz/sec)

10.Power Factor: 0.9 at the rated volt-amperes (VA)

11.Inverter Overload Capability: 125% of rated load for 10 minutes

150% of rated load for 1 minute

12.Bypass Overload Capability: > 212% for one cycle; > 150% for 1 minute

D.Battery

1.Battery Voltage: 356 VDC minimum before cutoff; 432 VDC nominal; 490 VDC equalization voltage

2. Maximum DC Current: Maximum DC current at cutoff voltage will be

[

]

A.

2.3MODES OF OPERATION

The UPS module shall be designed to operate as a double conversion, on-line reverse transfer system in the following modes.

A.Normal: The inverter shall continuously supply power to the critical load. The PFC rectifier shall derive power from the utility AC source and supply DC power to the inverter while simultaneously float charging the battery.

B.Emergency: Upon failure of the utility AC power source, the critical load shall be supplied by the inverter, which, without any interruption, shall obtain its power from the battery.

C.Recharge: Upon restoration of the utility AC power source (prior to complete battery discharge), the PFC rectifier shall power the inverter and simultaneously recharge the battery.

D.Bypass Mode: The static bypass transfer switch shall be used to transfer the load to the bypass without interruption to the critical power load. This shall be accomplished by turning the inverter off. Automatic re-transfer or forward transfer of the load shall be accomplished by turning the inverter on.

2.4COMPONENT DESCRIPTION

A.PFC Rectifier and Battery Charger

APC – MGE Galaxy 5000 Specification (60Hz) 5

Effective: June 1, 2008 REV X0 JJG

Parallel Module

 

Image 5
Contents General Summary MGE GalaxyStandards SubmittalsFinal Submittals TemperatureQualifications & Quality Assurance DELIVERY, STORAGE, and HandlingMAINTENANCE, Accessibility and Self Diagnostics WarrantyService and Spare Parts AC Output Characteristics AC Input CharacteristicsSystem Description UPS Design RequirementsPFC Rectifier and Battery Charger BatteryModes of Operation Component DescriptionStatic Bypass 100% Rated, Continuous Duty InverterOutput Static Switch 100% Rated, Continuous Duty System Controls and IndicatorsMeasurements Status Indications and Events Mechanical Design and Ventilation Cabinet Weights and Dimensions The width of the UPS isExternal Control and Communications Devices BatteryOptional Accessories Page Spare Parts Maintenance TrainingMaintenance & Service Contracts END of Section 40 KVA 50 KVA 60 KVA 80 KVA 100 130 Configuration Battery 100 130 KVA111 150 182 120 156Weight Entry Battery80 KVA 100 KVA 130 KVA 109 137 164 219 273 355300 lbs 700 lbs