Schneider Electric 5000 System Description, UPS Design Requirements, AC Input Characteristics

Page 4

static switch, battery plant, graphical status/control panel, dry contact and communications ports, and synchronizing circuitry as described herein.

2.2SYSTEM DESCRIPTION

A. UPS Design Requirements

1. Output Power Continuous Rating: The continuous output power rating of the UPS shall be [ ] kVA at a 0.9 lagging power factor.

Galaxy 5000 available: Choose 40, 50, 60, 80, 100, 130kVA

2.Input Voltage: 480 VAC – 15% / +10%, 3 phase, 3 wire “grounded wye” configuration plus ground.

3.Output voltage: 480 VAC 3 phase, 3 plus ground

4. Battery Autonomy: The UPS shall be capable of operating at full load for [ ] minutes at

0.9PF output at a temperature of 25°C on battery power.

5.Battery Type: Valve regulated sealed lead acid (VRLA)

B.AC Input Characteristics

1.Voltage: 480VAC, – 15% / +10%, 3 phase, 3 wire “grounded wye” configuration plus ground.

2.Frequency: 60 Hz ±5%

3.Power Factor: > .98 lagging

4.Total Harmonic Distortion: less than 5% at full load

5.Inrush Current: less than nominal input current for less than one cycle

6.Input Surge Protection: The UPS is equipped to withstand surges per IEC 1004/ANSI C62.41

C.AC Output Characteristics

1.Voltage: 480VAC , – /+ 1% steady-state variation phase to phase voltage VAC , 3 phase, 3 wire plus ground

2.Frequency: 60 Hz +1% (or selectable up to 4%); 60 Hz + 0.1% when free running

3.Voltage Regulation: + 1.0% for balanced load

+1.75 for 50% unbalanced load

+2.5% for 100% unbalanced load

4.Voltage Distortion: Maximum 2% total (THD) and 1% any single harmonic on 100% linear loads.

5.Voltage Transient (Step Load) Response: + 3% for 50% step load change

+5% for 100% step load change

APC – MGE Galaxy 5000 Specification (60Hz) 4

Effective: June 1, 2008 REV X0 JJG

Parallel Module

 

Image 4
Contents MGE Galaxy General SummaryStandards SubmittalsTemperature Final SubmittalsQualifications & Quality Assurance DELIVERY, STORAGE, and HandlingService and Spare Parts WarrantyMAINTENANCE, Accessibility and Self Diagnostics AC Input Characteristics AC Output CharacteristicsSystem Description UPS Design RequirementsBattery PFC Rectifier and Battery ChargerModes of Operation Component DescriptionInverter Static Bypass 100% Rated, Continuous DutySystem Controls and Indicators Output Static Switch 100% Rated, Continuous DutyMeasurements Status Indications and Events Cabinet Weights and Dimensions The width of the UPS is Mechanical Design and VentilationOptional Accessories BatteryExternal Control and Communications Devices Page Maintenance & Service Contracts Maintenance TrainingSpare Parts END of Section Configuration Battery 100 130 KVA 40 KVA 50 KVA 60 KVA 80 KVA 100 130111 150 182 120 156Entry Battery Weight80 KVA 100 KVA 130 KVA 109 137 164 219 273 355300 lbs 700 lbs