1.Uninterrupted Transfer: The static bypass transfer switch shall automatically cause the bypass source to assume the critical load without interruption after the logic senses one of the following conditions:
a)Inverter overload exceeds unit's rating
b)Battery protection period expired and bypass current is available
c)Inverter failure
2.Interrupted Transfer: If the bypass source is beyond the conditions stated below, the UPS will make an interrupted transfer (not less than 100 mSec in duration).
a)Bypass voltage greater than + 10%,
b)Bypass frequency greater than + 2 Hz from the UPS rated output frequency.
3.Automatic Uninterrupted Forward Transfer: The static bypass transfer switch shall automatically forward transfer power, without interruption, after the UPS inverter is turned "ON" after an instantaneous
4.Manual Transfer: A manual static transfer shall be initiated from the UPS Control Panel by turning the UPS inverter off.
5.Overload Ratings: The static bypass transfer switch shall have the following overload characteristics:
a)1000% of UPS output rating for 0.016 seconds (one cycle)
b)150% for 1 minute
c)125% of UPS for 10 minutes
D.Output Static Switch – 100% Rated, Continuous Duty
UPS output shall be equipped with a 100% rated output static switch without mechanical contactor device in parallel for higher reliability and consistent response time of 16.66 msec.
3.0SYSTEM CONTROLS AND INDICATORS
A.Microprocessor Controlled Logic
• The full UPS operation shall be provided through the use of microprocessor controlled logic. All operation and parameters are firmware controlled, thus eliminating the need for manual adjustments or potentiometers. The logic shall include a
• The UPS will include a standard easy to use control and indicator panel. Included will be a backlit, color graphic animated LCD display and LED indicators. The UPS panel will include UPS “ON” and UPS “OFF” pushbuttons that will permit the user to safely command the UPS on or off without risk of load loss.
• Display shall facilitate operation by offering the functions listed below. o Operating information supplied on the screens.
APC – MGE Galaxy 5000 Specification (60Hz) 7 | Effective: June 1, 2008 REV X0 JJG |
Parallel Module |
|