UPS Module Operating: | 0° to 40°C (32°F to 104°F) |
B.Relative humidity (operating and storage): 0 to 95%
C.Barometric Pressure: Up to 1000 meters above sea level (up to 2000 meters with ambient temperature less than 28°C) / (up to 12,000 meters above sea level non operating)
D. Audible Noise: | 69 dBA at 3 feet |
1.8WARRANTY
A.UPS Module: The UPS shall be covered by a full parts and labor warranty from the manufacturer for a period of twelve (12) months from date of installation or acceptance by customer or eighteen (18) months from date of shipment from the manufacturer, whichever occurs first.
B.Battery: The battery manufacturer’s warranty shall be passed through to the final customer and shall have a minimum period of one year.
1.9SERVICE AND SPARE PARTS
The manufacturer shall, upon request, provide spare parts kits for the UPS module in a timely manner as well as provide access to qualified factory trained first party service personnel to provide preventative maintenance and service on the UPS module when required.
1.10MAINTENANCE, ACCESSIBILITY AND SELF DIAGNOSTICS
All UPS subassemblies, as well as the battery, shall be accessible from the front. UPS design shall provide maximum reliability and minimum MTTR (mean time to repair). To that end, the UPS shall be equipped with a
Extensive acquisition of information vital for
Socket connection to interface with
The UPS shall be repairable by replacing standard subassemblies requiring no adjustments. Communication via a modem with a remote maintenance system shall be possible.
2.0PRODUCT DESCRIPTION
2.1APPROVED MANUFACTURERS & PRODUCT DESCRIPTION
A.Approved Manufacturer(s): The specified equipment will be manufactured by APC by Schneider Electric or approved manufacturer in compliance with specifications.
B.Product Description: This specification describes a
APC – MGE Galaxy 5000 Specification (60Hz) 3 | Effective: June 1, 2008 REV X0 JJG |
Parallel Module |
|