CHAPTER 5 BASIC CONNECTIONS FOR OPERATION

5.1 Connecting single load, Local sensing

Local sensing is suitable for applications where load regulation is not critical. Fig 5-1 shows recommended load and sensing connections for applications with a single load.

 

 

+V

1,2,4

+

 

 

 

FPS1000

 

+S

8

 

 

 

 

LOAD

 

 

 

 

 

 

-S

13

 

SIGNAL

ON/

 

 

-V

 

-

RTN

OFF

3,5,6

10

7

 

 

 

 

 

Fig 5-1: single load connection, local sensing

*In Local sense applications, the +/- sense have to be connected to the +/-V terminals of the FPS1000 units prior the operating the FPS1000 units

5.2 Connecting Single Load, Remote Sensing

Remote sensing is used in cases where the load regulation is important at the load terminals. Use twisted or shielded wires to minimize noise pick-up. If shielded wires are used, the shield should be connected to the ground at one point, either the power supply side or the load. The optimal point for the shield ground should be determined by experimentation. Refer to the power supply specifications for the maximum voltage drop allowed at the load wires.

 

 

 

Load line.

 

 

1,2,4

Up to 1V drop.

 

+V

+

 

8

FPS1000

+S

 

 

 

LOAD

 

 

-S

13

 

SIGNAL

ON/

3,5,6

 

-V

-

RTN

OFF

 

10

7

 

Sense lines

Load line.

 

 

 

Twisted pairs

Up to 1V drop.

Fig 5-2: Remote sensing, single load.

5.3 Connecting Multiple loads, radial distribution method

In cases of multiple loads connected to one supply, each load should be connected to the power supply's output terminals using separate pairs of wires. It is recommended that each pair of wires will be as short as possible and twisted or shielded to minimize noise pick-up and radiation.

The sense wires should be connected to the power supply output terminals or to the load with the most critical load regulation requirement.

 

 

 

 

+V

FPS1000

 

 

+S

SIGNAL

ON/

-S

-V

RTN

OFF

10

 

 

 

 

 

7

 

 

 

 

 

 

1,2,4

+

LOAD # 1

8

-

 

 

13

+

LOAD # 2

-

 

3,5,6

+

 

 

LOAD # 3

 

-

Fig 5-3: Multiple loads connection , radial distribution

14

Image 17
Contents FPS Series 1000W In 1U FPS1000 Series Table of Contents Limitation of Warranty WarrantyWarranty Service DisclaimerFPS1000 Power Supply and FPS-S1U Rack Safety Instructions Safety Symbols FPS1000 Series Specifications Outline Drawings FPS 1000 Series Outline Drawings FPS 1000/P Series Outline Drawings FPS1000 Power Supply Installation Current Carrying Capacity Connecting the LoadLoad Wiring Making the load connections Noise and Impedance EffectsInductive loads Repackaging for Shipment Input/Output connector informationFunctions and Features ACFail signal Dcok signalRemote On/Off control FPS10004.7KΩRemote Sensing Connecting Single Load, Remote Sensing Connecting single load, Local sensingConnecting Multiple loads, radial distribution method Basic Connections for OperationGrounding outputs Multiple loads connection with distribution terminalsParallel operation Parallel and Series OperationParallel operation with Remote sensing Output voltage trimming at parallel operationRemote On/Off control at parallel operation Signal Return bus at parallel operationSeries connection for positive and negative output voltage Series operationI2C BUS Interface Option Eeprom functions Block diagram of the I2C optionOperation and functions 7.4.1. Digital status Output current readback Analog functions4 A/D Scaling FPS1000 Typical application diagramFPS1000 Maintenance FPS-S1U 19 Rack Single Output Maximum output power Chapter FPS-S1U Rack SpecificationsFPS-S1U Rack Mounting FPS-S1U Rack InstallationRear panel description Control and monitoring signals connectorSCL I2C Blank panels Modules locationFPS-S1U and FPS-S1U/P Outline Drawings FPS-S1U/P Outline Drawing Multiple loads connection Basic Connections for Operation FPS-S1U RackOutput voltage trimming Supervisory signals12.4 On/Off control Parallel operation with Remote sensing Output voltage trimming at parallel operation Signal Return bus at parallel operationRemote On/Off control at parallel operation Addressing A0, A1, A2 FPS-S1U I2C BUS Interface OptionIntroduction Units under warranty FPS-S1U MaintenancePeriodic maintenance Adjustments and CalibrationFPS-T1U 19 Rack Triple Output Chapter FPS-T1U Rack SpecificationsFPS-T1U Rack Mounting FPS-T1U Rack InstallationFPS-T1U Rear panel J1A, J2B, J3C Conector Description Modules location FPS-T1U and FPS-T1U/P Outline Drawings FPS-T1U/P Outline Drawing 19.2 On/Off control Basic Connections for Operation FPS-T1U RackOutput Voltag Trimming Load Series operation Module a Module B Module C FPS-T1U I2C BUS Interface OptionFPS-T1U Maintenance