TOA Electronics FPS-S1U, FPS1000-24, FPS1000-12, FPS-T1U Output Voltag Trimming, Grounding outputs

Page 51

19.3 Output Voltag Trimming

Fig 19-4 shows typical output voltage trimming connection for FPS1000 unit ‘A’ inside the rack Units ‘B’ and ‘C’ connections - Refer to 17.7.5

FPS-T1U

+S

J1(A) J1(A)-8

FPS1000-12:

R2=0.0324*V2out -1.1298*Vout+9.9342

FPS1000 Module A

V_TRIM

-S

J1(A)-6

J1(A)-7

R1

R2

R1(KΩ)=5(KΩ)-R2(KΩ)

FPS1000-24:

R2=0.0785*V2out -5.819*Vout+105.132 R1(KΩ)=20(KΩ)-R2(KΩ)

FPS-1000 Module B

FPS-1000 Module C

R1&R2:0.5W

J2(B)

J3(C)

FPS1000-32:

R2=0.0463*V2out -4.5805*Vout+109.49 R1(KΩ)=20(KΩ)-R2(KΩΩ)

FPS1000-48:

R2=0.0497*V2out-7.2795*Vout+259.04 R1(KΩ)=50(KΩ)-R2(KΩ)

Fig 19-4 Output Voltag Trimming

19.4 Supervisory Signals

Signals are accessible at the J1(A), J2(B), J3(C) connectors on the rear panel of the rack Fig 19-5 shows typical connection for FPS1000 unit ‘A’. inside the rack

Units ‘B’ and ‘C’. connections - Refer to 17.7.5

FPS-T1U

FPS1000

12V AUX

Module A

AC_FAIL_A

 

DC_OK_A

 

TEMP.ALARM_A

 

SIGNAL RET

 

 

FPS-1000 Module B

FPS-1000 Module C

J1(A)

 

 

9

 

 

 

11

10K

10K

Application

 

 

5

 

 

Monitoring

14

10K

 

and Control

3circuits

J2(B)

J3(C)

Fig 19-5 Supervisory Signals

Note: AC_FAIL, DC_OK and TEMP.ALARM are open collector signals

19.5 Grounding outputs

Either the positive or negative output terminals can be grounded. To avoid noise problems caused by common-mode current flowing from the load to ground, it is recommended to ground the output terminal as close as possible to the power supply's output. Always use two wires to connect the load to the power supply regardless of how the system is grounded.

48

Image 51
Contents FPS Series 1000W In 1U FPS1000 Series Table of Contents Disclaimer WarrantyLimitation of Warranty Warranty ServiceFPS1000 Power Supply and FPS-S1U Rack Safety Instructions Safety Symbols FPS1000 Series Specifications Outline Drawings FPS 1000 Series Outline Drawings FPS 1000/P Series Outline Drawings FPS1000 Power Supply Installation Connecting the Load Load WiringCurrent Carrying Capacity Noise and Impedance Effects Inductive loadsMaking the load connections Repackaging for Shipment Input/Output connector informationFunctions and Features FPS10004.7KΩ Dcok signalACFail signal Remote On/Off controlRemote Sensing Basic Connections for Operation Connecting single load, Local sensingConnecting Single Load, Remote Sensing Connecting Multiple loads, radial distribution methodGrounding outputs Multiple loads connection with distribution terminalsOutput voltage trimming at parallel operation Parallel and Series OperationParallel operation Parallel operation with Remote sensingRemote On/Off control at parallel operation Signal Return bus at parallel operationSeries connection for positive and negative output voltage Series operationI2C BUS Interface Option Block diagram of the I2C option Operation and functions 7.4.1. Digital statusEeprom functions Analog functions 4 A/D ScalingOutput current readback FPS1000 Typical application diagramFPS1000 Maintenance FPS-S1U 19 Rack Single Output Maximum output power Chapter FPS-S1U Rack SpecificationsFPS-S1U Rack Mounting FPS-S1U Rack InstallationRear panel description Control and monitoring signals connectorSCL I2C Blank panels Modules locationFPS-S1U and FPS-S1U/P Outline Drawings FPS-S1U/P Outline Drawing Multiple loads connection Basic Connections for Operation FPS-S1U RackSupervisory signals 12.4 On/Off controlOutput voltage trimming Parallel operation with Remote sensing Output voltage trimming at parallel operation Signal Return bus at parallel operationRemote On/Off control at parallel operation FPS-S1U I2C BUS Interface Option IntroductionAddressing A0, A1, A2 Adjustments and Calibration FPS-S1U MaintenanceUnits under warranty Periodic maintenanceFPS-T1U 19 Rack Triple Output Chapter FPS-T1U Rack SpecificationsFPS-T1U Rack Mounting FPS-T1U Rack InstallationFPS-T1U Rear panel J1A, J2B, J3C Conector Description Modules location FPS-T1U and FPS-T1U/P Outline Drawings FPS-T1U/P Outline Drawing 19.2 On/Off control Basic Connections for Operation FPS-T1U RackOutput Voltag Trimming Load Series operation Module a Module B Module C FPS-T1U I2C BUS Interface OptionFPS-T1U Maintenance