CHAPTER 1 FPS1000 SERIES SPECIFICATIONS
| FPS1000 SERIES SPECIFICATIONS |
|
|
|
|
|
| ||||||
1 | Rated output voltage |
| V | 12 |
| 24 |
| 32 |
|
| 48 | ||
2 | Output voltage set point |
| V |
|
|
|
| ||||||
3 | Output voltage range |
| V | 10.5~13.2 |
| 21.5~29 |
| 28.8~38.4 |
|
| 43~58 | ||
4 | Maximum Output Current (Refer to Fig.1) |
| A | 72 |
| 40 |
| 31 |
|
| 21 | ||
5 | Maximum output power |
| W | 864 |
| 960 |
| 992 |
|
| 1008 | ||
6 | Input voltage / frequency range | (*1) |
|
|
| 85~265Vac continuous, 47~63Hz, Single phase |
| ||||||
7 | Maximum input current (at 100/200Vac) |
| A |
|
|
|
| 12.0/6.0 |
|
|
| ||
8 | Power Factor (Typ) |
|
| >0.98 at 115/230V and maximum output power |
| ||||||||
9 | Efficiency (Typ) | (*2) | % | 81/83% |
|
| 84/86% |
|
| 84/86% |
|
| 85/88% |
10 | Inrush current | (*3) | A |
|
|
| Less than 40A |
| |||||
11 |
| mS | 20mS typical at 100Vac input, rated output voltage and less than 80% of rated load. | ||||||||||
12 | Maximum line regulation | (*5) |
|
|
|
| 0.40% |
|
|
| |||
13 | Max load regulation | (*6) |
|
|
|
| 0.80% |
|
|
| |||
14 | Output Ripple and noise | (*4) | mV | 150 |
|
| 200 |
|
| 250 |
|
| 300 |
|
|
|
| ||||||||||
15 | Temperature stability |
| 0.05% of rated Vout for 8hrs after 30min | ||||||||||
16 | Temperature coefficient |
| PPM/°C |
|
|
|
| 200 |
|
|
| ||
17 | Remote sensing | (*7) | V |
|
|
| Possible. Refer to Instruction Manual. |
| |||||
18 | Parallel operation | (*9) |
|
|
| Possible. Refer to Instruction Manual. |
| ||||||
19 | Series operation |
|
|
|
| Possible. Refer to Instruction Manual. |
| ||||||
20 | Over current protection |
|
| 105~125% of maximum output current. Refer to Fig. 1 | |||||||||
21 | Over voltage protection | (*8) | V | 14.3~15.7 | 31~34 |
|
| 41.5~45.5 |
|
| 62~66 | ||
22 | Over temperature protection |
|
|
|
| Inverter shut down method, automatic reset. |
| ||||||
23 | Remote On/Off control |
| By electrical signal or dry contact. ON: 0~0.6V or short. OFF: 2~15V or open. | ||||||||||
24 | DC OK signal |
| Open collector signal. On when | ||||||||||
25 |
|
| Open collector signal. Refer to Instruction Manual |
| |||||||||
26 | AC fail signal |
|
| Open collector signal. Refer to Instruction Manual |
| ||||||||
27 | Auxiliary power supply |
|
|
|
| 11.2~12.5VDC. 0.25A Maximum output current. |
| ||||||
28 | Vout voltage trimming |
| Possible, via Vout Trim pin in the I/O connector. Refer to Instruction Manual. | ||||||||||
29 | Front panel indicators |
|
|
|
| AC OK, DC OK, DC FAIL |
| ||||||
30 | I2C Interface |
|
|
|
| Optional. Refer to Instruction Manual. |
| ||||||
31 | Operating | 0~50°C: 100% load. Derate 2%/°C, 50°C to 60°C, Derate 2.5%/°C, 60°C to 70°C. | |||||||||||
| models with IEC inlet |
| 0~50°C: 100% load. Derate 2%/°C, 50°C to 60°C. |
| |||||||||
32 | Storage temperature |
|
|
|
|
|
| ||||||
33 | Operating humidity |
|
|
|
| 10~90% RH, no condensation. |
| ||||||
34 | Storage humidity |
|
|
|
| 10~95% RH, no condensation. |
| ||||||
35 | Cooling |
|
|
|
| By internal Fans. Variable speed control. |
| ||||||
36 | Vibration |
|
|
|
| Built to meet ETS 300 019 |
| ||||||
37 | Shock |
|
|
|
| Built to meet ETS 300 019 |
| ||||||
38 | Conducted emission | (*10) |
|
|
| EN55022B, FCC part |
| ||||||
39 | Radiated emission |
|
|
|
| EN55022B, FCC part |
| ||||||
40 | Applicable safety standards |
|
|
|
|
| |||||||
41 | Withstand voltage |
| |||||||||||
42 | Insulation resistance |
| More than 100Mohm at 25° C and 70% RH. | ||||||||||
43 | Leakage current |
| mA |
|
|
| Less Than 1.1mA at 230Vac |
| |||||
44 | Weight (Typ) |
| Kg |
|
|
|
| 2.0 |
|
|
| ||
45 | Size (W*H*D) |
|
|
|
| 127x41x290mm. Refer to Outline Drawing. |
|
Notes:
*1: For cases where conformance to various safety standards (UL, EN etc.) is required, to be described as
*2: At 100/200Vac, rated load and 25˚C ambient temperature.
*3: Not applicable for the noise filter inrush current less than 0.2mS.
*4: Measured with JEITA
*5: From 85~132Vac or 170~265Vac, constant load.
*6: From
*7: Remote sensing can compensate up to 1V drop on each load wire.
*8: Inverter shut down method. Reset by AC voltage recycle or by On/Off control.
*9: Derate Maximum output power by 10% for input voltage less than 100V RMS.
*10 For FPS
Vout (V)
V2
Model | FPS1000 | FPS1000 | FPS1000 | FPS1000 |
V/I | ||||
V1 (V) | 12 | 24 | 32 | 48 |
V2 (V) | 13.2 | 29 | 38.4 | 58 |
I1 (A) | 66 | 33 | 26 | 17.25 |
I2 (A) | 72 | 40 | 31 | 21 |
V1
I1 | I2 | Iout (A) |
|
Fig. 1: Rated output current vs output voltage