TOA Electronics FPS1000-12, FPS1000-24, FPS1000-32, FPS-S1U, FPS-T1U FPS1000 Series Specifications

Page 7

CHAPTER 1 FPS1000 SERIES SPECIFICATIONS

 

FPS1000 SERIES SPECIFICATIONS

 

FPS1000-12

 

 

FPS1000-24

 

 

FPS1000-32

 

FPS1000-48

1

Rated output voltage

 

V

12

 

24

 

32

 

 

48

2

Output voltage set point

 

V

12+/-1%

 

24+/-1%

 

32+/-1%

 

 

48+/-1%

3

Output voltage range

 

V

10.5~13.2

 

21.5~29

 

28.8~38.4

 

 

43~58

4

Maximum Output Current (Refer to Fig.1)

 

A

72

 

40

 

31

 

 

21

5

Maximum output power

 

W

864

 

960

 

992

 

 

1008

6

Input voltage / frequency range

(*1)

---

 

 

 

85~265Vac continuous, 47~63Hz, Single phase

 

7

Maximum input current (at 100/200Vac)

 

A

 

 

 

 

12.0/6.0

 

 

 

8

Power Factor (Typ)

 

---

 

>0.98 at 115/230V and maximum output power

 

9

Efficiency (Typ)

(*2)

%

81/83%

 

 

84/86%

 

 

84/86%

 

 

85/88%

10

Inrush current

(*3)

A

 

 

 

Less than 40A

 

11

Hold-up time

 

mS

20mS typical at 100Vac input, rated output voltage and less than 80% of rated load.

12

Maximum line regulation

(*5)

---

 

 

 

 

0.40%

 

 

 

13

Max load regulation

(*6)

---

 

 

 

 

0.80%

 

 

 

14

Output Ripple and noise pk-pk

(*4)

mV

150

 

 

200

 

 

250

 

 

300

 

 

 

 

15

Temperature stability

 

---

0.05% of rated Vout for 8hrs after 30min warm-up. Constant line, load and temperature.

16

Temperature coefficient

 

PPM/°C

 

 

 

 

200

 

 

 

17

Remote sensing

(*7)

V

 

 

 

Possible. Refer to Instruction Manual.

 

18

Parallel operation

(*9)

---

 

 

 

Possible. Refer to Instruction Manual.

 

19

Series operation

 

---

 

 

 

Possible. Refer to Instruction Manual.

 

20

Over current protection

 

---

 

105~125% of maximum output current. Refer to Fig. 1

21

Over voltage protection

(*8)

V

14.3~15.7

31~34

 

 

41.5~45.5

 

 

62~66

22

Over temperature protection

 

---

 

 

 

Inverter shut down method, automatic reset.

 

23

Remote On/Off control

 

---

By electrical signal or dry contact. ON: 0~0.6V or short. OFF: 2~15V or open.

24

DC OK signal

 

---

Open collector signal. On when Vout>80+/-5% rated output. Max.sink current: 10mA

25

Over-Temp. warning

 

---

 

Open collector signal. Refer to Instruction Manual

 

26

AC fail signal

 

---

 

Open collector signal. Refer to Instruction Manual

 

27

Auxiliary power supply

 

---

 

 

 

11.2~12.5VDC. 0.25A Maximum output current.

 

28

Vout voltage trimming

 

---

Possible, via Vout Trim pin in the I/O connector. Refer to Instruction Manual.

29

Front panel indicators

 

---

 

 

 

AC OK, DC OK, DC FAIL

 

30

I2C Interface

 

---

 

 

 

Optional. Refer to Instruction Manual.

 

31

Operating temperature-models without IEC inlet

---

0~50°C: 100% load. Derate 2%/°C, 50°C to 60°C, Derate 2.5%/°C, 60°C to 70°C.

 

models with IEC inlet

---

 

0~50°C: 100% load. Derate 2%/°C, 50°C to 60°C.

 

32

Storage temperature

 

---

 

 

 

 

-30~85°C

 

33

Operating humidity

 

---

 

 

 

10~90% RH, no condensation.

 

34

Storage humidity

 

---

 

 

 

10~95% RH, no condensation.

 

35

Cooling

 

---

 

 

 

By internal Fans. Variable speed control.

 

36

Vibration

 

---

 

 

 

Built to meet ETS 300 019

 

37

Shock

 

---

 

 

 

Built to meet ETS 300 019

 

38

Conducted emission

(*10)

---

 

 

 

EN55022B, FCC part 15J-B, VCCI-B

 

39

Radiated emission

 

---

 

 

 

EN55022B, FCC part 15J-B, VCCI-B

 

40

Applicable safety standards

 

---

 

 

 

UL60950-1, EN60950-1

 

41

Withstand voltage

 

---

Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. Output-Ground: 500Vrms,1min.

42

Insulation resistance

 

---

More than 100Mohm at 25° C and 70% RH. Output-Ground: 500Vdc

43

Leakage current

 

mA

 

 

 

Less Than 1.1mA at 230Vac

 

44

Weight (Typ)

 

Kg

 

 

 

 

2.0

 

 

 

45

Size (W*H*D)

 

---

 

 

 

127x41x290mm. Refer to Outline Drawing.

 

Notes:

*1: For cases where conformance to various safety standards (UL, EN etc.) is required, to be described as 100-240Vac (50/60Hz).

*2: At 100/200Vac, rated load and 25˚C ambient temperature.

*3: Not applicable for the noise filter inrush current less than 0.2mS.

*4: Measured with JEITA RC-9131A 1:1 probe, 20MHz B.W.

*5: From 85~132Vac or 170~265Vac, constant load.

*6: From No-load to Rated load, constant input voltage. Measured at the sensing point in Remote sense.

*7: Remote sensing can compensate up to 1V drop on each load wire.

*8: Inverter shut down method. Reset by AC voltage recycle or by On/Off control.

*9: Derate Maximum output power by 10% for input voltage less than 100V RMS.

*10 For FPS 1000-12/P(S), when used not with FPS-S1U or FPS-T1U racks, an EMI suppressor clamp should be attached to the AC cable, as close as possible to the AC inlet, to meet class B.

Vout (V)

V2

Model

FPS1000

FPS1000

FPS1000

FPS1000

V/I

-12

-24

-32

-48

V1 (V)

12

24

32

48

V2 (V)

13.2

29

38.4

58

I1 (A)

66

33

26

17.25

I2 (A)

72

40

31

21

V1

I1

I2

Iout (A)

 

Fig. 1: Rated output current vs output voltage

4

Image 7
Contents FPS Series 1000W In 1U FPS1000 Series Table of Contents Disclaimer WarrantyLimitation of Warranty Warranty ServiceFPS1000 Power Supply and FPS-S1U Rack Safety Instructions Safety Symbols FPS1000 Series Specifications Outline Drawings FPS 1000 Series Outline Drawings FPS 1000/P Series Outline Drawings FPS1000 Power Supply Installation Load Wiring Connecting the LoadCurrent Carrying Capacity Inductive loads Noise and Impedance EffectsMaking the load connections Repackaging for Shipment Input/Output connector informationFunctions and Features FPS10004.7KΩ Dcok signalACFail signal Remote On/Off controlRemote Sensing Basic Connections for Operation Connecting single load, Local sensingConnecting Single Load, Remote Sensing Connecting Multiple loads, radial distribution methodGrounding outputs Multiple loads connection with distribution terminalsOutput voltage trimming at parallel operation Parallel and Series OperationParallel operation Parallel operation with Remote sensingRemote On/Off control at parallel operation Signal Return bus at parallel operationSeries connection for positive and negative output voltage Series operationI2C BUS Interface Option Operation and functions 7.4.1. Digital status Block diagram of the I2C optionEeprom functions 4 A/D Scaling Analog functionsOutput current readback FPS1000 Typical application diagramFPS1000 Maintenance FPS-S1U 19 Rack Single Output Maximum output power Chapter FPS-S1U Rack SpecificationsFPS-S1U Rack Mounting FPS-S1U Rack InstallationRear panel description Control and monitoring signals connectorSCL I2C Blank panels Modules locationFPS-S1U and FPS-S1U/P Outline Drawings FPS-S1U/P Outline Drawing Multiple loads connection Basic Connections for Operation FPS-S1U Rack12.4 On/Off control Supervisory signalsOutput voltage trimming Parallel operation with Remote sensing Output voltage trimming at parallel operation Signal Return bus at parallel operationRemote On/Off control at parallel operation Introduction FPS-S1U I2C BUS Interface OptionAddressing A0, A1, A2 Adjustments and Calibration FPS-S1U MaintenanceUnits under warranty Periodic maintenanceFPS-T1U 19 Rack Triple Output Chapter FPS-T1U Rack SpecificationsFPS-T1U Rack Mounting FPS-T1U Rack InstallationFPS-T1U Rear panel J1A, J2B, J3C Conector Description Modules location FPS-T1U and FPS-T1U/P Outline Drawings FPS-T1U/P Outline Drawing 19.2 On/Off control Basic Connections for Operation FPS-T1U RackOutput Voltag Trimming Load Series operation Module a Module B Module C FPS-T1U I2C BUS Interface OptionFPS-T1U Maintenance