FPS-S1U Instruction Manual
13.1.2 Output voltage trimming at parallel operation
The output voltage of the units connected in parallel can be made by a single trimmer or resistive divider.
| | | | V_TRIM | 7 | | | | |
| | | | 1 | | | | |
FPS-S1U # 1 | | | A, B, C | 10 | | | | |
| | ON/ ON/ +S | | | | | |
| | | ON/ | | V_TRIM | | | |
| SIG. | | OFF | OFF OFF | | | | |
CS | | A | B | C -S | | | | V_TRIM | |
RTN | | | | | |
9 | | 5 | 15 | | 25 | | | | |
11 | | | | | V_TRIM |
| | | | V_TRIM | 7 | V_TRIM | +V | +S | |
| | | | 1 | |
| | | | | |
FPS-S1U # 2 | | | A, B, C | 10 | | | | R1 |
| | | | | | | |
| | ON/ ON/ +S | | | | | |
| | | ON/ | | | | | |
| SIG. | | OFF | OFF OFF | | | | | R2 |
CS | | A | B | C -S | | | | -S |
RTN | | | | -V |
9 | 11 | 5 | 15 | | 25 | | | | |
| | V_TRIM | | | |
| | | | | | | | | |
FPS-S1U # 3
| | | | ON/ | ON/ ON/+S |
| | SIG. | | OFF | OFF OFF |
| CS | A | B | C -S |
| RTN |
| 9 | 11 | 5 | 15 | 25 |
Fig 13-3: Output voltage trimming at parallel operation
FPS-S1U with FPS1000-12 installed: R2=0.0324*V2out -1.1298*Vout+9.9342 R1(KΩ)=5(KΩ)-R2(KΩ)
FPS-S1U with FPS1000-24 installed: R2=0.0785*V2out -5.819*Vout+105.132 R1(KΩ)=20(KΩ)-R2(KΩ)
FPS-S1U with FPS1000-32 installed: R2=0.0463*V2out -4.5805*Vout+109.49 R1(KΩ)=20(KΩ)-R2(KΩΩ)
FPS-S1U with FPS1000-48 installed: R2=0.0497*V2out-7.2795*Vout+259.04 R1(KΩ)=50(KΩ)-R2(KΩ)
13.1.3 Signal Return bus at parallel operation
The Signal Return of each paralleled FPS-S1U rack can be connected together to form a common Signal Return bus. By this way, the control and monitoring signals of the paralleled racks can be connected to the same control and monitoring circuitry. The Signal Return bus can be connected to the -V or -S or +V or -S or float. Fig 13-4 shows typical connection of the Signal Return at parallel operation.
FPS-S1U #1 AC_FAIL 
DC_OK
OVER-TEMP 
ALARM
FPS-S1U #2 AC_FAIL 
DC_OK
OVER-TEMP
ALARM
FPS-S1U #3 AC_FAIL 
DC_OK
OVER-TEMP 
ALARM
CONTROL AND MONITORING CIRCUITS
FPS-S1U #1 SIGNALS
FPS-S1U #2 SIGNALS
FPS-S1U #3 SIGNALS
SIGNALS RETURN
Fig 13-4: Signal Return connection at parallel operation