CHAPTER 12 BASIC CONNECTIONS FOR OPERATION FPS-S1U RACK

12.1 Connecting single load, Local sensing

Local sensing is suitable for applications where load regulation is not critical. Fig 12-1 shows recommended load and sensing connections for applications with a single load.

FPS-S1U

 

 

 

+V

 

+V

 

 

 

+S

 

 

 

 

 

 

13

 

 

 

 

 

 

LOAD

 

 

 

 

 

 

 

ON/

ON/

ON/

-S

22

 

SIGNAL

 

 

OFF

OFF

OFF

-V

 

 

RTN

A

B

C

 

-V

11

5

15

25

 

 

 

Fig 12-1: single load connection, local sensing

*In Local sense applications, the +/- sense have to be connected to the

+/-V terminals of the FPS-S1U prior to operating the FPS1000 units plugged in.

12.2 Connecting Single Load, Remote Sensing

Remote sensing is used in cases where the load regulation is important at the load terminals. Use twisted or shielded wires to minimize noise pick-up. If shielded wires are used, the shield should be connected to the ground at one point, either the power supply side or the load. The optimal point for the shield ground should be determined by experimentation. Refer to the power supply specifications for the maximum voltage drop allowed at the load wires.

+V

FPS-S1U+S

SIGNAL

ON/

ON/

ON/

-S

OFF

OFF

OFF

-V

RET

A

B

C

 

 

5

 

15

 

 

 

 

11

 

 

 

25

 

 

 

 

 

 

 

 

 

 

Load line. Up to 1V drop.

 

+V

13

*

LOAD

22

 

 

-V

Sense lines

Load line.

Twisted pairs

Up to 1V drop.

Fig 12-2: Remote sensing, single load.

12.3 Multiple loads connection

If remotely located output distribution terminals are used, the power supply output terminals should be connected to the distribution terminals by a pair of twisted or shielded wires. Each load should be separately connected to the remote distribution terminals (see Fig 12-3). If remote sensing is required, the sensing wires should be connected to the distribution terminals or at the most critical load.

+V

 

 

 

 

+V

 

FPS-S1U

 

 

+S

13

 

 

 

 

 

 

ON/ ON/ ON/

-S

22

SIGNAL

 

OFF

OFF

OFF

-V

 

RET

A

B

C

 

11

5

15

25

-V

 

 

 

 

 

+

-LOAD # 1

+

-LOAD # 2

+

-LOAD # 3

Fig 12-3: Multiple loads connection with distribution terminal

32

Image 35
Contents FPS Series 1000W In 1U FPS1000 Series Table of Contents Disclaimer WarrantyLimitation of Warranty Warranty ServiceFPS1000 Power Supply and FPS-S1U Rack Safety Instructions Safety Symbols FPS1000 Series Specifications Outline Drawings FPS 1000 Series Outline Drawings FPS 1000/P Series Outline Drawings FPS1000 Power Supply Installation Current Carrying Capacity Connecting the LoadLoad Wiring Making the load connections Noise and Impedance EffectsInductive loads Repackaging for Shipment Input/Output connector informationFunctions and Features FPS10004.7KΩ Dcok signalACFail signal Remote On/Off controlRemote Sensing Basic Connections for Operation Connecting single load, Local sensingConnecting Single Load, Remote Sensing Connecting Multiple loads, radial distribution methodGrounding outputs Multiple loads connection with distribution terminalsOutput voltage trimming at parallel operation Parallel and Series OperationParallel operation Parallel operation with Remote sensingRemote On/Off control at parallel operation Signal Return bus at parallel operationSeries connection for positive and negative output voltage Series operationI2C BUS Interface Option Eeprom functions Block diagram of the I2C optionOperation and functions 7.4.1. Digital status Output current readback Analog functions4 A/D Scaling FPS1000 Typical application diagramFPS1000 Maintenance FPS-S1U 19 Rack Single Output Maximum output power Chapter FPS-S1U Rack SpecificationsFPS-S1U Rack Mounting FPS-S1U Rack InstallationRear panel description Control and monitoring signals connectorSCL I2C Blank panels Modules locationFPS-S1U and FPS-S1U/P Outline Drawings FPS-S1U/P Outline Drawing Multiple loads connection Basic Connections for Operation FPS-S1U RackOutput voltage trimming Supervisory signals12.4 On/Off control Parallel operation with Remote sensing Output voltage trimming at parallel operation Signal Return bus at parallel operationRemote On/Off control at parallel operation Addressing A0, A1, A2 FPS-S1U I2C BUS Interface OptionIntroduction Adjustments and Calibration FPS-S1U MaintenanceUnits under warranty Periodic maintenanceFPS-T1U 19 Rack Triple Output Chapter FPS-T1U Rack SpecificationsFPS-T1U Rack Mounting FPS-T1U Rack InstallationFPS-T1U Rear panel J1A, J2B, J3C Conector Description Modules location FPS-T1U and FPS-T1U/P Outline Drawings FPS-T1U/P Outline Drawing 19.2 On/Off control Basic Connections for Operation FPS-T1U RackOutput Voltag Trimming Load Series operation Module a Module B Module C FPS-T1U I2C BUS Interface OptionFPS-T1U Maintenance