TOA Electronics FPS1000-12, FPS1000-24, FPS1000-32, FPS-S1U, FPS-T1U, FPS1000-48 SCL I2C

Page 31

10.7.5 Control and monitoring signals connector

9

CS

Current sharing signal. When FPS-S1U racks are connected in parallel, the CS pins

 

 

of the units should be connected to allow current balance between units.

 

 

 

10

V_TRIM_C

Connection for output voltage trimming of FPS1000 unit "C". The voltage can be

 

 

trimmed within its range specifications.

 

 

 

11

SIGNAL_RETURN

Return for the following control and supervisory signals: On/Off, DC_OK,

 

 

Over_temperature Alarm, AC_Fail, Auxiliary 12V supply. The Signal return is isolated

 

 

from the output terminals.

 

 

 

12

DC_OK_C

Open collector signal, referenced to pin 11 (Signal Return). On when the output voltage

 

 

of FPS1000 unit "C” is higher than 80%+/-5%. The maximum sink current: 10mA

 

 

and the maximum external voltage is 15V.

 

 

 

13

+SENSE

Positive sensing. The +Sense signal should be connected to the positive terminal of

 

 

the load. The +Sense and -Sense leads should be twisted pair to minimize noise pick-

 

 

up effect. The maximum load wires drop compensation is 1V/wire.

 

 

 

14

AC_FAIL_B

Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage

 

 

of FPS1000 unit "B" is 85Vrms. The maximum sink current is 10mA, and the maximum

 

 

external voltage is 15Vdc.

 

 

 

15

ON/OFF_B

Turns the output of FPS1000 unit "B" to On and Off by electrical signal or dry contact

 

 

between pin 15 and pin 11 (Signal Return). 0~0.6V or Short: On, 2~15V or Open:

 

 

Off. The maximum source current is 2.6mA.

 

 

 

16

AC_FAIL_A

Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage

 

 

of FPS1000 unit "A" is 85Vrms. The maximum sink current is 10mA, and the maximum

 

 

external voltage is 15Vdc.

 

 

 

17

NC

Not connected

18

NC

Not connected

 

 

 

19

NC

Not connected

 

 

 

20

SCL (I2C)

Serial Clock used in the I2C interface option. Refer to the I2C interface description in

 

 

the Chapter 7 in this Instruction Manual.

 

 

 

21

SDA (I2C)

Serial Data used in the I2C interface option. Refer to the I2C interface description in

 

 

the Chapter 7 in this Instruction Manual.

 

 

 

22

-SENSE

Negative sensing. The -Sense signal should be connected to the negative terminal

 

 

of the load. The -Sense and +Sense leads should be twisted pair to minimize noise

 

 

pick-up effect. The maximum load wires drop compensation is 1V/wire.

 

 

 

23

TEMP_ALARM_C

Open collector signal, referenced to pin 11 (Signal Return). On when the internal temperature

 

 

of FPS1000 unit "C" is within safe limit, Off approx 10°C below Thermal shut down. The

 

 

maximum sink current is 10mA and the maximum external voltage is 15V.

 

 

 

24

AC_FAIL_C

Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage

 

 

of FPS1000 unit "C" is 85Vrms. The maximum sink current is 10mA, and the maximum

 

 

external voltage is 15Vdc.

 

 

 

25

ON/OFF_C

Turns the output of FPS1000 unit "C" to On and Off by electrical signal or dry contact

 

 

between pin 25 and pin 11 (Signal Return). 0~0.6V or Short: On, 2~15V or Open: Off.

 

 

The maximum source current is 2.6mA.

 

 

 

28

Image 31
Contents FPS Series 1000W In 1U FPS1000 Series Table of Contents Disclaimer WarrantyLimitation of Warranty Warranty ServiceFPS1000 Power Supply and FPS-S1U Rack Safety Instructions Safety Symbols FPS1000 Series Specifications Outline Drawings FPS 1000 Series Outline Drawings FPS 1000/P Series Outline Drawings FPS1000 Power Supply Installation Load Wiring Connecting the LoadCurrent Carrying Capacity Inductive loads Noise and Impedance EffectsMaking the load connections Repackaging for Shipment Input/Output connector informationFunctions and Features FPS10004.7KΩ Dcok signalACFail signal Remote On/Off controlRemote Sensing Basic Connections for Operation Connecting single load, Local sensingConnecting Single Load, Remote Sensing Connecting Multiple loads, radial distribution methodGrounding outputs Multiple loads connection with distribution terminalsOutput voltage trimming at parallel operation Parallel and Series OperationParallel operation Parallel operation with Remote sensingRemote On/Off control at parallel operation Signal Return bus at parallel operationSeries connection for positive and negative output voltage Series operationI2C BUS Interface Option Operation and functions 7.4.1. Digital status Block diagram of the I2C optionEeprom functions 4 A/D Scaling Analog functionsOutput current readback FPS1000 Typical application diagramFPS1000 Maintenance FPS-S1U 19 Rack Single Output Maximum output power Chapter FPS-S1U Rack SpecificationsFPS-S1U Rack Mounting FPS-S1U Rack InstallationRear panel description Control and monitoring signals connectorSCL I2C Blank panels Modules locationFPS-S1U and FPS-S1U/P Outline Drawings FPS-S1U/P Outline Drawing Multiple loads connection Basic Connections for Operation FPS-S1U Rack12.4 On/Off control Supervisory signalsOutput voltage trimming Parallel operation with Remote sensing Output voltage trimming at parallel operation Signal Return bus at parallel operationRemote On/Off control at parallel operation Introduction FPS-S1U I2C BUS Interface OptionAddressing A0, A1, A2 Adjustments and Calibration FPS-S1U MaintenanceUnits under warranty Periodic maintenanceFPS-T1U 19 Rack Triple Output Chapter FPS-T1U Rack SpecificationsFPS-T1U Rack Mounting FPS-T1U Rack InstallationFPS-T1U Rear panel J1A, J2B, J3C Conector Description Modules location FPS-T1U and FPS-T1U/P Outline Drawings FPS-T1U/P Outline Drawing 19.2 On/Off control Basic Connections for Operation FPS-T1U RackOutput Voltag Trimming Load Series operation Module a Module B Module C FPS-T1U I2C BUS Interface OptionFPS-T1U Maintenance