TOA Electronics FPS1000-12, FPS1000-24, FPS1000-32, FPS-S1U Chapter, FPS-T1U Rack Specifications

Page 43

CHAPTER 16

FPS-T1U RACK SPECIFICATIONS

 

 

 

 

1

Number of power supply modules

(*1)

---

 

Maximum 3 x FPS1000 modules.

 

2

Maximum output power

(*2)

W

 

3000

 

 

 

3

Input voltage / frequency range

(*3)

---

85~265Vac continuous, 47~63Hz, Single phase

4

Maximum input current (at 100/200Vac)

A

12.0/6.0 for each FPS1000 unit installed

 

5

AC input connector

 

---

FPS-T1U :IEC inlet for each power supply module . FPS-T1U/P :None

6

Output terminals

 

 

---

 

Bus-bars.Refer to outline drawing.

 

7

Remote sensing

 

(*4)

V

 

Possible.

 

 

 

8

Parallel operation

 

---

Possible. Up to 3 racks with max 8FPS 1000 units of the same voltage and current rating.

9

Series operation

 

(*5)

---

Possible. Up to 3x FPS1000 units of the same voltage and current rating

10

Remote On/Off control

(*6)

---

Separate control for each FPS 1000 unit , By electrical signal or dry contact

On/Off logic is user selectable. Refer to instruction manual.

 

 

 

 

 

11

DC_OK signal

 

 

---

Separate control for each FPS1000 unit, Open collector signal.

 

 

On when Vout >80% +/-5%. Max.sink current: 10mA

 

 

 

 

 

12

AC fail signal

 

 

---

Separate control for each FPS1000 unit ,Open collector signal.

 

 

 

Refer to Instruction Manual

 

 

 

 

 

 

 

 

13

Over Temperature alarm signal

 

---

Separate control for each FPS1000 unit ,Open collector signal.

 

 

Refer to Instruction Manual

 

 

 

 

 

 

 

 

14

Vout voltage trimming

 

---

Possible, via separate control for each FPS1000 unit .Refer to Instruction Manual.

15

Auxiliary power supply

 

---

11.2~12.5VDC.Maximum output current:0.25A, for each FPS1000 unit.

16

Operating temperature

 

---

°

 

°

°

°

 

 

 

 

 

0~50 C: 100% load. Derate 2%/

 

C, 50 C to 60 C.

17

Storage temperature

 

---

 

°

 

 

 

 

 

 

 

 

 

-30~85 C

 

 

 

18

Operating humidity

 

---

 

10~90% RH, no condensation.

 

19

Storage humidity

 

---

 

10~95% RH, no condensation.

 

20

Vibration

 

 

---

 

Built to meet ETS 300 019

 

21

Shock

 

 

---

 

Built to meet ETS 300 019

 

22

Applicable safety standards

 

---

 

UL60950-1, EN60950-1

 

23

Withstand voltage

 

---

Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. Output-Ground:

 

 

1414Vdc, 1min.

 

 

 

 

 

 

 

 

 

 

24

Insulation resistance

 

---

 

°

 

 

 

 

 

 

 

 

More than 100Mohm at 25 C and 70% RH. Output-Ground: 500Vdc

25

Weight (Typ)

 

 

Kg

 

3.7

 

 

 

26

Size (W*H*D)

 

 

---

440x44x351mm. Refer to Outline Drawing.

27

Warranty

 

 

Yr

 

Two Years

 

 

 

Notes:

*1: The Output of all the FPS1000 modules are floating in the rack.

*2: For input voltage lower than 100Vac, maximum output power derated by 10% of the power rating.

*3: For cases where conformance to to various safety standards (UL, EN etc.) is required, to be described as 100-240Vac (50/60Hz).

*4: Remote sensing can compensate up to 1V drop on each load wire.

*5: Not apllicable for units with I2C bus option.

*6: Factory default: ON/OFF_1 P.S. is On when AC is applied.

40

Image 43
Contents FPS Series 1000W In 1U FPS1000 Series Table of Contents Disclaimer WarrantyLimitation of Warranty Warranty ServiceFPS1000 Power Supply and FPS-S1U Rack Safety Instructions Safety Symbols FPS1000 Series Specifications Outline Drawings FPS 1000 Series Outline Drawings FPS 1000/P Series Outline Drawings FPS1000 Power Supply Installation Load Wiring Connecting the LoadCurrent Carrying Capacity Inductive loads Noise and Impedance EffectsMaking the load connections Repackaging for Shipment Input/Output connector informationFunctions and Features FPS10004.7KΩ Dcok signalACFail signal Remote On/Off controlRemote Sensing Basic Connections for Operation Connecting single load, Local sensingConnecting Single Load, Remote Sensing Connecting Multiple loads, radial distribution methodGrounding outputs Multiple loads connection with distribution terminalsOutput voltage trimming at parallel operation Parallel and Series OperationParallel operation Parallel operation with Remote sensingRemote On/Off control at parallel operation Signal Return bus at parallel operationSeries connection for positive and negative output voltage Series operationI2C BUS Interface Option Operation and functions 7.4.1. Digital status Block diagram of the I2C optionEeprom functions 4 A/D Scaling Analog functionsOutput current readback FPS1000 Typical application diagramFPS1000 Maintenance FPS-S1U 19 Rack Single Output Maximum output power Chapter FPS-S1U Rack SpecificationsFPS-S1U Rack Mounting FPS-S1U Rack InstallationRear panel description Control and monitoring signals connectorSCL I2C Blank panels Modules locationFPS-S1U and FPS-S1U/P Outline Drawings FPS-S1U/P Outline Drawing Multiple loads connection Basic Connections for Operation FPS-S1U Rack12.4 On/Off control Supervisory signalsOutput voltage trimming Parallel operation with Remote sensing Output voltage trimming at parallel operation Signal Return bus at parallel operationRemote On/Off control at parallel operation Introduction FPS-S1U I2C BUS Interface OptionAddressing A0, A1, A2 Adjustments and Calibration FPS-S1U MaintenanceUnits under warranty Periodic maintenanceFPS-T1U 19 Rack Triple Output Chapter FPS-T1U Rack SpecificationsFPS-T1U Rack Mounting FPS-T1U Rack InstallationFPS-T1U Rear panel J1A, J2B, J3C Conector Description Modules location FPS-T1U and FPS-T1U/P Outline Drawings FPS-T1U/P Outline Drawing 19.2 On/Off control Basic Connections for Operation FPS-T1U RackOutput Voltag Trimming Load Series operation Module a Module B Module C FPS-T1U I2C BUS Interface OptionFPS-T1U Maintenance