3.7 CONNECTING THE LOAD

WARNING

Turn off the AC input power before making or changing any rear panel connection. Ensure that all connections are securely tightened before applying power. There is a potential shock hazard when using a power supply with a rated output greater than 40V.

3.7.1 Load Wiring.

The following considerations should be made to select wiring for connecting the load to the power supply: * Current carrying capacity of the wire (refer to 3.7.2).

*Insulation rating of the wire should be at least equivalent to the maximum output voltage of the power supply.

*Maximum wire length and voltage drop (refer to 3.7.2).

*Noise and impedance effects of the load wiring (refer to 3.7.3).

3.7.2 Current Carrying Capacity

Two factors should must be considered while selecting the wire size. 1.Wires should be at least heavy enough not to overheating while carrying the power supply load current at the rated load, or the current that would flow in the event the load wires were shorted, whichever is greater.

2.Wire size should be selected to enable voltage drop per lead to be less than 1.0V at the rated current. Please refer to Tables 3-2 and 3-3 for maximum wire length to limit the voltage drop in American and European dimensions respectively.

wire size

Resistivity

Maximum length in Feet to limit voltage

 

 

AWG

Ohm/kft

drop to 1V or less.

 

 

 

 

 

 

5A

10A

20A

 

50A

150A

14

2.526

80

40

20

 

8

2

12

1.589

120

60

30

 

12

3.4

10

0.9994

200

100

50

 

20

6

8

0.6285

320

160

80

 

32

10

6

0.3953

500

250

125

 

50

16

4

0.2486

800

400

200

 

80

26

2

0.1564

1200

600

300

 

125

40

0

0.0983

2000

1000

500

 

200

68

Table 3-2:Maximum wire length for 1V drop on lead (in feet).

Cross sect.

Resistivity

Maximum length in meters to limit voltage

 

 

Area

Ohm/km

drop to 1V or less.

 

 

 

 

(mm^2)

 

5A

10A

20A

 

50A

150A

2.5

8.21

24.0

12.0

6.0

 

2.4

0.8

4

5.09

39.2

18.6

9.8

 

4.0

1.4

6

3.39

59.0

29.4

14.8

 

5.8

2.0

10

1.95

102.6

51.2

25.6

 

10.2

3.4

16

1.24

160.0

80.0

40.0

 

16.0

5.4

25

0.795

250.0

125.0

62.0

 

25.2

8.4

35

0.565

354.0

177.0

88.0

 

35.4

11.8

Table 3-3:Maximum wire length for 1V drop on lead (in meters).

For currents not shown in Tables 3-2 and 3-3 , use the formula : Maximum length=1000/(current*resistivity)

Where current is expressed in ampers and resistivity in ohms/km or ohms/1000ft.

8

Image 11
Contents FPS Series 1000W In 1U FPS1000 Series Table of Contents Disclaimer WarrantyLimitation of Warranty Warranty ServiceFPS1000 Power Supply and FPS-S1U Rack Safety Instructions Safety Symbols FPS1000 Series Specifications Outline Drawings FPS 1000 Series Outline Drawings FPS 1000/P Series Outline Drawings FPS1000 Power Supply Installation Current Carrying Capacity Connecting the LoadLoad Wiring Making the load connections Noise and Impedance EffectsInductive loads Repackaging for Shipment Input/Output connector informationFunctions and Features FPS10004.7KΩ Dcok signalACFail signal Remote On/Off controlRemote Sensing Basic Connections for Operation Connecting single load, Local sensingConnecting Single Load, Remote Sensing Connecting Multiple loads, radial distribution methodGrounding outputs Multiple loads connection with distribution terminalsOutput voltage trimming at parallel operation Parallel and Series OperationParallel operation Parallel operation with Remote sensingRemote On/Off control at parallel operation Signal Return bus at parallel operationSeries connection for positive and negative output voltage Series operationI2C BUS Interface Option Eeprom functions Block diagram of the I2C optionOperation and functions 7.4.1. Digital status Output current readback Analog functions4 A/D Scaling FPS1000 Typical application diagramFPS1000 Maintenance FPS-S1U 19 Rack Single Output Maximum output power Chapter FPS-S1U Rack SpecificationsFPS-S1U Rack Mounting FPS-S1U Rack InstallationRear panel description Control and monitoring signals connectorSCL I2C Blank panels Modules locationFPS-S1U and FPS-S1U/P Outline Drawings FPS-S1U/P Outline Drawing Multiple loads connection Basic Connections for Operation FPS-S1U RackOutput voltage trimming Supervisory signals12.4 On/Off control Parallel operation with Remote sensing Output voltage trimming at parallel operation Signal Return bus at parallel operationRemote On/Off control at parallel operation Addressing A0, A1, A2 FPS-S1U I2C BUS Interface OptionIntroduction Adjustments and Calibration FPS-S1U MaintenanceUnits under warranty Periodic maintenanceFPS-T1U 19 Rack Triple Output Chapter FPS-T1U Rack SpecificationsFPS-T1U Rack Mounting FPS-T1U Rack InstallationFPS-T1U Rear panel J1A, J2B, J3C Conector Description Modules location FPS-T1U and FPS-T1U/P Outline Drawings FPS-T1U/P Outline Drawing 19.2 On/Off control Basic Connections for Operation FPS-T1U RackOutput Voltag Trimming Load Series operation Module a Module B Module C FPS-T1U I2C BUS Interface OptionFPS-T1U Maintenance