6. Configuring the Gateway

6.4. Transferring a Configuration to the Gateway

When using AbcConf, you can transfer the configuration you are editing to the gateway at any time.

Choose “Download configuration to ABC-LUFP” from the “File”

menu or click on the button, in the AbcConf toolbar.

AbcConf initializes a check test of the gateway type. During this test, the PC should not carry out any other operations, as this could lead to AbcConf apparently freezing up and slow down the PC’s general operation for several minutes! The test then continues and the PC returns to normal running speed.

Once this test has finished, a window called “Download” opens and a progress bar shows the state of progress for the transfer of the configuration to the gateway. You must never interrupt this operation, otherwise you will have to start it again from the beginning.

Check that the transfer has been correctly carried out: LED s DEVICE STATUS should be flashing green.

If this LED is flashing red/green, save the configuration you were editing, open the file containing the default configuration for LUFP9 gateways, then transfer it to the gateway. This will restore it to a known initial state. You can then continue with the configuration you were transferring, and make any corrections which may be necessary.

6.5. Monitoring the Content of the Gateway’s Memory

One of the main commands that you will need to use when setting up the gateway is the command allowing you to read the contents of the gateway’s memory and to display it in a window used for this purpose. This will be particularly useful when you are working on your PLC configurations and applications. However, it only shows data from the “Data” and “Preset Data” fields configured in the “Query” and “Response” elements of just one of the Modbus slaves, plus the content of the gateway’s two reserved registers, located at memory addresses 16#0000-16#0001 (gateway status word) and 16#0200-16#0201 (DeviceNet master command word).

To monitor the content of the gateway’s memory, start by selecting the node corresponding to the Modbus slave whose data you wish to view, then choose “Monitor” from the menu whose name corresponds to the name of the previously selected node. A monitoring window then appears. The sample window shown at the top of the next page corresponds to a view of the contents of the memory exchanged, using the gateway’s default configuration, with the “TeSys U n°1” motor starter.

43

Image 43
Contents LUFP9 Page LUFP9 Page Table of contents Introduction to the user guide IntroductionTerminology Introduction to the LUFP9 GatewayAltistart Additional Documentation Notational ConventionsDownstream network no.1 ModbusModbus VW33-A48 Downstream network no.3 ModbusPrinciple Used to Configure and Operate the LUFP9 Gateway Modbus network ABC ConfiguratorDeviceNet Network LUFP9 gatewayRSNetWorx RSLogixHardware Implementation of the LUFP9 Gateway Configuration Modbus RTUOn Receipt Mounting the Gateway on a DIN Rail Powering the gatewayMounting the gateway Dismounting the gateway Examples of Modbus connection topologies Connecting the Gateway to the Modbus NetworkLUFP9 gateway Pin outs TSXCSA00120 Ω Wiring recommendations for the Modbus networkHubs, drops, taps, and line terminations Pin Connecting the LUFP9 gateway to the DeviceNet networkWire colour CablesSelector Switches DeviceNet speed 3 4 5 6 7 Configuring DeviceNet Communication FeaturesSpeed Address Mac ID Selector DeviceNet Switches Address 3 4 5 6 7Encoding the Gateway Address Signalling DeviceNet Master PLC SLC500 DeviceNet upstream network Software Implementation of the GatewayIntroduction System ArchitectureModbus cycle time Configuring the Motor StartersManaging degraded modes Installing the Gateway Description File Configuring the Gateway in RsNetWorxSelecting and adding the master PLC’s DeviceNet scanner Editing gateway parameters Selecting and Adding the Gateway to the DeviceNet NetworkSoftware Implementation of the Gateway Configuring the DeviceNet Scanner I1.2 Configuring Inputs from the GatewayService PLC input Description I1.1O1.2 Configuring Outputs Intended for the GatewayService PLC output Description O1.1Output Value Meaning MSB + LSB Description of Services Assigned to Gateway Inputs/OutputsInput Value Meaning MSB + LSB Developing a DeviceNet Application Transferring the DeviceNet Scanner ConfigurationControl/Status Byte field Sub-chapter Gateway Initialization and DiagnosticsFull Management SummaryFbdu Modbus exchange startup Fbhssend New DeviceNet master command wordBits Description Gateway Status Word Bits Description Abchssend New gateway diagnostic11EC Error code associated with the Modbus network ED Error data item associated with the Modbus networkDescription of the error Diagnostic only DeviceNet Master Command Word Simplified Operation Connecting the Gateway to the Configuration PC Configuring the GatewayPC COM Male 9 point SUB-D LUFP9 Configuration Female RJ45RS-232 link protocol Male RJ45Importing the Gateway Configuration Installing AbcConfMonitoring the Content of the Gateway’s Memory Transferring a Configuration to the GatewayConfiguring the Gateway Deleting a Modbus Slave Procedure for deleting a Modbus slaveKeyboard shortcut Ctrl Copying a previously configured Modbus slaveAdding a Modbus Slave Adding a new type of Modbus slaveImporting/exporting a Modbus slave configuration Replacing a Periodic Input Data Element Changing the Periodic Data Exchanged With a Modbus SlaveReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway I1.20 I1.17I1.18 I1.19Configuring the Gateway Configuring the Gateway Configuring the Gateway O1.18 O1.17Deleting Aperiodic Parameter Data Configuring the Gateway Changing the Name of a Modbus Slave Changing a Modbus slave ConfigurationChanging the Address of a Modbus Slave Modbus response Adding and Setting Up a Modbus CommandName of the Modbus command Modbus query With TeSys U Motor StartersWith a Generic Modbus Slave Configuring the Gateway DeviceNet Configuration Description Element Configuring the QueryConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Field Size Description Frame Configuring the Content of the Query FrameSize FieldFrame Configuring the Content of the Response Frame Mode. The default value, CRC, should not be changedModbus Commands Based on Standard Commands Adding a Special Modbus CommandModbus Commands which Can Be Completely Changed by the User Fieldbus element Configuring the General Characteristics of the GatewayABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Communication Characteristics Appendix a Technical CharacteristicsEnvironment Input data area InputsGeneral data area OutputsGeneral data Output data area16#06 Appendix B Default ConfigurationConfiguring Modbus exchanges 16#10Input Data Memory Area Content of the Gateway’s Dpram Memory16#0200 Main Program LAD 2 MAINLUFP9 Appendix C Practical Example RSLogixScanvalidation Address Symbol DescriptionAddress Symbol Display Cmdreset ModuleAppendix C Practical Example RSLogix Numparam Appendix C Practical Example RSLogix Wrrunning Reserves relating to the RSLogix 500 example Address Symbol DisplayClass Required Instances Interfaces Appendix D DeviceNet ObjectsIntroduction to the Gateway’s DeviceNet Objects List of the Gateway’s DeviceNet ObjectsIdentity Object class 16#01 Graphical Representation of the Gateway’s DeviceNet ObjectsAttributes of instance 16#01 of class 16#01 Services of instance 16#01 of class 16#01DeviceNet Object class 16#03 Message Router Object class 16#02Revision index of the Assembly Object class Assembly Objects Class 16#04Services of instance 16#01 of class 16#03 Services in class 16#04Attributes of instance 16#96 of class 16#04 Modbus Outputs Services of instances 16#64 and 16#96 of class 16#04Connection Object Class 16#05 Attributes of instance 16#64 of class 16#04 Modbus InputsAttributes of class 16#05 Services in class 16#05Produced connection ID Initial comm. characteristicsWatchdog timeout action 16#83Type Value 16#01 Get State Access NameGet / Set Produced connection path Type Value16# 20 04 24 64 30 Type Value 16#07 Get / Set Produced connection size #0 xx Type Value 16#04 Get / Set Produced connection IDAttributes of class 16#2B Services in class 16#2BAcknowledge Handler Object class 16#2B Attributes of instances 16#01 to 16#04 of class 16#05Type Value 16#06 Get Data with ack path list size Services of instance 16#01 of class 16#2BData with ack path list Attributes of class 16#A0 Services in class 16#A0Services of instance 16#01 of class 16#A0 10.10. I/O Data Input Mapping Object Class 16#A0Attributes of class 16#A1 Services in class 16#A1Services of instance 16#01 of class 16#A1 10.11. I/O Data Output Mapping Object Class 16#A1Attributes of instance 16#01 of class 16#AA Diagnostic Object Class 16#AAServices in class 16#AA Attributes of class 16#AAChanged data field Access Name Need Type Value 16#09 Get LED statusModule type DeviceNet module statusServices of instance 16#01 of class 16#AA Appendix E Modbus Commands Preset Single Register command 16#06 Read Holding Registers Command 16#03Frame Field Value or properties Modbus Protocol Exception Responses Preset Multiple Registers Command 16#10Code Name Description of the exception Exception Page User’s manual V1.0 2003-03