Schneider Electric LUFP9 user manual Description of Services Assigned to Gateway Inputs/Outputs

Page 31

4. Software Implementation of the Gateway

4.2.8. Description of Services Assigned to Gateway Inputs/Outputs

Managing the downstream Modbus network: Please see chapter 5.2 Diagnostic only, page 37, for a detailed

description of this service. The example described in chapter 9.1 Main Program: “LAD 2 - MAIN_LUFP9”, page 86, only automatically acknowledges gateway diagnostics, that is to say it does not exploit the data from these diagnostics. In the case of the gateway’s default configuration, under AbcConf, the “Control/Status Byte” field of the “ABC” element is equal to “Enabled but no startup lock.”

Periodic communications (inputs): The value of each of the 8 words for this service corresponds to the value of the status register of a TeSys U motor starter (register located at address 455).

Periodic communications (outputs): The value of each of the 8 words for this service corresponds to the value to be sent to the command register for a TeSys U motor starter (register located at address 704).

Please see chapter 9.2 Controlling/Monitoring Sub-Program for a TeSys U Motor Starter: “LAD 3 - CMD_MON”, page 87, for an example of the simplified use of these “periodic communications” services.

Aperiodic communications: Please see chapter 9.3 Sub-Program for Reading a Parameter in all TeSys U

Motor Starters: “LAD 4 - RD_PAR”, page 89, and chapter 9.4 Sub-Program for Writing a Parameter on a Single

TeSys U Motor Starter: “LAD 5 - WR_PAR”, page 91, for an example of how to use the “aperiodic communications” services.

These aperiodic communications services offer functions similar to those of “parameter area PKW”, which can be found on certain Schneider Electric products, such as some ATV drives.

The 16-bit inputs and outputs for which the MSB and LSB order is specified must be used by the DeviceNet master inverting the LSB / MSB order so as to restore the value of the corresponding item of Modbus data.

Sample reading of a motor starter parameter:

Reading of the 1st fault register (address = 452 = 16#01C4) on “TeSys U n°5” motor starter. The initial values of O:1.16 and I:1.16 are equal to 16#1306. The result of the reading is 16#0002 (magnetic fault).

Output

Value

Meaning (MSB + LSB)

O:1.10

16#0305

Function no. + Slave no.

O:1.11

16#C401

Parameter address (MSBLSB)

O:1.12

16#0100

Number of parameters (MSBLSB)

O:1.16

16#1307

“Trigger byte” for the query (Pf)

Input

Value

Meaning (MSB + LSB)

I:1.10

16#0500

Slave no. + (not used)

I:1.11

16#0203

Number of bytes + Function no.

I:1.12

16#0200

Value read (MSBLSB)

I:1.16

16#1307

“Trigger byte” for the response (Pf)

Sample writing of a motor starter parameter:

Writing of the 2nd command register (address = 705 = 16#02C1) on “TeSys U n°7” motor starter at the value 16#0006 (clear statistics + reset thermal memory). The initial values of O:1.16 and I:1.16 are equal to 16#1307. The result of the writing is a command echo, that is to say that the values of the “address parameter” and “value to be written” fields are identical in both the query and the response.

Output

Value

Meaning (MSB + LSB)

O:1.13

16#0607

Function no. + Slave no.

O:1.14

16#C102

Parameter address (MSBLSB)

O:1.15

16#0600

Value to be written (MSBLSB)

O:1.16

16#1407

“Trigger byte” for the query (PF)

Input

Value

Meaning (MSB + LSB)

I:1.13

16#0607

Function no. + Slave no.

I:1.14

16#C102

Parameter address (MSBLSB)

I:1.15

16#0600

Value to be written (MSBLSB)

I:1.16

16#1407

“Trigger byte” for the response (PF)

Avoid writing incorrect values in outputs which correspond to the aperiodic communication services described above, as they would lead to the transmission of an incoherent Modbus frame. In fact there is no check on the data used by these services and so it is up to the DeviceNet master PLC application to manage them.

In addition, do not ever use these services in “Broadcast” mode (Modbus address = 0).

31

Image 31
Contents LUFP9 Page LUFP9 Page Table of contents Introduction to the user guide IntroductionTerminology Introduction to the LUFP9 GatewayAltistart Additional Documentation Notational ConventionsDownstream network no.1 ModbusModbus VW33-A48 Downstream network no.3 ModbusPrinciple Used to Configure and Operate the LUFP9 Gateway Modbus network ABC ConfiguratorDeviceNet Network LUFP9 gatewayRSNetWorx RSLogixHardware Implementation of the LUFP9 Gateway Configuration Modbus RTUOn Receipt Mounting the Gateway on a DIN Rail Powering the gatewayMounting the gateway Dismounting the gateway Examples of Modbus connection topologies Connecting the Gateway to the Modbus NetworkLUFP9 gateway Pin outs TSXCSA00120 Ω Wiring recommendations for the Modbus networkHubs, drops, taps, and line terminations Pin Connecting the LUFP9 gateway to the DeviceNet networkWire colour CablesSelector Switches DeviceNet speed 3 4 5 6 7 Configuring DeviceNet Communication FeaturesSpeed Address Mac ID Selector DeviceNet Switches Address 3 4 5 6 7Encoding the Gateway Address Signalling DeviceNet Master PLC SLC500 DeviceNet upstream network Software Implementation of the GatewayIntroduction System ArchitectureModbus cycle time Configuring the Motor StartersManaging degraded modes Installing the Gateway Description File Configuring the Gateway in RsNetWorxSelecting and adding the master PLC’s DeviceNet scanner Editing gateway parameters Selecting and Adding the Gateway to the DeviceNet NetworkSoftware Implementation of the Gateway Configuring the DeviceNet Scanner I1.2 Configuring Inputs from the GatewayService PLC input Description I1.1O1.2 Configuring Outputs Intended for the GatewayService PLC output Description O1.1Output Value Meaning MSB + LSB Description of Services Assigned to Gateway Inputs/OutputsInput Value Meaning MSB + LSB Developing a DeviceNet Application Transferring the DeviceNet Scanner ConfigurationControl/Status Byte field Sub-chapter Gateway Initialization and DiagnosticsFull Management SummaryFbdu Modbus exchange startup Fbhssend New DeviceNet master command wordBits Description Gateway Status Word Bits Description Abchssend New gateway diagnostic11EC Error code associated with the Modbus network ED Error data item associated with the Modbus networkDescription of the error Diagnostic only DeviceNet Master Command Word Simplified Operation Connecting the Gateway to the Configuration PC Configuring the GatewayPC COM Male 9 point SUB-D LUFP9 Configuration Female RJ45RS-232 link protocol Male RJ45Importing the Gateway Configuration Installing AbcConfMonitoring the Content of the Gateway’s Memory Transferring a Configuration to the GatewayConfiguring the Gateway Deleting a Modbus Slave Procedure for deleting a Modbus slaveKeyboard shortcut Ctrl Copying a previously configured Modbus slaveAdding a Modbus Slave Adding a new type of Modbus slaveImporting/exporting a Modbus slave configuration Replacing a Periodic Input Data Element Changing the Periodic Data Exchanged With a Modbus SlaveReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway I1.20 I1.17I1.18 I1.19Configuring the Gateway Configuring the Gateway Configuring the Gateway O1.18 O1.17Deleting Aperiodic Parameter Data Configuring the Gateway Changing the Name of a Modbus Slave Changing a Modbus slave ConfigurationChanging the Address of a Modbus Slave Modbus response Adding and Setting Up a Modbus CommandName of the Modbus command Modbus query With TeSys U Motor StartersWith a Generic Modbus Slave Configuring the Gateway DeviceNet Configuration Description Element Configuring the QueryConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Field Size Description Frame Configuring the Content of the Query FrameSize FieldFrame Configuring the Content of the Response Frame Mode. The default value, CRC, should not be changedModbus Commands Based on Standard Commands Adding a Special Modbus CommandModbus Commands which Can Be Completely Changed by the User Fieldbus element Configuring the General Characteristics of the GatewayABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Communication Characteristics Appendix a Technical CharacteristicsEnvironment Input data area InputsGeneral data area OutputsGeneral data Output data area16#06 Appendix B Default ConfigurationConfiguring Modbus exchanges 16#10Input Data Memory Area Content of the Gateway’s Dpram Memory16#0200 Main Program LAD 2 MAINLUFP9 Appendix C Practical Example RSLogixScanvalidation Address Symbol DescriptionAddress Symbol Display Cmdreset ModuleAppendix C Practical Example RSLogix Numparam Appendix C Practical Example RSLogix Wrrunning Reserves relating to the RSLogix 500 example Address Symbol DisplayClass Required Instances Interfaces Appendix D DeviceNet ObjectsIntroduction to the Gateway’s DeviceNet Objects List of the Gateway’s DeviceNet ObjectsIdentity Object class 16#01 Graphical Representation of the Gateway’s DeviceNet ObjectsAttributes of instance 16#01 of class 16#01 Services of instance 16#01 of class 16#01DeviceNet Object class 16#03 Message Router Object class 16#02Revision index of the Assembly Object class Assembly Objects Class 16#04Services of instance 16#01 of class 16#03 Services in class 16#04Attributes of instance 16#96 of class 16#04 Modbus Outputs Services of instances 16#64 and 16#96 of class 16#04Connection Object Class 16#05 Attributes of instance 16#64 of class 16#04 Modbus InputsAttributes of class 16#05 Services in class 16#05Produced connection ID Initial comm. characteristicsWatchdog timeout action 16#83Type Value 16#01 Get State Access NameGet / Set Produced connection path Type Value16# 20 04 24 64 30 Type Value 16#07 Get / Set Produced connection size #0 xx Type Value 16#04 Get / Set Produced connection IDAttributes of class 16#2B Services in class 16#2BAcknowledge Handler Object class 16#2B Attributes of instances 16#01 to 16#04 of class 16#05Type Value 16#06 Get Data with ack path list size Services of instance 16#01 of class 16#2BData with ack path list Attributes of class 16#A0 Services in class 16#A0Services of instance 16#01 of class 16#A0 10.10. I/O Data Input Mapping Object Class 16#A0Attributes of class 16#A1 Services in class 16#A1Services of instance 16#01 of class 16#A1 10.11. I/O Data Output Mapping Object Class 16#A1Attributes of instance 16#01 of class 16#AA Diagnostic Object Class 16#AAServices in class 16#AA Attributes of class 16#AAChanged data field Access Name Need Type Value 16#09 Get LED statusModule type DeviceNet module statusServices of instance 16#01 of class 16#AA Appendix E Modbus Commands Preset Single Register command 16#06 Read Holding Registers Command 16#03Frame Field Value or properties Modbus Protocol Exception Responses Preset Multiple Registers Command 16#10Code Name Description of the exception Exception Page User’s manual V1.0 2003-03