1. Introduction
Each LUFP9 DeviceNet / Modbus RTU gateway allows a PLC on the DeviceNet network to command, control and configure up to 8 Modbus slaves. If there are more than 8 Modbus slaves, you will need to use an appropriate number of LUFP9 gateways. In the same way, if the exchanges with the Modbus slaves require more than 25 Modbus commands (that is to say more than 50 queries and responses), you will have to distribute the Modbus slaves over several gateways.
The LUFP9 gateway behaves both as a DeviceNet slave on the upstream network and as a Modbus RTU master on the downstream network.
See chapter 7.2 Communication Characteristics, page 80, if you would like to read about the technical communication characteristics of the LUFP9 gateway.
The gateway can carry out its data exchanges (inputs and outputs of all types) with the Modbus slaves cyclically, aperiodically or in an
N.B. If, for example, a communication is periodic on the Modbus network, the corresponding data does not have to be exchanged periodically on the DeviceNet network and vice versa.
The diagram on the page to the left illustrates the distribution of several slaves over three downstream Modbus RTU networks, each of these networks being interfaced with the DeviceNet master PLC using an LUFP9 gateway.
1.7. Principle Used to Configure and Operate the LUFP9 Gateway
The gateway is part of a family of products (referred to as LUFPz) designed to meet generic needs for connection between two networks using different communication protocols.
The software elements common to all these gateways (a configuration tool known as
ÖThe exchanges between the gateway (which operates as a Modbus master) and the Modbus slaves are wholly configured using the
By configuring the queries and responses for Modbus commands via this tool the user can create links between a part of the content of the corresponding Modbus frames and the content of the gateway’s physical memory (input memory for the content of the Modbus responses and output memory for the content of the queries).
ÖThe exchanges between the DeviceNet master PLC and the LUFP9 gateway should be configured in such a way that the DeviceNet master can read the input data and write the output data from the gateway, but only the data used for the Modbus exchanges (see previous point).
10