Schneider Electric LUFP9 user manual Configuring the Gateway

Page 51

6. Configuring the Gateway

3)Changing the location of the Modbus data received in the gateway’s memory: As the number of bytes read (see previous step) has increased from 2 to 16, the Modbus data received must be placed at a different location in the gateway’s memory, and the size of the memory occupied must also be adjusted appropriately.

If you are not certain how much of the gateway’s memory is currently occupied, select “Sub-Network” and choose “Monitor” from the Sub-Network” menu. The following window appears, allowing you to see how much of the gateway’s memory is occupied.

To see which memory locations are occupied by data from the command you are interested in, all you have to do is uncheck the box corresponding to the “Read Holding Registers” command from the “TeSys U n°2” node, as shown above. We can see that the Modbus data received in response to this command occupy 2 bytes located from address 16#0004.

The memory locations 16#0000 and 16#0001 are reserved (see chapter 5 Gateway Initialization and Diagnostics, page 33). So you will not be able to place any Modbus data in these locations.

The sizes displayed above the graphics areas of this window (“In Area 32 bytes” and “Out Area 32 bytes”) correspond to the total input and ouput sizes you must check under RsNetWorx (see point 6) on next page) and configure for the DeviceNet scanner (see point 7) ).

If you wish to place the 16 bytes of Modbus data which will be received by the gateway for this command into memory, once the changes have been made, we will have to move all the other input data by 14 bytes, which may be tedious, or change the memory location of the block of data received. In the example described here, we will be using the second solution, although the first solution is actually preferable, in principle, as it avoids leaving any “holes” in the gateway’s memory, thus optimising the transfer of all of the data to the DeviceNet master PLC. Furthermore, the 1747-SDN scanner can only exchange 32 input words with the master PLC. Leaving “holes” of this sort in the gateway’s memory is therefore not recommended in cases of large configurations.

So we will be placing the 16 bytes of data from address 16#0020 (32 in decimal), that is to say directly after the input data for the gateway’s default configuration.

Close the “Sub-network Monitor” window, then once you are back in the main AbcConf window, select the “Data length” and “Data location” fields of the “Data” element from the “Response” one after another and change their values as shown at the top of the next page. AbcConf will automatically convert any value entered in decimal to hexadecimal.

51

Image 51
Contents LUFP9 Page LUFP9 Page Table of contents Introduction to the user guide IntroductionIntroduction to the LUFP9 Gateway TerminologyAltistart Additional Documentation Notational ConventionsDownstream network no.1 ModbusModbus VW33-A48 Downstream network no.3 ModbusPrinciple Used to Configure and Operate the LUFP9 Gateway Modbus network ABC ConfiguratorDeviceNet Network LUFP9 gatewayRSNetWorx RSLogixConfiguration Modbus RTU Hardware Implementation of the LUFP9 GatewayOn Receipt Powering the gateway Mounting the Gateway on a DIN RailMounting the gateway Dismounting the gateway Examples of Modbus connection topologies Connecting the Gateway to the Modbus NetworkLUFP9 gateway Pin outs TSXCSA00Wiring recommendations for the Modbus network 120 ΩHubs, drops, taps, and line terminations Pin Connecting the LUFP9 gateway to the DeviceNet networkWire colour CablesSelector Switches DeviceNet speed 3 4 5 6 7 Configuring DeviceNet Communication FeaturesSelector DeviceNet Switches Address 3 4 5 6 7 Speed Address Mac IDEncoding the Gateway Address Signalling DeviceNet Master PLC SLC500 DeviceNet upstream network Software Implementation of the GatewayIntroduction System ArchitectureConfiguring the Motor Starters Modbus cycle timeManaging degraded modes Configuring the Gateway in RsNetWorx Installing the Gateway Description FileSelecting and adding the master PLC’s DeviceNet scanner Editing gateway parameters Selecting and Adding the Gateway to the DeviceNet NetworkSoftware Implementation of the Gateway Configuring the DeviceNet Scanner I1.2 Configuring Inputs from the GatewayService PLC input Description I1.1O1.2 Configuring Outputs Intended for the GatewayService PLC output Description O1.1Description of Services Assigned to Gateway Inputs/Outputs Output Value Meaning MSB + LSBInput Value Meaning MSB + LSB Developing a DeviceNet Application Transferring the DeviceNet Scanner ConfigurationControl/Status Byte field Sub-chapter Gateway Initialization and DiagnosticsFull Management SummaryFbhssend New DeviceNet master command word Fbdu Modbus exchange startupBits Description Gateway Status Word Bits Description Abchssend New gateway diagnostic11EC Error code associated with the Modbus network ED Error data item associated with the Modbus networkDescription of the error Diagnostic only DeviceNet Master Command Word Simplified Operation Connecting the Gateway to the Configuration PC Configuring the GatewayPC COM Male 9 point SUB-D LUFP9 Configuration Female RJ45RS-232 link protocol Male RJ45Importing the Gateway Configuration Installing AbcConfMonitoring the Content of the Gateway’s Memory Transferring a Configuration to the GatewayConfiguring the Gateway Deleting a Modbus Slave Procedure for deleting a Modbus slaveKeyboard shortcut Ctrl Copying a previously configured Modbus slaveAdding a Modbus Slave Adding a new type of Modbus slaveImporting/exporting a Modbus slave configuration Replacing a Periodic Input Data Element Changing the Periodic Data Exchanged With a Modbus SlaveReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway I1.20 I1.17I1.18 I1.19Configuring the Gateway Configuring the Gateway Configuring the Gateway O1.18 O1.17Deleting Aperiodic Parameter Data Configuring the Gateway Changing the Name of a Modbus Slave Changing a Modbus slave ConfigurationChanging the Address of a Modbus Slave Modbus response Adding and Setting Up a Modbus CommandName of the Modbus command Modbus query With TeSys U Motor StartersWith a Generic Modbus Slave Configuring the Gateway DeviceNet Configuration Description Element Configuring the QueryConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Field Size Description Frame Configuring the Content of the Query FrameField SizeFrame Configuring the Content of the Response Frame Mode. The default value, CRC, should not be changedModbus Commands Based on Standard Commands Adding a Special Modbus CommandModbus Commands which Can Be Completely Changed by the User Fieldbus element Configuring the General Characteristics of the GatewayABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Appendix a Technical Characteristics Communication CharacteristicsEnvironment Input data area InputsGeneral data area OutputsGeneral data Output data area16#06 Appendix B Default ConfigurationConfiguring Modbus exchanges 16#10Input Data Memory Area Content of the Gateway’s Dpram Memory16#0200 Main Program LAD 2 MAINLUFP9 Appendix C Practical Example RSLogixScanvalidation Address Symbol DescriptionAddress Symbol Display Cmdreset ModuleAppendix C Practical Example RSLogix Numparam Appendix C Practical Example RSLogix Wrrunning Reserves relating to the RSLogix 500 example Address Symbol DisplayClass Required Instances Interfaces Appendix D DeviceNet ObjectsIntroduction to the Gateway’s DeviceNet Objects List of the Gateway’s DeviceNet ObjectsIdentity Object class 16#01 Graphical Representation of the Gateway’s DeviceNet ObjectsAttributes of instance 16#01 of class 16#01 Services of instance 16#01 of class 16#01DeviceNet Object class 16#03 Message Router Object class 16#02Revision index of the Assembly Object class Assembly Objects Class 16#04Services of instance 16#01 of class 16#03 Services in class 16#04Attributes of instance 16#96 of class 16#04 Modbus Outputs Services of instances 16#64 and 16#96 of class 16#04Connection Object Class 16#05 Attributes of instance 16#64 of class 16#04 Modbus InputsAttributes of class 16#05 Services in class 16#05Produced connection ID Initial comm. characteristicsWatchdog timeout action 16#83Type Value 16#01 Get State Access NameType Value Get / Set Produced connection path16# 20 04 24 64 30 Type Value 16#07 Get / Set Produced connection size #0 xx Type Value 16#04 Get / Set Produced connection IDAttributes of class 16#2B Services in class 16#2BAcknowledge Handler Object class 16#2B Attributes of instances 16#01 to 16#04 of class 16#05Services of instance 16#01 of class 16#2B Type Value 16#06 Get Data with ack path list sizeData with ack path list Attributes of class 16#A0 Services in class 16#A0Services of instance 16#01 of class 16#A0 10.10. I/O Data Input Mapping Object Class 16#A0Attributes of class 16#A1 Services in class 16#A1Services of instance 16#01 of class 16#A1 10.11. I/O Data Output Mapping Object Class 16#A1Attributes of instance 16#01 of class 16#AA Diagnostic Object Class 16#AAServices in class 16#AA Attributes of class 16#AAChanged data field Access Name Need Type Value 16#09 Get LED statusModule type DeviceNet module statusServices of instance 16#01 of class 16#AA Appendix E Modbus Commands Read Holding Registers Command 16#03 Preset Single Register command 16#06Frame Field Value or properties Modbus Protocol Exception Responses Preset Multiple Registers Command 16#10Code Name Description of the exception Exception Page User’s manual V1.0 2003-03