6. Configuring the Gateway

Field in the

Size in the

Description

 

frame

frame

 

 

 

Checksum

2 bytes

Error check type: Type of error check for the frame.

 

 

- CRC

Default method. This is the method adopted for the Modbus

 

 

RTU protocol.

 

 

 

- LRC

This method relates to the Modbus ASCII protocol. So it

 

 

should not be used in this case.

 

 

- XOR

Simple “OR Exclusive” applied to the frame’s bytes.

 

 

E.g. The LUFP9 gateway is specifically designed for the Modbus protocol RTU

 

 

mode. The default value, “CRC”, should not be changed.

 

 

Error check start byte: Indicates the number of the byte, in the frame, from

 

 

which the calculation of the “checksum” should begin. The first byte in each

 

 

frame carries the number 0.

 

 

E.g. The calculation of a frame’s checksum should always begin with the first

 

 

byte. The value of this field should therefore remain set to zero.

6.11.2.5. Configuring the Content of the Response Frame

The window shown below is obtained using “Edit Frame” from the “Response” menu. The values shown in it correspond to the values assigned by default to the Modbus command response we have created. The correspondence with the content of the corresponding Modbus frame has been added underneath this window.

Slave no.

Function no.

Word number (MSB / LSB)

Value of the word (MSB / LSB)

CRC16 (LSB / MSB)

Edit the values which are not greyed out, one after another.

There is a description of them on the next page, but also see the previous chapter, as the nature of the content of response frames is very similar to that of the fields in Modbus query frames.

If the value of a field from the response of a Modbus slave is different from that configured via AbcConf, the response will be rejected by the gateway. It will then proceed to a re-transmission of the query, provided that at least one re-transmission has been configured for this command (see chapter 6.11.2.2 Configuring the Query, page 66). Of course, this remark does not relate to the data itself, that is to say the Modbus frame fields configured using the “Data location,” “Data length,” and “Byte swap” elements.

72

Image 72
Contents LUFP9 Page LUFP9 Page Table of contents Introduction Introduction to the user guideIntroduction to the LUFP9 Gateway TerminologyAltistart Notational Conventions Additional DocumentationModbus Modbus VW33-A48Downstream network no.3 Modbus Downstream network no.1Principle Used to Configure and Operate the LUFP9 Gateway ABC Configurator Modbus networkLUFP9 gateway RSNetWorxRSLogix DeviceNet NetworkConfiguration Modbus RTU Hardware Implementation of the LUFP9 GatewayOn Receipt Powering the gateway Mounting the Gateway on a DIN RailMounting the gateway Dismounting the gateway Connecting the Gateway to the Modbus Network Examples of Modbus connection topologiesLUFP9 gateway TSXCSA00 Pin outsWiring recommendations for the Modbus network 120 ΩHubs, drops, taps, and line terminations Connecting the LUFP9 gateway to the DeviceNet network Wire colourCables PinConfiguring DeviceNet Communication Features Selector Switches DeviceNet speed 3 4 5 6 7Selector DeviceNet Switches Address 3 4 5 6 7 Speed Address Mac IDEncoding the Gateway Address Signalling Software Implementation of the Gateway IntroductionSystem Architecture DeviceNet Master PLC SLC500 DeviceNet upstream networkConfiguring the Motor Starters Modbus cycle timeManaging degraded modes Configuring the Gateway in RsNetWorx Installing the Gateway Description FileSelecting and adding the master PLC’s DeviceNet scanner Selecting and Adding the Gateway to the DeviceNet Network Editing gateway parametersSoftware Implementation of the Gateway Configuring the DeviceNet Scanner Configuring Inputs from the Gateway Service PLC input DescriptionI1.1 I1.2Configuring Outputs Intended for the Gateway Service PLC output DescriptionO1.1 O1.2Description of Services Assigned to Gateway Inputs/Outputs Output Value Meaning MSB + LSBInput Value Meaning MSB + LSB Transferring the DeviceNet Scanner Configuration Developing a DeviceNet ApplicationGateway Initialization and Diagnostics Full ManagementSummary Control/Status Byte field Sub-chapterFbhssend New DeviceNet master command word Fbdu Modbus exchange startupBits Description Bits Description Abchssend New gateway diagnostic 11EC Error code associated with the Modbus networkED Error data item associated with the Modbus network Gateway Status WordDescription of the error Diagnostic only DeviceNet Master Command Word Simplified Operation Configuring the Gateway Connecting the Gateway to the Configuration PCLUFP9 Configuration Female RJ45 RS-232 link protocolMale RJ45 PC COM Male 9 point SUB-DInstalling AbcConf Importing the Gateway ConfigurationTransferring a Configuration to the Gateway Monitoring the Content of the Gateway’s MemoryConfiguring the Gateway Procedure for deleting a Modbus slave Deleting a Modbus SlaveCopying a previously configured Modbus slave Adding a Modbus SlaveAdding a new type of Modbus slave Keyboard shortcut CtrlImporting/exporting a Modbus slave configuration Changing the Periodic Data Exchanged With a Modbus Slave Replacing a Periodic Input Data ElementReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway I1.17 I1.18I1.19 I1.20Configuring the Gateway Configuring the Gateway Configuring the Gateway O1.17 O1.18Deleting Aperiodic Parameter Data Configuring the Gateway Changing a Modbus slave Configuration Changing the Name of a Modbus SlaveChanging the Address of a Modbus Slave Adding and Setting Up a Modbus Command Name of the Modbus command Modbus queryWith TeSys U Motor Starters Modbus responseWith a Generic Modbus Slave Configuring the Gateway DeviceNet Configuring the Query Configuration Description ElementConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Configuring the Content of the Query Frame Field Size Description FrameField SizeFrame Mode. The default value, CRC, should not be changed Configuring the Content of the Response FrameAdding a Special Modbus Command Modbus Commands Based on Standard CommandsModbus Commands which Can Be Completely Changed by the User Configuring the General Characteristics of the Gateway Fieldbus elementABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Appendix a Technical Characteristics Communication CharacteristicsEnvironment Inputs Input data areaOutputs General dataOutput data area General data areaAppendix B Default Configuration Configuring Modbus exchanges16#10 16#06Content of the Gateway’s Dpram Memory Input Data Memory Area16#0200 Appendix C Practical Example RSLogix Main Program LAD 2 MAINLUFP9Address Symbol Description ScanvalidationCmdreset Module Address Symbol DisplayAppendix C Practical Example RSLogix Numparam Appendix C Practical Example RSLogix Wrrunning Address Symbol Display Reserves relating to the RSLogix 500 exampleAppendix D DeviceNet Objects Introduction to the Gateway’s DeviceNet ObjectsList of the Gateway’s DeviceNet Objects Class Required Instances InterfacesGraphical Representation of the Gateway’s DeviceNet Objects Identity Object class 16#01Services of instance 16#01 of class 16#01 Attributes of instance 16#01 of class 16#01Message Router Object class 16#02 DeviceNet Object class 16#03Assembly Objects Class 16#04 Services of instance 16#01 of class 16#03Services in class 16#04 Revision index of the Assembly Object classServices of instances 16#64 and 16#96 of class 16#04 Connection Object Class 16#05Attributes of instance 16#64 of class 16#04 Modbus Inputs Attributes of instance 16#96 of class 16#04 Modbus OutputsServices in class 16#05 Attributes of class 16#05Initial comm. characteristics Watchdog timeout action16#83 Produced connection IDAccess Name Type Value 16#01 Get StateType Value Get / Set Produced connection path16# 20 04 24 64 30 Type Value 16#07 Get / Set Produced connection size Type Value 16#04 Get / Set Produced connection ID #0 xxServices in class 16#2B Acknowledge Handler Object class 16#2BAttributes of instances 16#01 to 16#04 of class 16#05 Attributes of class 16#2BServices of instance 16#01 of class 16#2B Type Value 16#06 Get Data with ack path list sizeData with ack path list Services in class 16#A0 Services of instance 16#01 of class 16#A010.10. I/O Data Input Mapping Object Class 16#A0 Attributes of class 16#A0Services in class 16#A1 Services of instance 16#01 of class 16#A110.11. I/O Data Output Mapping Object Class 16#A1 Attributes of class 16#A1Diagnostic Object Class 16#AA Services in class 16#AAAttributes of class 16#AA Attributes of instance 16#01 of class 16#AAAccess Name Need Type Value 16#09 Get LED status Module typeDeviceNet module status Changed data fieldServices of instance 16#01 of class 16#AA Appendix E Modbus Commands Read Holding Registers Command 16#03 Preset Single Register command 16#06Frame Field Value or properties Preset Multiple Registers Command 16#10 Modbus Protocol Exception ResponsesCode Name Description of the exception Exception Page User’s manual V1.0 2003-03