Schneider Electric LUFP9 user manual Signalling

Page 22

3. Signalling

The gateway’s 6 LEDs and the descriptive label on the removable cover which hides its block of selector switches allow you to diagnose the status of the gateway:

c

d

 

telm

 

 

 

 

 

LUFP9

 

 

f

 

n o

 

 

p q

e

 

 

 

 

r s

 

 

 

 

h

1 NETWORK STATUS

 

2 MODULE STATUS

g

3 NOT USED

 

4 NOT USED

 

 

 

 

5 MODBUS

 

 

6 GATEWAY

DeviceNet

 

LED

LED Æ Gateway state

 

 

Off: Gateway not connected to

 

 

the DeviceNet bus

 

 

Green: Gateway connected to

 

 

the DeviceNet bus:

 

 

Connection established

 

 

Red: Fatal error on connection

n

NETWORK

to the DeviceNet bus

 

STATUS

Flashing (green): Gateway

 

 

connected to the DeviceNet bus:

 

 

Connection not established

 

 

Flashing (red):Timeout in

 

 

connection to the DeviceNet bus

 

 

 The length of this timeout is

 

 

defined by the DeviceNet master

p NOT USED

Off: —

 

 

 

 

 

Off: No power

 

 

 

 

 

Flashing (green): No Modbus

 

 

communications

r MODBUS

 

Green: Modbus

 

 

communications OK

 

 

 

 

 

Red: Loss of communication with

 

 

at least one Modbus slave (1)

 

 

 

 

LED

LED Æ Gateway state

 

 

Off: No power

 

 

 

 

 

Red: Unrecoverable failure

o

MODULE

 

 

STATUS

Green: Gateway is operational

 

 

 

 

 

 

 

Flashing (red): Minor fault

 

 

q NOT USED

Off: —

 

 

 

 

 

Off: No power

 

 

Flashing (red/green):

 

 

Configuration absent / not valid

s GATEWAY

 Use AbcConf to load a valid

configuration

 

 

Green: Gateway currently being

 

 

initialized and configured

 

 

Flashing (green): Gateway is in

 

 

running order: Configuration OK

(1)The LED rMODBUS becomes red whenever you use incorrect values in the outputs corresponding to the queries of the two aperiodic services designed to read/write the value of any parameter of a Modbus slave (see chapter 4.2.8 Description of Services Assigned to Gateway Inputs/Outputs, page 31). This LED will only revert to its former green state if you reuse these very same services, but with correct values. More generally, this LED becomes red, then reverts to a green state, on loss and recovery of the communications with any Modbus slave.

N.B. If the DEVICE STATUS LED s is flashing following a sequence beginning with one or

more red flashes, we advise that you note down the order of this sequence and give this information to the Schneider Electric support service.

In some cases, all you need to do is power the gateway off then back on again to solve the problem.

22

Image 22
Contents LUFP9 Page LUFP9 Page Table of contents Introduction Introduction to the user guideTerminology Introduction to the LUFP9 GatewayAltistart Notational Conventions Additional DocumentationDownstream network no.3 Modbus ModbusModbus VW33-A48 Downstream network no.1Principle Used to Configure and Operate the LUFP9 Gateway ABC Configurator Modbus networkRSLogix LUFP9 gatewayRSNetWorx DeviceNet NetworkHardware Implementation of the LUFP9 Gateway Configuration Modbus RTUOn Receipt Mounting the Gateway on a DIN Rail Powering the gatewayMounting the gateway Dismounting the gateway Connecting the Gateway to the Modbus Network Examples of Modbus connection topologiesLUFP9 gateway TSXCSA00 Pin outs120 Ω Wiring recommendations for the Modbus networkHubs, drops, taps, and line terminations Cables Connecting the LUFP9 gateway to the DeviceNet networkWire colour PinConfiguring DeviceNet Communication Features Selector Switches DeviceNet speed 3 4 5 6 7Speed Address Mac ID Selector DeviceNet Switches Address 3 4 5 6 7Encoding the Gateway Address Signalling System Architecture Software Implementation of the GatewayIntroduction DeviceNet Master PLC SLC500 DeviceNet upstream networkModbus cycle time Configuring the Motor StartersManaging degraded modes Installing the Gateway Description File Configuring the Gateway in RsNetWorxSelecting and adding the master PLC’s DeviceNet scanner Selecting and Adding the Gateway to the DeviceNet Network Editing gateway parametersSoftware Implementation of the Gateway Configuring the DeviceNet Scanner I1.1 Configuring Inputs from the GatewayService PLC input Description I1.2O1.1 Configuring Outputs Intended for the GatewayService PLC output Description O1.2Output Value Meaning MSB + LSB Description of Services Assigned to Gateway Inputs/OutputsInput Value Meaning MSB + LSB Transferring the DeviceNet Scanner Configuration Developing a DeviceNet ApplicationSummary Gateway Initialization and DiagnosticsFull Management Control/Status Byte field Sub-chapterFbdu Modbus exchange startup Fbhssend New DeviceNet master command wordBits Description ED Error data item associated with the Modbus network Bits Description Abchssend New gateway diagnostic11EC Error code associated with the Modbus network Gateway Status WordDescription of the error Diagnostic only DeviceNet Master Command Word Simplified Operation Configuring the Gateway Connecting the Gateway to the Configuration PCMale RJ45 LUFP9 Configuration Female RJ45RS-232 link protocol PC COM Male 9 point SUB-DInstalling AbcConf Importing the Gateway ConfigurationTransferring a Configuration to the Gateway Monitoring the Content of the Gateway’s MemoryConfiguring the Gateway Procedure for deleting a Modbus slave Deleting a Modbus SlaveAdding a new type of Modbus slave Copying a previously configured Modbus slaveAdding a Modbus Slave Keyboard shortcut CtrlImporting/exporting a Modbus slave configuration Changing the Periodic Data Exchanged With a Modbus Slave Replacing a Periodic Input Data ElementReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway I1.19 I1.17I1.18 I1.20Configuring the Gateway Configuring the Gateway Configuring the Gateway O1.17 O1.18Deleting Aperiodic Parameter Data Configuring the Gateway Changing a Modbus slave Configuration Changing the Name of a Modbus SlaveChanging the Address of a Modbus Slave With TeSys U Motor Starters Adding and Setting Up a Modbus CommandName of the Modbus command Modbus query Modbus responseWith a Generic Modbus Slave Configuring the Gateway DeviceNet Configuring the Query Configuration Description ElementConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Configuring the Content of the Query Frame Field Size Description FrameSize FieldFrame Mode. The default value, CRC, should not be changed Configuring the Content of the Response FrameAdding a Special Modbus Command Modbus Commands Based on Standard CommandsModbus Commands which Can Be Completely Changed by the User Configuring the General Characteristics of the Gateway Fieldbus elementABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Communication Characteristics Appendix a Technical CharacteristicsEnvironment Inputs Input data areaOutput data area OutputsGeneral data General data area16#10 Appendix B Default ConfigurationConfiguring Modbus exchanges 16#06Content of the Gateway’s Dpram Memory Input Data Memory Area16#0200 Appendix C Practical Example RSLogix Main Program LAD 2 MAINLUFP9Address Symbol Description ScanvalidationCmdreset Module Address Symbol DisplayAppendix C Practical Example RSLogix Numparam Appendix C Practical Example RSLogix Wrrunning Address Symbol Display Reserves relating to the RSLogix 500 exampleList of the Gateway’s DeviceNet Objects Appendix D DeviceNet ObjectsIntroduction to the Gateway’s DeviceNet Objects Class Required Instances InterfacesGraphical Representation of the Gateway’s DeviceNet Objects Identity Object class 16#01Services of instance 16#01 of class 16#01 Attributes of instance 16#01 of class 16#01Message Router Object class 16#02 DeviceNet Object class 16#03Services in class 16#04 Assembly Objects Class 16#04Services of instance 16#01 of class 16#03 Revision index of the Assembly Object classAttributes of instance 16#64 of class 16#04 Modbus Inputs Services of instances 16#64 and 16#96 of class 16#04Connection Object Class 16#05 Attributes of instance 16#96 of class 16#04 Modbus OutputsServices in class 16#05 Attributes of class 16#0516#83 Initial comm. characteristicsWatchdog timeout action Produced connection IDAccess Name Type Value 16#01 Get StateGet / Set Produced connection path Type Value16# 20 04 24 64 30 Type Value 16#07 Get / Set Produced connection size Type Value 16#04 Get / Set Produced connection ID #0 xxAttributes of instances 16#01 to 16#04 of class 16#05 Services in class 16#2BAcknowledge Handler Object class 16#2B Attributes of class 16#2BType Value 16#06 Get Data with ack path list size Services of instance 16#01 of class 16#2BData with ack path list 10.10. I/O Data Input Mapping Object Class 16#A0 Services in class 16#A0Services of instance 16#01 of class 16#A0 Attributes of class 16#A010.11. I/O Data Output Mapping Object Class 16#A1 Services in class 16#A1Services of instance 16#01 of class 16#A1 Attributes of class 16#A1Attributes of class 16#AA Diagnostic Object Class 16#AAServices in class 16#AA Attributes of instance 16#01 of class 16#AADeviceNet module status Access Name Need Type Value 16#09 Get LED statusModule type Changed data fieldServices of instance 16#01 of class 16#AA Appendix E Modbus Commands Preset Single Register command 16#06 Read Holding Registers Command 16#03Frame Field Value or properties Preset Multiple Registers Command 16#10 Modbus Protocol Exception ResponsesCode Name Description of the exception Exception Page User’s manual V1.0 2003-03