TP-Link TL-SG3424 manual Ethernet Cable

Page 15

L2 Managed Switch

Requirements for the distance between Ethernet cable and other pipelines are shown in the table.

 

 

Ethernet Cable

Other Pipelines

 

 

 

Min Parallel Net Length

 

Min Parallel-overlapping Net Height

 

L (mm1

 

H (mm1

 

 

 

 

Down-conductor

1000

 

300

 

 

 

 

PE

50

 

20

 

 

 

 

Service pipe

150

 

20

 

 

 

 

Compressed air pipe

150

 

20

 

 

 

 

Thermal pipe (not wrapped1

500

 

500

 

 

 

 

Thermal pipe (wrapped1

300

 

300

 

 

 

 

Gas pipe

300

 

20

 

 

 

 

The two diagrams below demonstrate parallel net length and parallel-overlapping net height.

Note: The above minimum net length/height is required when metal raceway is not used. If any requirements cannot be met, you can add a steel tube or metal raceway for shielding.

Requirements for the distance between Ethernet cable and high-power electric devices are in following tables.

Cable

 

Pave Way

 

 

Min Parallel

 

 

 

Length (mm1

 

 

 

 

 

 

 

 

 

 

 

<2kVA

 

Parallel cabling

130

 

 

 

 

 

 

One is in the grounded metal raceway or metal pipe

70

powerline

 

 

 

 

 

 

 

The both are in the grounded metal raceway or metal pipe

10

 

 

 

 

 

 

 

 

2~5kVA

 

Parallel cabling

300

 

 

 

 

 

 

One is in the grounded metal raceway or metal pipe

150

powerline

 

 

 

 

 

 

 

The both are in the grounded metal raceway or metal pipe

80

 

 

 

 

 

 

 

 

>5kVA

 

Parallel cabling

600

 

 

 

 

 

 

One is in the grounded metal raceway or metal pipe

300

powerline

 

 

 

 

 

 

 

The both are in the grounded metal raceway or metal pipe

150

 

 

 

 

 

 

 

 

 

 

 

 

 

Device

 

Min Distance (m1

 

 

 

 

 

 

 

Switch case

 

1.00

 

 

 

 

 

 

Transformer room

2.00

 

 

 

 

 

 

Elevator tower

2.00

 

 

 

 

 

 

Air-conditioner room

2.00

 

 

 

 

 

 

 

 

Lightning Protection 11

Image 15
Contents Installation Guide Copyright & Trademarks FCC Statement Audience Contents Front Panel CCCCCCCCCCCIntroductionProduct Overview AppearanceLEDs Front panel of TL-SG3424P is shown as the following figure Rear Panel Port FeatureGrounding Terminal CCCCCCCCCCCInstallation Package Contents2222Safety Precautions Clearness Electromagnetic InterferenceLightening Protection Desktop Installation 2222Installation Tools2222Product Installation Installation SiteRack Installation Requirements for Cabling Indoors CCCCCCCCCCCLightning ProtectionCabling Reasonably Requirements for Cabling OutdoorsEthernet Cable Connecting to the Grounding Bar Connecting to the Ground via the Power Supply3333Connect to Ground 3333Equipotential Bonding 3333Use Lightning Arrester CCCCCCCCCCCConnection Ethernet Port4444SFP Port 4444Verify Installation 4444Power On4444Console Port 4444Initialization For TL-SG3210 SwitchConfigure the Switch via GUI CCCCCCCCCCCConfigurationLogon by a Console Port 5555Configure the Switch Using CLISelect the port to connect in -6, and click OK Logon by Telnet Type cmd in the prompt Run window as -10 and click OK FFFFFFFFFFFFFLog in the Switch Qqqq Why does the Power LED work abnormally? AAAAAAAAAAAATroubleshootingAAAAAAAAAAAAHardware Specifications AAAAAAAAAAAATechnical Support L2 Managed Switch Tel +86 755 Mail support@tp-link.com 7106504453 REV2.0.0