Rackmount Solutions VA 10000 Commissioning of an External Battery Cabinet, External Battery Packs

Page 16

4.1 Commissioning of an External Battery Cabinet

The following table shows the designations of the battery cabinets which are available for the UPS devices.

Table 2. External Battery Packs

Model

Cabinet

Batteries

 

 

 

 

 

 

Active 700

NA

NA

 

 

 

Active 1000

BPActive1000-19

2x (3 x 7. 2 Ah)

 

 

 

Active 2000

BPActive3000-19

2x (8 x 7. 2 Ah)

 

 

 

Active 3000

BPActive3000-19

2x (8 x 7. 2 Ah)

 

 

 

Disconnect the UPS from the mains and the loads from the UPS.

CAUTION: Make sure that the circuit breaker on the external battery cabinet is in the OFF position.

CAUTION: Battery cabinets are not interchangeable. Use ONLY the battery cabinet indicated above.

Connect the battery cabinet types BP1000, BP3000 to the UPS using the supplied cable. The connection scheme is shown in the figures below. Switch the circuit breaker on the battery cabinet to the ON position.

The UPS is now ready for operation.

NOTE: Battery charging times may be longer when using an external battery cabinet.

WARNING:

Battery Plug 1

Circuit Breaker

Battery Plug 2

Fig. 13: Connection of Battery Extensions for devices Active 1000

WARNING: The connection of the external battery cabinet may only be done by qualified personnel in accordance with the applicable safety regulations.

CAUTION: For the electrical installation, the maximum load capacity of the connection cable has to be taken into account.

12

Chloride Active and E-Series UPS User Manual

Image 16 Contents
Page Important Safety Instructions FCC ComplianceChloride Introduction Operational Characteristics E-Series Technical Support and Service Active Safety NotesChloride Introduction Registering your Chloride Active UPSPage Display and Operation Elements Active Overload LoadFront Rear Active 700Active 2000 Active 3000 Rear ViewInstallation and operating notes SafetyActive Rackmount Series Connection of a battery pack Battery Cabinets Type of Battery Packs Maximum Number of Packs Mechanical AttachmentUnit Rear View and Connections Active 700-19 and Active Active700-19Active 2000-19 and Active Active3000-19Active Installation and Commissioning External Battery Packs Commissioning of an External Battery CabinetModel Cabinet Batteries Operational Characteristics Active Ready for Operation Check Self TestModes of Operation Battery Operation, Inverter On Mains FailureNormal Operation, Inverter On Mains Available Bypass Operation, Inverter OFF Overload 140% Front Display Panel During Bypass Operation Overload 140%Description of the Interface Active Standard Interface COM aInterface COM a Optional Interface COM BPin Number Condition INV Shutdown Cleaning Maintenance ActiveStorage Troubleshooting Troubleshooting ActiveProblem Possible Cause Action to Take Page Active Tower and Rackmount Specifications Chloride Active UPS North AmericaBattery extension SignalsUPS Model Active Mechanical DataUPS Model Active Connections Mains connections Load connectionActive Rackmount Technical Data for North American Models Operating DataBattery Lifetime Typical lifetime of the batteriesTechnical Support and Service E-Series Registering your Chloride E-Series UPSPage Display and Operation Elements E-Series Switch for at least 1 second. a tone sounds Series E61 and E101 E41 or E61Series E203 E81 or E101Series Installation and Commissioning Installation of the E-Series HardwiredPage Minimum Requirements for E-Series UPS Installation Lbs AwgWiring Diagram for the E101 Commissioning of the E-Series Starting Up the E-SeriesDryers, vacuum cleaners BPE61 Technical data of the connection cable E101 E203Self Test Modes of Operation Bypass Operation, Inverter OFF Overload 140% Description of the Interface E-Series Optional Interface COM B Emergency Power Off EPO Series Models E153X and E203X onlyMaintenance E-Series Troubleshooting E-Series Page Series Specifications Chloride E-Series UPS North AmericaBPE101 Weight lbs 337 894 Dimensions HxWxD in. mm E101XA E203XA E41XA E81 E153XA Connections Optional Power Distribution Units PDU available 4 -10 kVA Optional Power Distribution UnitsChloride Power Protection