Rackmount Solutions VA 700, VA 3000, VA 10000, VA 6000, VA 20000 manual BPE61

Page 43

13.4 Commissioning of an External Battery Cabinet

The following table shows the designations of the battery cabinets which are available for the UPS devices.

Table 8. External Battery Packs

Model

Cabinet

 

Batteries

 

 

 

 

 

 

 

 

E61 (E41)

BPE61

2x

(20 x 7. 2 Ah)

 

 

 

 

 

E101

(E81)/

BPE101

1x

(20 x 38 Ah)

E203

(E153)

 

 

 

 

 

 

 

 

Disconnect the UPS from the mains and the loads from the UPS.

CAUTION: Make sure that the circuit breaker on the external battery cabinet is in the OFF position.

CAUTION: Battery cabinets are not interchangeable. Use ONLY the battery cabinet indicated above.

Connect the battery cabinet types BP1000, BP3000 and BPE61 to the UPS using the supplied cable. The connection scheme is shown in the figures below. With type BPE101, make the hard-wired connection between UPS and the battery cabinet (see figures 28 and 29 on page 40).

Switch the circuit breaker on the battery cabinet to the ON position.

The UPS is now ready for operation.

NOTE: Battery charging times may be longer when using an external battery cabinet.

Battery Plug for Connection of an

Additional Battery Extension

Fig. 27: Connection of an External Battery Cabinet to Type E61

Chloride Active and E-Series UPS User Manual

39

Image 43 Contents
Page FCC Compliance Important Safety InstructionsChloride Introduction Operational Characteristics E-Series Registering your Chloride Active UPS Technical Support and Service ActiveSafety Notes Chloride IntroductionPage Overload Load Display and Operation Elements ActiveFront Active 700 RearActive 3000 Rear View Active 2000Installation and operating notes SafetyActive Rackmount Series Mechanical Attachment Connection of a battery packBattery Cabinets Type of Battery Packs Maximum Number of PacksActive700-19 Unit Rear View and Connections Active 700-19 and ActiveActive3000-19 Active 2000-19 and ActiveActive Installation and Commissioning External Battery Packs Commissioning of an External Battery CabinetModel Cabinet Batteries Self Test Operational Characteristics Active Ready for Operation CheckModes of Operation Battery Operation, Inverter On Mains FailureNormal Operation, Inverter On Mains Available Front Display Panel During Bypass Operation Overload 140% Bypass Operation, Inverter OFF Overload 140%Standard Interface COM a Description of the Interface ActiveInterface COM a Optional Interface COM BPin Number Condition INV Shutdown Cleaning Maintenance ActiveStorage Troubleshooting Troubleshooting ActiveProblem Possible Cause Action to Take Page Chloride Active UPS North America Active Tower and Rackmount SpecificationsMechanical Data Battery extensionSignals UPS Model ActiveLoad connection UPS Model Active Connections Mains connectionsOperating Data Active Rackmount Technical Data for North American ModelsTypical lifetime of the batteries Battery LifetimeRegistering your Chloride E-Series UPS Technical Support and Service E-SeriesPage Display and Operation Elements E-Series Switch for at least 1 second. a tone sounds E41 or E61 Series E61 and E101E81 or E101 Series E203Installation of the E-Series Hardwired Series Installation and CommissioningPage Lbs Awg Minimum Requirements for E-Series UPS InstallationWiring Diagram for the E101 Starting Up the E-Series Commissioning of the E-SeriesDryers, vacuum cleaners BPE61 E101 E203 Technical data of the connection cableSelf Test Modes of Operation Bypass Operation, Inverter OFF Overload 140% Description of the Interface E-Series Optional Interface COM B Series Models E153X and E203X only Emergency Power Off EPOMaintenance E-Series Troubleshooting E-Series Page Chloride E-Series UPS North America Series SpecificationsBPE101 Weight lbs 337 894 Dimensions HxWxD in. mm E101XA E203XA E41XA E81 E153XA Connections Optional Power Distribution Units Optional Power Distribution Units PDU available 4 -10 kVAChloride Power Protection