Warning
Do not strip more than the recommended amount of wire. (See Figure 26.) Stripping more than the recommended amount can create a safety hazard by leaving exposed wire on the terminal block after installation. E10
8mm ±1mm
(0.31in. ±0.039in.)
451
Figure 26. Stripped Wire
4.Connect the frame ground wire to the terminal marked with the ground symbol by inserting the wire into the terminal and tightening the connection with a flathead screwdriver, as shown in Figure 27.
Warning
When installing this equipment, always ensure that the frame ground connection is installed first and disconnected last. E11
452
Figure 27. Connecting the Stripped Wire
5.Connect the positive feed wire to the terminal block marked (+).
6.Connect the negative feed wire to the terminal block marked (-).
Warning
Check to see if there are any exposed copper strands coming from the installed wires. When this installation is done correctly there should be no exposed copper wire strands extending from the terminal block. Any exposed wiring can conduct harmful levels of electricity to persons touching the wires. E12
71