TDK 5KW technical manual Multiple load connection with distribution terminals, Grounding outputs

Page 33

Load lines, twisted pair, shortest length possible.

+V

Power -V

Supply

-Rem.sense -Local sense +Local sense +Rem.sense

+Load#1

+Load#2

+Load#3

Fig.3-13: Multiple loads connection, radial distribution, local sense

3.9.10 Multiple load connection with distribution terminals

If remotely located output distribution terminals are used, the power supply output terminals should be connected to the distribution terminals by pair of twisted and/or shielded wires. Each load should be separately connected to the remote distribution terminals (see Fig.3-14).

If remote sensing is required, the sensing wires should be connected to the distribution terminals or at the most critical load.

+V

Power -V

Supply

-Rem.sense -Local sense +Local sense +Rem.sense

Distribution terminal

+ Load#1

+V

 

+ Load#2

-V

+ Load#3

Fig.3-14: Multiple loads connection with distribution terminal

3.9.11 Grounding outputs

Either the positive or negative output terminals can be grounded. To avoid noise problems caused by common-mode current flowing from the load to ground, it is recommended to ground the output terminal as close as possible to the power supply chassis ground.

Always use two wires to connect the load to the power supply regardless of how the system is grounded.

WARNING

Models up to 60VDC Rated Output shall not float outputs more than +/-60VDC above/below chassis ground. Models > 60VDC Rated Output shall not float outputs more than +/-600VDC above/below chassis ground. 25

83-515-000 Rev. B

Image 33
Contents 2U Genesystm 5kW Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ……………… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Progamming OPTION………………………………… Warranty Service Limitation of WarrantyDisclaimer Trademark InformationSafety Instructions FCC Compliance Notice Environmental ConditionsSICHERHEITS-INSTALLATIONS Anweisungen Anderungen and Bauteileersatz Sicherheits-und WarnsymboleSICHERHEITS-HINWEISE UmweltbedingungenGeneral Information Features and optionsIntroduction General DescriptionControl via the serial communication port Multiple output power systemAnalog voltage programming and monitoring Parallel operationAccessories Specifications 83-515-000 Rev. B Supplemental Characteristics Genesystm 5000W Power Supplies Outline Drawings General InstallationPreparation for USE Initial InspectionsRack Mounting To install the Power Supply in a rackLOCATION, Mounting and Cooling AC Source RequirementsAC Input Connector AC Input Power ConnectionAC Input Wire Connection AC Input CordStripped Wires installed in Strain Relief Prior to Operation TURN-ON Checkout ProcedureConstant Voltage Check Constant Current CheckBaud Rate Setting RS-232 and RS-485 only Address SettingUVL Check Foldback CheckLoad Wiring Connecting the LoadCurrent Carrying Capacity AWGWire termination Noise and Impedance EffectsInductive loads Making the load connections 8V to 100V Models Load wires connection, 8V to 100V models 83-515-000 Rev. B Connecting single loads, local sensing default Connecting single loads, remote sensingConnecting multiple loads, radial distribution method Grounding outputs Multiple load connection with distribution terminalsLocal and Remote Sensing Sense wiringOutput Terminal Grounding Local sensing10.4 J2 sense connector technical information Remote sensingRepackaging for Shipment Front Panel Controls and Indicators Front and Rear Panel Controls and ConnectorsSection Rear Panel Connections and Controls SW1 setup DIP-switch Rear Panel SW1 Setup Switch1 SW1 position function Resetting the SW1 switchMaking J1 connections Rear Panel J1 Programming and Monitoring ConnectorEnain SignalIfcom LocalConstant Current Mode Constant Voltage ModeLocal Operation IntroductionResetting the OVP circuit Setting the OVP levelAutomatic Crossover Over Voltage Protection OVP4A Under Voltage Limit UVL Output SHUT-OFF SO Control VIA Rear Panel J1 ConnectorFoldback Protection Output ON/OFF ControlENABLE/DISABLE Control VIA Rear Panel J1 Connector CV/CC SignalPsok Signal Last Setting Memory Over Temperature Protecton OTPSAFE-START and AUTO-RESTART Modes Series OperationSeries connection, local sensing Series connection for increased output voltageSeries connection for positive/negative output voltages Series connection for positive and negative output voltageParallel Operation Setting the units as Master or Slave Advanced parallel configurationMaster and Slave units default operation Connection to the loadTo release units from Slave mode Current display accuracyAST OFF *OUT OFF Front Panel Locking DAISY-CHAIN ConnectionUnlocked front panel Locked front panelRemote Analog Programming LOCAL/REMOTE Analog ControlLOCAL/REMOTE Analog Indication J1 connector, rear panel view Remote resistive programming Resisitive Programming of Output Voltage and Current LimitRemote Monitoring of Output Voltage and Current Configuration RS232 & RS485 Remote ControlRear Panel RS232/RS485 Connector 6 RS232/RS485 port in Local modeFront panel in Remote mode MD Mode enable Serial communication mode MD Mode DescriptionMD Mode SRQ MD Mode SRQ RetransmissionSingle power supply Connecting Power Supplies to RS232 or RS485 BUSCommunication Interface Protocol Command SET Description Error MessagesInitialization Control Commands ID Control CommandsOutput Control Commands Filter DVC?FILTER? OUT?General Global Output CommandsEnable MD Mode MD Mode Option Required Single Byte CommandsDisable SRQ retransmission MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredPrint Power On Time Addressed commands with response Read registersTest if MD Mode is Installed Addressed commands without response Acknowledge SRQ1010 None Disable retransmission of SRQs by sup Voltage programming range Status Control Commands STATUS, Error and SRQ RegistersStatus Registers Conditional RegistersFold BITService Request Enable and Event Registers Fault Enable RegisterFault Event Register Status Event Register Status Enable RegisterPower supply set-up Serial Communication Test SET-UPCommunication Test Isolated Analog Programming Option Specifications1 0-5V/0-10V Option PN IS510 PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance OUP Fuse Rating

5KW specifications

The TDK 5KW is a cutting-edge power supply solution designed to deliver high performance and efficiency in a compact form. This robust unit is engineered for various applications, including industrial automation, telecommunications, and renewable energy systems. With a focus on reliability and durability, the TDK 5KW is an excellent choice for users seeking a dependable power source.

One of the standout features of the TDK 5KW is its advanced power conversion technology. It utilizes a high-frequency switching technique that allows for superior efficiency, minimizing energy loss and reducing heat generation. By operating at high efficiency levels, the TDK 5KW helps lower operational costs while contributing to a greener environment.

The power supply is equipped with a wide input voltage range, making it suitable for global applications. It can accept input voltages from 90 to 264 VAC, ensuring versatility and compatibility with various electrical systems. This feature also enhances its usability in different geographic regions without the need for additional transformers or converters.

Another significant characteristic of the TDK 5KW is its modular design, which allows for easy integration into existing systems. The power supply features a compact footprint, making it ideal for installations where space is at a premium. Moreover, its robust construction ensures that it can withstand harsh operating conditions, including extreme temperatures and vibrations.

Reliability is further enhanced through built-in protection features, including overvoltage, overcurrent, and short-circuit protection. These safety mechanisms not only safeguard the power supply itself but also protect the connected equipment from damage, making it a trustworthy choice for critical applications.

The TDK 5KW also supports various communication protocols, enabling seamless integration into modern automation systems. This feature allows for real-time monitoring and control, providing users with essential data to optimize performance and troubleshoot issues efficiently.

In summary, the TDK 5KW is a powerful, efficient, and reliable power supply solution that caters to a broad range of applications. Its advanced technologies, modular design, and robust safety features make it an essential component for anyone looking to enhance their electrical systems with a high-quality power source.