TDK 5KW technical manual Global Output Commands, General

Page 66

26

MODE?

Returns the power supply operation mode. When the power supply is On (OUT

1) it will return “CV” or “CC”. When the power supply is OFF (OUT 0 or fault

 

 

shutdown) it will return “OFF”.

27

MS?

Returns the Master/Slave setting. Master: n= 1, 2, 3, or 4 Slave: n=0

NOTES:

1.In Advanced parallel mode (refer to Sec. 5.15.2), “n” is the total system current.

2.In Advanced parallel mode, “MC?” returns the Master unit current multiplied by the number of slave units +1.

7.9 GLOBAL OUTPUT COMMANDS

7.9.1 GENERAL

All supplies, even if not the currently addressed supply, receiving a global comm. and will execute the command. No response to the PC issuing the command will be returned to the PC. The PC issu- ing the command will be responsible to delay and any other communications until the command is execute. 200 Ms minimum is the suggested delay.

If the command contains an error, out of range values for example, no error report will be sent to the issuing PC.

Table 7-3

1.

GRST

Reset. Brings the power supply to a safe and known state:

 

 

 

Output voltage: 0V, output current: 0A, OUT: Off, Remote: RMT 1,

 

 

AST: Off

OVP: Max,

UVL: 0.

 

 

The conditional register (FLT and STAT) are updated. Other registers are not

 

 

changed.

 

 

 

 

Non-Latching faults (FB, OVP, SO) are cleared, OUT fault stays

2.

GPV n

Sets the output voltage value in volts. The range of voltage values is shown in

 

 

Table 7-5. ‘n’ may be up to 12 char plus dec. pt

 

3.

GPC n

Program the output current value in amperes. The range of current values is

 

 

shown in Table 7-6. ‘n’ may be up to 12 char plus dec. pt

 

4.

GOUT

Turns the output to ON or OFF:

 

 

 

 

“OUT 1/ON” = turn on

 

 

 

 

“OUT 0/OFF” = turnoff, clears CV and CC bits in the Status Condition (STAT).

 

 

OUT ON will respond with “E07’ if the output cannot be turned on because of a

 

 

latching fault (OTP< AC, ENA, SO) shutdown.

 

5.

GSAV

Save present settings. Same settings as power-down last settings listed in Er-

 

 

ror!

 

 

 

 

Reference source not found. Except the address and Baud rate are not saved

 

 

Saves to the RAM. These settings are erased when the supply power is

 

 

switched off and the new ‘last settings’ are saved.

 

6.

GRCL

Recall last settings. Settings are from last power-down or from last ‘SAV’ or

 

 

‘GSAV’ command. Address and Baud rate are not recalled so communication is

 

 

not interrupted.

 

 

58

83-515-000 Rev. B

Image 66
Contents 2U Genesystm 5kW Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ……………… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Progamming OPTION………………………………… Disclaimer Limitation of WarrantyWarranty Service Trademark InformationSafety Instructions Environmental Conditions FCC Compliance NoticeSICHERHEITS-INSTALLATIONS Anweisungen SICHERHEITS-HINWEISE Sicherheits-und WarnsymboleAnderungen and Bauteileersatz UmweltbedingungenIntroduction Features and optionsGeneral Information General DescriptionAnalog voltage programming and monitoring Multiple output power systemControl via the serial communication port Parallel operationAccessories Specifications 83-515-000 Rev. B Supplemental Characteristics Genesystm 5000W Power Supplies Outline Drawings Preparation for USE InstallationGeneral Initial InspectionsLOCATION, Mounting and Cooling To install the Power Supply in a rackRack Mounting AC Source RequirementsAC Input Wire Connection AC Input Power ConnectionAC Input Connector AC Input CordStripped Wires installed in Strain Relief Constant Voltage Check TURN-ON Checkout ProcedurePrior to Operation Constant Current CheckUVL Check Address SettingBaud Rate Setting RS-232 and RS-485 only Foldback CheckCurrent Carrying Capacity Connecting the LoadLoad Wiring AWGWire termination Noise and Impedance EffectsInductive loads Making the load connections 8V to 100V Models Load wires connection, 8V to 100V models 83-515-000 Rev. B Connecting single loads, local sensing default Connecting single loads, remote sensingConnecting multiple loads, radial distribution method Multiple load connection with distribution terminals Grounding outputsOutput Terminal Grounding Sense wiringLocal and Remote Sensing Local sensing10.4 J2 sense connector technical information Remote sensingRepackaging for Shipment Front and Rear Panel Controls and Connectors Front Panel Controls and IndicatorsSection Rear Panel Connections and Controls Rear Panel SW1 Setup Switch SW1 setup DIP-switchResetting the SW1 switch 1 SW1 position functionRear Panel J1 Programming and Monitoring Connector Making J1 connectionsIfcom SignalEnain LocalLocal Operation Constant Voltage ModeConstant Current Mode IntroductionAutomatic Crossover Setting the OVP levelResetting the OVP circuit Over Voltage Protection OVPFoldback Protection Output SHUT-OFF SO Control VIA Rear Panel J1 Connector4A Under Voltage Limit UVL Output ON/OFF ControlENABLE/DISABLE Control VIA Rear Panel J1 Connector CV/CC SignalPsok Signal SAFE-START and AUTO-RESTART Modes Over Temperature Protecton OTPLast Setting Memory Series OperationSeries connection for increased output voltage Series connection, local sensingSeries connection for positive and negative output voltage Series connection for positive/negative output voltagesParallel Operation Master and Slave units default operation Advanced parallel configurationSetting the units as Master or Slave Connection to the loadTo release units from Slave mode Current display accuracyAST OFF *OUT OFF Unlocked front panel DAISY-CHAIN ConnectionFront Panel Locking Locked front panelRemote Analog Programming LOCAL/REMOTE Analog ControlLOCAL/REMOTE Analog Indication J1 connector, rear panel view Resisitive Programming of Output Voltage and Current Limit Remote resistive programmingRemote Monitoring of Output Voltage and Current RS232 & RS485 Remote Control ConfigurationRear Panel RS232/RS485 Connector 6 RS232/RS485 port in Local modeFront panel in Remote mode MD Mode SRQ MD Mode DescriptionMD Mode enable Serial communication mode MD Mode SRQ RetransmissionConnecting Power Supplies to RS232 or RS485 BUS Single power supplyCommunication Interface Protocol Error Messages Command SET DescriptionInitialization Control Commands ID Control CommandsOutput Control Commands FILTER? DVC?Filter OUT?Global Output Commands GeneralDisable SRQ retransmission MD Mode Option Required Single Byte CommandsEnable MD Mode MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredTest if MD Mode is Installed Addressed commands with response Read registersPrint Power On Time Addressed commands without response Acknowledge SRQ1010 None Disable retransmission of SRQs by sup Voltage programming range STATUS, Error and SRQ Registers Status Control CommandsConditional Registers Status RegistersBIT FoldService Request Enable and Event Registers Fault Enable RegisterFault Event Register Status Enable Register Status Event RegisterPower supply set-up Serial Communication Test SET-UPCommunication Test 1 0-5V/0-10V Option PN IS510 SpecificationsIsolated Analog Programming Option PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance Fuse Rating OUP

5KW specifications

The TDK 5KW is a cutting-edge power supply solution designed to deliver high performance and efficiency in a compact form. This robust unit is engineered for various applications, including industrial automation, telecommunications, and renewable energy systems. With a focus on reliability and durability, the TDK 5KW is an excellent choice for users seeking a dependable power source.

One of the standout features of the TDK 5KW is its advanced power conversion technology. It utilizes a high-frequency switching technique that allows for superior efficiency, minimizing energy loss and reducing heat generation. By operating at high efficiency levels, the TDK 5KW helps lower operational costs while contributing to a greener environment.

The power supply is equipped with a wide input voltage range, making it suitable for global applications. It can accept input voltages from 90 to 264 VAC, ensuring versatility and compatibility with various electrical systems. This feature also enhances its usability in different geographic regions without the need for additional transformers or converters.

Another significant characteristic of the TDK 5KW is its modular design, which allows for easy integration into existing systems. The power supply features a compact footprint, making it ideal for installations where space is at a premium. Moreover, its robust construction ensures that it can withstand harsh operating conditions, including extreme temperatures and vibrations.

Reliability is further enhanced through built-in protection features, including overvoltage, overcurrent, and short-circuit protection. These safety mechanisms not only safeguard the power supply itself but also protect the connected equipment from damage, making it a trustworthy choice for critical applications.

The TDK 5KW also supports various communication protocols, enabling seamless integration into modern automation systems. This feature allows for real-time monitoring and control, providing users with essential data to optimize performance and troubleshoot issues efficiently.

In summary, the TDK 5KW is a powerful, efficient, and reliable power supply solution that caters to a broad range of applications. Its advanced technologies, modular design, and robust safety features make it an essential component for anyone looking to enhance their electrical systems with a high-quality power source.