TDK 5KW technical manual Wire termination, Noise and Impedance Effects, Inductive loads

Page 28

Cross sect.

Resistivity

 

Maximum length in meters to limit

 

area

 

voltage drop to 1V or less

 

OHM/Km

 

 

(mm²)

10A

20A

50A

100A

200A

400A

 

2.5

8.21

12.0

6.0

2.4

1.2

0.6

0.3

4

5.09

18.6

9.8

4.0

2

1.0

0.5

6

3.39

29.4

14.8

5.8

2.9

1.45

0.7

10

1.95

51.2

25.6

10.2

5.1

2.5

1.25

16

1.24

80.0

40.0

16.0

8

4

2

25

0.795

125.0

62.0

25.2

12.6

6.3

3.1

35

0.565

177.0

88.0

35.4

17.7

8.8

4.4

Table 3-3: Maximum wire length for 1 V drop on lead (in meters)

For currents not shown in Table 3-2 and 3-3, use the formula:

Maximum length=1000/(current x resistivity)

Where current is expressed in Amperes and resistivity in ohms/km or ohms/1000ft.

3.9.3Wire termination

The wires should be properly terminated with terminals securely attached. DO NOT use unterminated wires for load connection at the power supply.

CAUTION

When local sensing, a short from +LS or +S to -V or -S or -LS, will cause damage to the power supply. Reversing the sense wires might cause damage to the power supply in local and remote sensing. (Do not connect -S to +V or +S to -V).

3.9.4Noise and Impedance Effects

To minimize the noise pickup or radiation, the load wires and remote sense wires should be twisted pairs to the shortest possible length. Shielding of sense leads may be necessary in high noise envi- ronments. Where shielding is used, connect the shield to the chassis via a rear panel Ground screw. Even if noise is not a concern, the load and remote sense wires should be twisted-pairs to reduce coupling, which might impact the stability of power supply. The sense leads should be separated from the power leads.

Twisting the load wires reduces the parasitic inductance of the cable, which could produce high fre- quency voltage spikes at the load and the output of the power supply, because of current variation in the load itself.

The impedance introduced between the power supply output and the load could make the ripple and noise at the load worse than the noise at the power supply rear panel output. Additional filtering with bypass capacitors at the load terminals may be required to bypass the high frequency load current.

3.9.5Inductive loads

Inductive loads can produce voltage spikes that may be harmful to the power supply. A diode should be connected across the output. The diode voltage and current rating should be greater than the power supply maximum output voltage and current rating. Connect the cathode to the positive output and the anode to the negative output of the power supply.

Where positive load transients such as back EMF from a motor may occur, connect a surge suppres- sor across the output to protect the power supply. The breakdown voltage rating of the suppressor must be approximately 10% higher than the maximum output voltage of the power supply.

20

83-515-000 Rev. B

Image 28
Contents 2U Genesystm 5kW Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ……………… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Progamming OPTION………………………………… Limitation of Warranty Warranty ServiceDisclaimer Trademark InformationSafety Instructions Environmental Conditions FCC Compliance NoticeSICHERHEITS-INSTALLATIONS Anweisungen Sicherheits-und Warnsymbole Anderungen and BauteileersatzSICHERHEITS-HINWEISE UmweltbedingungenFeatures and options General InformationIntroduction General DescriptionMultiple output power system Control via the serial communication portAnalog voltage programming and monitoring Parallel operationAccessories Specifications 83-515-000 Rev. B Supplemental Characteristics Genesystm 5000W Power Supplies Outline Drawings Installation GeneralPreparation for USE Initial InspectionsTo install the Power Supply in a rack Rack MountingLOCATION, Mounting and Cooling AC Source RequirementsAC Input Power Connection AC Input ConnectorAC Input Wire Connection AC Input CordStripped Wires installed in Strain Relief TURN-ON Checkout Procedure Prior to OperationConstant Voltage Check Constant Current CheckAddress Setting Baud Rate Setting RS-232 and RS-485 onlyUVL Check Foldback CheckConnecting the Load Load WiringCurrent Carrying Capacity AWGNoise and Impedance Effects Wire terminationInductive loads Making the load connections 8V to 100V Models Load wires connection, 8V to 100V models 83-515-000 Rev. B Connecting single loads, remote sensing Connecting single loads, local sensing defaultConnecting multiple loads, radial distribution method Multiple load connection with distribution terminals Grounding outputsSense wiring Local and Remote SensingOutput Terminal Grounding Local sensingRemote sensing 10.4 J2 sense connector technical informationRepackaging for Shipment Front and Rear Panel Controls and Connectors Front Panel Controls and IndicatorsSection Rear Panel Connections and Controls Rear Panel SW1 Setup Switch SW1 setup DIP-switchResetting the SW1 switch 1 SW1 position functionRear Panel J1 Programming and Monitoring Connector Making J1 connectionsSignal EnainIfcom LocalConstant Voltage Mode Constant Current ModeLocal Operation IntroductionSetting the OVP level Resetting the OVP circuitAutomatic Crossover Over Voltage Protection OVPOutput SHUT-OFF SO Control VIA Rear Panel J1 Connector 4A Under Voltage Limit UVLFoldback Protection Output ON/OFF ControlCV/CC Signal ENABLE/DISABLE Control VIA Rear Panel J1 ConnectorPsok Signal Over Temperature Protecton OTP Last Setting MemorySAFE-START and AUTO-RESTART Modes Series OperationSeries connection for increased output voltage Series connection, local sensingSeries connection for positive and negative output voltage Series connection for positive/negative output voltagesParallel Operation Advanced parallel configuration Setting the units as Master or SlaveMaster and Slave units default operation Connection to the loadCurrent display accuracy To release units from Slave modeAST OFF *OUT OFF DAISY-CHAIN Connection Front Panel LockingUnlocked front panel Locked front panelLOCAL/REMOTE Analog Control Remote Analog ProgrammingLOCAL/REMOTE Analog Indication J1 connector, rear panel view Resisitive Programming of Output Voltage and Current Limit Remote resistive programmingRemote Monitoring of Output Voltage and Current RS232 & RS485 Remote Control Configuration6 RS232/RS485 port in Local mode Rear Panel RS232/RS485 ConnectorFront panel in Remote mode MD Mode Description MD Mode enable Serial communication modeMD Mode SRQ MD Mode SRQ RetransmissionConnecting Power Supplies to RS232 or RS485 BUS Single power supplyCommunication Interface Protocol Error Messages Command SET DescriptionID Control Commands Initialization Control CommandsOutput Control Commands DVC? FilterFILTER? OUT?Global Output Commands GeneralSingle Byte Commands Enable MD Mode MD Mode Option RequiredDisable SRQ retransmission MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredAddressed commands with response Read registers Print Power On TimeTest if MD Mode is Installed Addressed commands without response Acknowledge SRQ1010 None Disable retransmission of SRQs by sup Voltage programming range STATUS, Error and SRQ Registers Status Control CommandsConditional Registers Status RegistersBIT FoldFault Enable Register Service Request Enable and Event RegistersFault Event Register Status Enable Register Status Event RegisterSerial Communication Test SET-UP Power supply set-upCommunication Test Specifications Isolated Analog Programming Option1 0-5V/0-10V Option PN IS510 PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance Fuse Rating OUP

5KW specifications

The TDK 5KW is a cutting-edge power supply solution designed to deliver high performance and efficiency in a compact form. This robust unit is engineered for various applications, including industrial automation, telecommunications, and renewable energy systems. With a focus on reliability and durability, the TDK 5KW is an excellent choice for users seeking a dependable power source.

One of the standout features of the TDK 5KW is its advanced power conversion technology. It utilizes a high-frequency switching technique that allows for superior efficiency, minimizing energy loss and reducing heat generation. By operating at high efficiency levels, the TDK 5KW helps lower operational costs while contributing to a greener environment.

The power supply is equipped with a wide input voltage range, making it suitable for global applications. It can accept input voltages from 90 to 264 VAC, ensuring versatility and compatibility with various electrical systems. This feature also enhances its usability in different geographic regions without the need for additional transformers or converters.

Another significant characteristic of the TDK 5KW is its modular design, which allows for easy integration into existing systems. The power supply features a compact footprint, making it ideal for installations where space is at a premium. Moreover, its robust construction ensures that it can withstand harsh operating conditions, including extreme temperatures and vibrations.

Reliability is further enhanced through built-in protection features, including overvoltage, overcurrent, and short-circuit protection. These safety mechanisms not only safeguard the power supply itself but also protect the connected equipment from damage, making it a trustworthy choice for critical applications.

The TDK 5KW also supports various communication protocols, enabling seamless integration into modern automation systems. This feature allows for real-time monitoring and control, providing users with essential data to optimize performance and troubleshoot issues efficiently.

In summary, the TDK 5KW is a powerful, efficient, and reliable power supply solution that caters to a broad range of applications. Its advanced technologies, modular design, and robust safety features make it an essential component for anyone looking to enhance their electrical systems with a high-quality power source.