TDK 5KW technical manual 4A Under Voltage Limit UVL, Foldback Protection, Output ON/OFF Control

Page 45

5.4A UNDER VOLTAGE LIMIT (UVL)

The UVL prevents adjustment of the Output Voltage below a certain limit. The combination of UVL and OVP functions, allow the user to create a protection window for sensitive load circuitry.

5.4.1Setting the UVL level

Setting the UVL can be made when the power supply output is Enabled (On) or Disabled (Off). To set the UVL level, press the OVP/UVL button TWICE, so that the CURRENT meter shows “UUL”. The VOLTAGE meter shows the UVL setting level. Rotate the VOLTAGE encoder knob to adjust the UVL level. The display will show ‘UUL” and the setting value for 5 seconds after the adjustment has been completed and then will return to its previous state.

UVL setting values are limited at the maximum level to approximately 95% of the Output Voltage set- ting. Attempting to adjust the UVL above this limit will result in no response to the adjustment attempt. The minimum UVL setting is zero.

5.5 FOLDBACK PROTECTION

Foldback protection will shut down the power supply output if the load current exceeds the current limit setting level. This protection is useful when the load circuitry is sensitive to an overcurrent condi- tion.

5.5.1Setting the Foldback protection

To arm the Foldback protection, the FOLD button should be pressed so that the FOLD LED illumi- nates. In this condition, transition from Constant Voltage to Constant Current mode will activate the Foldback protection. Activation of the Foldback protection disables the power supply output, causes the ALARM LED to blink and displays “Fb” on the VOLTAGE meter.

5.5.2Resetting activated Foldback protection

There are four methods to reset an activated Foldback protection.

1.Press the OUT button. The power supply output is enabled and the Output Voltage and Current will return to their last setting. In this method, the Foldback protection remains armed, therefore if the load current is higher than the current limit setting, the Foldback protection will be activated again.

2.Press the FOLD button to cancel the Foldback protection. The power supply output will be dis- abled and the VOLTAGE display will show “OFF”. Press the OUT button to enable the power sup- ply output.

3.Turn the power supply output Off and then On using the SO control (refer to Section 5.7). In this method the Foldback protection remains armed, therefore if the load current is higher than the output current setting, the Foldback protection will be activated.

4.Turn the power supply Off using the AC On/Off switch, wait until the front panel display turns Off, then turn the unit back ON again. The power supply output is enabled and the Output Voltage and Current will return to their last setting. In this method, the Foldback protection remains armed, therefore if the load current is higher than the output current setting, the Foldback protection will be activated again.

5.6 OUTPUT ON/OFF CONTROL

The Output On/Off Enables or Disables the power supply output. Use this function to make adjust- ments to either the power supply or the load without shutting off the AC power. The Output On/Off can be activated from the front panel using the OUT button or from the rear panel J1 connector. The OUT button can be pressed at any time to Enable or Disable the power supply output. When the out- put is disabled, the Output Voltage and Current fall to zero and the VOLTAGE display shows “OFF”.

5.7 OUTPUT SHUT-OFF (SO) CONTROL VIA REAR PANEL J1 CONNECTOR

Contacts 2, 3 and 15 of J1 (Fig.4-2, Item 5) serve as Output Shut-Off (SO) terminals. The SO termi- nals accept a 2.5V to 15V signal or Open-Short contact to disable or enable the power supply output. The SO function will be activated only when a transition from On to Off is detected after applying AC power to the unit. (Thus, in Auto-Restart mode, the output will be Enabled after applying AC power; even if SO is at an Off level). After an On to Off transition it is detected, the SO will Enable or Disable the power supply output according to the signal level or the short/open applied to J1. This function is

37

83-515-000 Rev. B

Image 45
Contents 2U Genesystm 5kW Page Page Genesys Manual Supplement Table of Contents Front and Rear Panel Controls and Connectors ……………… Remote Analog PROGRAMMING……………………………………………… Isolated Analog Progamming OPTION………………………………… Warranty Service Limitation of WarrantyDisclaimer Trademark InformationSafety Instructions FCC Compliance Notice Environmental ConditionsSICHERHEITS-INSTALLATIONS Anweisungen Anderungen and Bauteileersatz Sicherheits-und WarnsymboleSICHERHEITS-HINWEISE UmweltbedingungenGeneral Information Features and optionsIntroduction General DescriptionControl via the serial communication port Multiple output power systemAnalog voltage programming and monitoring Parallel operationAccessories Specifications 83-515-000 Rev. B Supplemental Characteristics Genesystm 5000W Power Supplies Outline Drawings General InstallationPreparation for USE Initial InspectionsRack Mounting To install the Power Supply in a rackLOCATION, Mounting and Cooling AC Source RequirementsAC Input Connector AC Input Power ConnectionAC Input Wire Connection AC Input CordStripped Wires installed in Strain Relief Prior to Operation TURN-ON Checkout ProcedureConstant Voltage Check Constant Current CheckBaud Rate Setting RS-232 and RS-485 only Address SettingUVL Check Foldback CheckLoad Wiring Connecting the LoadCurrent Carrying Capacity AWGWire termination Noise and Impedance EffectsInductive loads Making the load connections 8V to 100V Models Load wires connection, 8V to 100V models 83-515-000 Rev. B Connecting single loads, local sensing default Connecting single loads, remote sensingConnecting multiple loads, radial distribution method Grounding outputs Multiple load connection with distribution terminalsLocal and Remote Sensing Sense wiringOutput Terminal Grounding Local sensing10.4 J2 sense connector technical information Remote sensingRepackaging for Shipment Front Panel Controls and Indicators Front and Rear Panel Controls and ConnectorsSection Rear Panel Connections and Controls SW1 setup DIP-switch Rear Panel SW1 Setup Switch1 SW1 position function Resetting the SW1 switchMaking J1 connections Rear Panel J1 Programming and Monitoring ConnectorEnain SignalIfcom LocalConstant Current Mode Constant Voltage ModeLocal Operation IntroductionResetting the OVP circuit Setting the OVP levelAutomatic Crossover Over Voltage Protection OVP4A Under Voltage Limit UVL Output SHUT-OFF SO Control VIA Rear Panel J1 ConnectorFoldback Protection Output ON/OFF ControlENABLE/DISABLE Control VIA Rear Panel J1 Connector CV/CC SignalPsok Signal Last Setting Memory Over Temperature Protecton OTPSAFE-START and AUTO-RESTART Modes Series OperationSeries connection, local sensing Series connection for increased output voltageSeries connection for positive/negative output voltages Series connection for positive and negative output voltageParallel Operation Setting the units as Master or Slave Advanced parallel configurationMaster and Slave units default operation Connection to the loadTo release units from Slave mode Current display accuracyAST OFF *OUT OFF Front Panel Locking DAISY-CHAIN ConnectionUnlocked front panel Locked front panelRemote Analog Programming LOCAL/REMOTE Analog ControlLOCAL/REMOTE Analog Indication J1 connector, rear panel view Remote resistive programming Resisitive Programming of Output Voltage and Current LimitRemote Monitoring of Output Voltage and Current Configuration RS232 & RS485 Remote ControlRear Panel RS232/RS485 Connector 6 RS232/RS485 port in Local modeFront panel in Remote mode MD Mode enable Serial communication mode MD Mode DescriptionMD Mode SRQ MD Mode SRQ RetransmissionSingle power supply Connecting Power Supplies to RS232 or RS485 BUSCommunication Interface Protocol Command SET Description Error MessagesInitialization Control Commands ID Control CommandsOutput Control Commands Filter DVC?FILTER? OUT?General Global Output CommandsEnable MD Mode MD Mode Option Required Single Byte CommandsDisable SRQ retransmission MD Mode Option Required Enable SRQ retransmission MD Mode Option RequiredPrint Power On Time Addressed commands with response Read registersTest if MD Mode is Installed Addressed commands without response Acknowledge SRQ1010 None Disable retransmission of SRQs by sup Voltage programming range Status Control Commands STATUS, Error and SRQ RegistersStatus Registers Conditional RegistersFold BITService Request Enable and Event Registers Fault Enable RegisterFault Event Register Status Event Register Status Enable RegisterPower supply set-up Serial Communication Test SET-UPCommunication Test Isolated Analog Programming Option Specifications1 0-5V/0-10V Option PN IS510 PPM/CIsolated Programming & Monitoring Connector Setup and Operating Instructions Maintenance OUP Fuse Rating

5KW specifications

The TDK 5KW is a cutting-edge power supply solution designed to deliver high performance and efficiency in a compact form. This robust unit is engineered for various applications, including industrial automation, telecommunications, and renewable energy systems. With a focus on reliability and durability, the TDK 5KW is an excellent choice for users seeking a dependable power source.

One of the standout features of the TDK 5KW is its advanced power conversion technology. It utilizes a high-frequency switching technique that allows for superior efficiency, minimizing energy loss and reducing heat generation. By operating at high efficiency levels, the TDK 5KW helps lower operational costs while contributing to a greener environment.

The power supply is equipped with a wide input voltage range, making it suitable for global applications. It can accept input voltages from 90 to 264 VAC, ensuring versatility and compatibility with various electrical systems. This feature also enhances its usability in different geographic regions without the need for additional transformers or converters.

Another significant characteristic of the TDK 5KW is its modular design, which allows for easy integration into existing systems. The power supply features a compact footprint, making it ideal for installations where space is at a premium. Moreover, its robust construction ensures that it can withstand harsh operating conditions, including extreme temperatures and vibrations.

Reliability is further enhanced through built-in protection features, including overvoltage, overcurrent, and short-circuit protection. These safety mechanisms not only safeguard the power supply itself but also protect the connected equipment from damage, making it a trustworthy choice for critical applications.

The TDK 5KW also supports various communication protocols, enabling seamless integration into modern automation systems. This feature allows for real-time monitoring and control, providing users with essential data to optimize performance and troubleshoot issues efficiently.

In summary, the TDK 5KW is a powerful, efficient, and reliable power supply solution that caters to a broad range of applications. Its advanced technologies, modular design, and robust safety features make it an essential component for anyone looking to enhance their electrical systems with a high-quality power source.