Westinghouse MA7200 Plus quick start manual To set parameter Bn-18 =, Word About PID Control

Page 14

MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

To set parameter Bn-18 = 005.00

(Integral Time )

Keypad Steps

1 - Press the key

2 - Press the EDIT key

ENTER

3 - Press the key twice; then the key

RESET

4 - Press the RESET key ; then the

key 5 times

Resulting Display

Bn-18

PID I_ Time

Flashing

Bn-18 = 010.00 s

PID I_ Time

Flashing

Bn-18 = 000.00 s

PID I_ Time

Flashing

Bn-18 = 005.00 s

6 - Press the

EDIT

key to save.

ENTER

PID I_ Time

Entry Accepted

2 Seconds

7 - Press the

PRGM

key to return to the main display.

DRIVE

Flashing

Bn-18 = 005.00 s

PID I_ Time

Word About PID Control-

________________________________________________________________ 14

TECO – Westinghouse Motor Company

Image 14
Contents MA7200 Plus Inverter PID Quick Start Guide for Fan and Pump Applications Before Starting the InverterCheck Fan or Pump Motor Operation Apply Power to the DriveSet Drive to Run Mode Teco Westinghouse Motor Company Digital Input / Output terminal connections Analog Feedback terminal connections Select Start / Stop Method of Control Sn-04 Setting Minimum Speed in Pump Applications To set parameter Cn-19 = 050%Turn on PID control To set the parameter Sn-24 = Select Feedback Engineering Units P1-01 and Scaling P1-02Press Key Key 4 times Maximum value of Engineering Units To set parameter Bn-17 = To set parameter Bn-18 = Word About PID ControlTo set parameter Bn-01 = 30.0 s To set parameter Bn-02 =30.0 P1-02=0200 Set parameter P1-04 = Press Key Sleep wakeup Level Press the key twice then the key Key MA7200 Plus Block Diagram Testing The SystemTeco Westinghouse Motor Company Appendix a