Westinghouse MA7200 Plus quick start manual Turn on PID control

Page 9

MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

Step 8– Select PID control (Sn-64), and Feedback input (Sn – 24) [4 – 20 mA or 0 – 10 Vdc]

Before selecting the parameter(s), ensure the inverter is in the STOP mode.

To activate PID control parameter (Sn-64)must be set to =1.

The Feedback Input parameter (Sn –24)is set to = 1 (AIN, 4-20 mA), as factory default. To select (VIN, 0-10 Vdc), (Sn-24)must be set to 0. (See Figs. 3a, 3b and 3c for feedback connections)

To set the parameter(s), follow the navigation procedure as shown next.

(Turn on PID control)

1 - Press the key

2 - Press the key twice

3 - Press the key until display shows

4 - Press the key

5 - Press the key

6 - Press the key to .

7 - Press the key to return to the main display.

Flashing

0

Flashing

1

2 Seconds

Flashing

1

________________________________________________________________ 9

TECO – Westinghouse Motor Company

Image 9
Contents MA7200 Plus Inverter Before Starting the Inverter PID Quick Start Guide for Fan and Pump ApplicationsApply Power to the Drive Set Drive to Run ModeCheck Fan or Pump Motor Operation Teco Westinghouse Motor Company Digital Input / Output terminal connections Analog Feedback terminal connections Select Start / Stop Method of Control Sn-04 To set parameter Cn-19 = 050% Setting Minimum Speed in Pump ApplicationsTurn on PID control Select Feedback Engineering Units P1-01 and Scaling P1-02 To set the parameter Sn-24 =Press Key Key 4 times Maximum value of Engineering Units To set parameter Bn-17 = Word About PID Control To set parameter Bn-18 =To set parameter Bn-01 = 30.0 s To set parameter Bn-02 =30.0 P1-02=0200 Set parameter P1-04 = Press Key Sleep wakeup Level Press the key twice then the key Key Testing The System MA7200 Plus Block DiagramTeco Westinghouse Motor Company Appendix a