MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

Step 10 – Setting PID Parameters; Proportional Gain (Bn-17) and Integral Time (Bn-18)

After all external connections have been made and the protective covers have been replaced, power up the inverter but do not run at this point.

Parameters Bn-17 = 1.0 (Proportional Gain) and Bn-18 = 10.0s (Integral Time) are factory set to the values shown. However, a good starting point for these values is setting the Proportional Gain Bn-17 = 2.0 and the Integral Time Bn-18 = 5.0s. To change these parameters, follow the keypad navigation procedure below.

To set parameter Bn-17 = 02.0

 

 

 

 

 

 

(Proportional Gain )

 

 

 

 

Keypad Steps

 

Resulting Display

1 - Press the

 

PRGM

key

 

 

 

 

 

 

An – 01 -

 

DRIVE

 

 

 

 

 

 

Freq. Cmd. 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 - Press the

 

DSPL

key

 

 

 

 

 

Bn-01

 

 

 

 

 

 

Acc. Time 1

 

 

 

 

 

 

 

 

 

 

 

 

 

3 - Press the

 

 

 

key until the display shows

 

 

 

Bn-17

 

 

 

 

 

 

PID P_ Gain

 

 

 

 

 

 

 

 

 

 

 

 

 

4 - Press the

ENTER

key

 

 

 

Bn-17 = 01.00

 

 

EDIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PID P_ Gain

5 - Press the

 

 

 

key twice; then the

key

 

 

Bn-17 = 02.00

RESET

 

 

PID P_ Gain

 

 

 

 

 

 

 

 

 

 

 

 

 

6 - Press the

EDIT

 

key to save.

 

 

 

 

Entry Accepted

ENTER

 

 

 

 

 

 

 

 

Flashing

Flashing

2Seconds

Flashing

Next set Bn-18 = 005.00

Cn-19 = 050%

Freq Cmd Low Bound

________________________________________________________________ 13

TECO – Westinghouse Motor Company

Image 13
Contents MA7200 Plus Inverter Before Starting the Inverter PID Quick Start Guide for Fan and Pump ApplicationsSet Drive to Run Mode Apply Power to the DriveCheck Fan or Pump Motor Operation Teco Westinghouse Motor Company Digital Input / Output terminal connections Analog Feedback terminal connections Select Start / Stop Method of Control Sn-04 To set parameter Cn-19 = 050% Setting Minimum Speed in Pump ApplicationsTurn on PID control Select Feedback Engineering Units P1-01 and Scaling P1-02 To set the parameter Sn-24 =Press Key Key 4 times Maximum value of Engineering Units To set parameter Bn-17 = Word About PID Control To set parameter Bn-18 =To set parameter Bn-01 = 30.0 s To set parameter Bn-02 =30.0 P1-02=0200 Set parameter P1-04 = Press Key Sleep wakeup Level Press the key twice then the key Key Testing The System MA7200 Plus Block DiagramTeco Westinghouse Motor Company Appendix a