MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

Step 11 – Setting parameters acceleration (Bn-01) and deceleration (Bn-02) times

Acceleration and Deceleration times as well as the PID control [(P) Proportional Gain and/or the (I) Integral Time (see STEP 11) directly control the system dynamic response. The longer the acceleration and deceleration time, the slower the system response, and the shorter time, the faster the response. An excessive amount of time can result in sluggish system performance while too short of a time may result in system instability.

The starting values suggested by this guide normally result in good system performance for the majority of fan and pump applications. If the values need to be adjusted, caution should be exercised, and the changes should be in small increments to avoid system instability.

Parameters Bn-01(Acceleration) and Bn-02(Deceleration) are both set at the factory for 10.0 seconds. For fan and pump applications, the recommended starting values are 30 seconds. To change these parameters, follow the keypad navigation procedure as shown next.

To set parameter Bn-01 = 30.0 s

(Acceleration Time )

Keypad Steps

 

Resulting Display

1 - Press the

PRGM

key

 

 

 

An – 01 -

DRIVE

 

 

 

Freq. Cmd. 1

 

 

 

 

 

 

 

 

 

 

 

2 - Press the

DSPL

key

 

 

 

Bn-01

 

 

 

Acc. Time 1

 

 

 

 

 

 

Flashing

3 - Press the

4 - Press the

5 - Press the

EDIT

ENTER

RESET

EDIT

ENTER

key

 

 

 

 

 

 

Bn-01 = 0010.0

 

 

 

 

 

 

Acc. Time 1

 

 

 

 

 

 

 

key 3 times; then the

Key twice

 

 

Bn-01 = 0030.0

 

 

Acc. Time 1

 

 

 

 

 

 

 

key to save.

 

 

 

 

 

Entry Accepted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Next set Bn-02 = 0030.0

 

 

 

Bn-01 = 0030.0

 

 

 

Acc. Time 1

 

 

 

 

 

 

 

Flashing

2Seconds

Flashing

________________________________________________________________ 15

TECO – Westinghouse Motor Company

Image 15
Contents MA7200 Plus Inverter Before Starting the Inverter PID Quick Start Guide for Fan and Pump ApplicationsApply Power to the Drive Set Drive to Run ModeCheck Fan or Pump Motor Operation Teco Westinghouse Motor Company Digital Input / Output terminal connections Analog Feedback terminal connections Select Start / Stop Method of Control Sn-04 To set parameter Cn-19 = 050% Setting Minimum Speed in Pump ApplicationsTurn on PID control Select Feedback Engineering Units P1-01 and Scaling P1-02 To set the parameter Sn-24 =Press Key Key 4 times Maximum value of Engineering Units To set parameter Bn-17 = Word About PID Control To set parameter Bn-18 =To set parameter Bn-01 = 30.0 s To set parameter Bn-02 =30.0 P1-02=0200 Set parameter P1-04 = Press Key Sleep wakeup Level Press the key twice then the key Key Testing The System MA7200 Plus Block DiagramTeco Westinghouse Motor Company Appendix a