Westinghouse MA7200 Plus quick start manual Set parameter P1-04 =

Page 18

MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

Set parameter P1-04 = 1

 

(Turn on sleep function)

Resulting Display

Keypad Steps

 

1 - Press the

 

PRGM

key

 

 

An – 01 -

 

DRIVE

 

 

Freq. Cmd. 1

 

 

 

 

 

 

 

 

 

2 - Press the

 

DSPL

key 4 times

 

P1-04

 

 

PID Sleep Function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

3 - Press the

EDIT

 

key

 

 

 

 

P1-04 = 0

ENTER

 

 

PID Sleep Invalid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

4 - Press the

 

 

 

key

 

 

 

P1-04 = 1

 

 

 

 

PID Sleep Valid

 

 

 

 

 

 

 

 

 

5 - Press the

EDIT

ENTER

key to save.

 

 

 

Entry Accepted

 

 

 

 

 

 

 

 

 

 

 

 

 

Next set P2-01 = 60%

 

 

P1-04 = 1

 

 

PID Sleep Valid

 

 

 

 

 

 

2Seconds

Flashing

________________________________________________________________ 18

TECO – Westinghouse Motor Company

Image 18
Contents MA7200 Plus Inverter PID Quick Start Guide for Fan and Pump Applications Before Starting the InverterApply Power to the Drive Set Drive to Run ModeCheck Fan or Pump Motor Operation Teco Westinghouse Motor Company Digital Input / Output terminal connections Analog Feedback terminal connections Select Start / Stop Method of Control Sn-04 Setting Minimum Speed in Pump Applications To set parameter Cn-19 = 050%Turn on PID control To set the parameter Sn-24 = Select Feedback Engineering Units P1-01 and Scaling P1-02Press Key Key 4 times Maximum value of Engineering Units To set parameter Bn-17 = To set parameter Bn-18 = Word About PID ControlTo set parameter Bn-01 = 30.0 s To set parameter Bn-02 =30.0 P1-02=0200 Set parameter P1-04 = Press Key Sleep wakeup Level Press the key twice then the key Key MA7200 Plus Block Diagram Testing The SystemTeco Westinghouse Motor Company Appendix a