MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

To set parameter Bn-02 =30.0

(deceleration Time )

Keypad Steps

1 - Press the key

2 - Press the EDIT key

ENTER

3 - Press the

key 3 times; then the

key twice

Resulting Display

Bn-02

Dec. Time 1

Flashing

Bn-02 = 0010.0 s

Dec. Time 1

Flashing

Bn-02 = 0030.0 s

 

RESET

 

4 - Press the

EDIT

key to save.

ENTER

Dec. Time 1

Entry Accepted

2 Seconds

5 - Press the

PRGM

key to return to the main display.

DRIVE

Flashing

Bn-02 = 0030.0 s

Dec. Time 1

Step 12 – Setting PID Sleep Function parameters (P1-04), (P2-01), (P2-02), (P2-03) and (P2-04).

(NOTE: In the case of a Fan application skip this step and go to Step13)

The PID Sleep function is turned on by parameter (P1-04)when set to (=1). This allows the system to turn off the PID and thus the inverter output so that the pump does not run when the system level (PSI) is above the set-point. This sleep start level is set by parameter (P2- 01) in a range from 0 – 100% of the maximum inverter output. When the system level drops below a value (the units are selected by Step 8) set by parameter (P2-03),the sleep wakeup level, the output of the inverter will turn on. Parameters (P2-02)and (P2-04)provide delay times in seconds for sleep start level and sleep wakeup level respectively. Fig. 4 will serve to illustrate this.

________________________________________________________________ 16

TECO – Westinghouse Motor Company

Image 16
Contents MA7200 Plus Inverter PID Quick Start Guide for Fan and Pump Applications Before Starting the InverterSet Drive to Run Mode Apply Power to the DriveCheck Fan or Pump Motor Operation Teco Westinghouse Motor Company Digital Input / Output terminal connections Analog Feedback terminal connections Select Start / Stop Method of Control Sn-04 Setting Minimum Speed in Pump Applications To set parameter Cn-19 = 050%Turn on PID control To set the parameter Sn-24 = Select Feedback Engineering Units P1-01 and Scaling P1-02Press Key Key 4 times Maximum value of Engineering Units To set parameter Bn-17 = To set parameter Bn-18 = Word About PID ControlTo set parameter Bn-01 = 30.0 s To set parameter Bn-02 =30.0 P1-02=0200 Set parameter P1-04 = Press Key Sleep wakeup Level Press the key twice then the key Key MA7200 Plus Block Diagram Testing The SystemTeco Westinghouse Motor Company Appendix a