MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________
Step 7 – Setting Minimum Speed in Pump Applications
(NOTE: In the case of a fan application skip this step and go to Step 8)
•In the case of pump applications it is normally required to limit the minimum speed that the pump will operate regardless of the input speed command. The pump minimum speed is usually specified either by the pump manufacturer or the application. Once this value has been established, the minimum output frequency of the inverter and thus the minimum motor (pump) speed can be set by parameter
•The following is an example of setting the minimum motor (pump) speed to 1800 RPM, which is 50% of the maximum pump speed, 3600 RPM.
To set parameter Cn-19 = 050%
(Minimum pump speed )
Keypad Steps | Resulting Display | ||||||||||
1 - Press the |
| PRGM | key |
|
|
|
|
| An – 01 - | ||
| DRIVE |
|
|
|
|
| Freq. Cmd. 1 | ||||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| |
2 - Press the |
| DSPL | key 3 times |
|
|
|
| ||||
|
|
|
|
| Input Voltage | ||||||
|
|
|
|
|
|
|
|
|
|
| |
3 - Press the |
|
| key until the display shows |
|
|
| |||||
|
|
|
|
| Freq Cmd Low Bound | ||||||
|
|
|
|
|
|
|
|
|
|
| |
4 - Press the |
|
|
| key |
|
|
| Flashing | |||
ENTER |
|
|
| ||||||||
| EDIT |
|
|
|
|
|
|
|
|
Freq Cmd Low Bound
Flashing
5 - Press the
6 - Press the
RESET
EDIT
ENTER
key twice; then the | key 5 times |
|
| ||
|
| Freq Cmd Low Bound | |||
|
|
|
|
| |
key to save. |
|
|
|
| Entry Accepted |
|
|
|
2Seconds
Flashing
| PRGM | Freq Cmd Low Bound | |
7 - Press the | key to return to the main display. | ||
DRIVE |
________________________________________________________________ 8