Westinghouse MA7200 Plus quick start manual Select Start / Stop Method of Control Sn-04

Page 7

MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

Step 6 – Select Start / Stop Method of Control (Sn-04)

Before selecting this parameter, ensure the inverter is in the STOP mode.

The set-pointis selected by the keypad (Sn-05=0), and the start / stop method can be from the keypad or external contact (see Fig. 2a). NOTE: The set-point can also be set from an external source but commonly it is set from the keypad.

The parameter (Sn – 04) is set to = 0 (keypad), as factory default. If external contact is desired, follow the navigation procedure below to set (Sn-04 = 1).

________________________________________________________________ 7

TECO – Westinghouse Motor Company

Image 7
Contents MA7200 Plus Inverter Before Starting the Inverter PID Quick Start Guide for Fan and Pump ApplicationsSet Drive to Run Mode Apply Power to the DriveCheck Fan or Pump Motor Operation Teco Westinghouse Motor Company Digital Input / Output terminal connections Analog Feedback terminal connections Select Start / Stop Method of Control Sn-04 To set parameter Cn-19 = 050% Setting Minimum Speed in Pump ApplicationsTurn on PID control Select Feedback Engineering Units P1-01 and Scaling P1-02 To set the parameter Sn-24 =Press Key Key 4 times Maximum value of Engineering Units To set parameter Bn-17 = Word About PID Control To set parameter Bn-18 =To set parameter Bn-01 = 30.0 s To set parameter Bn-02 =30.0 P1-02=0200 Set parameter P1-04 = Press Key Sleep wakeup Level Press the key twice then the key Key Testing The System MA7200 Plus Block DiagramTeco Westinghouse Motor Company Appendix a