600 Series Hazardous Location Installation Requirements

1.WARNING! Do not disconnect while circuit is live, unless area is known to be non-hazardous.

2.WARNING! Install only in accordance with Local & National Codes of .Authorities Having Jurisdiction.

3.Class I, Div 2 installation requires that all devices connected to this product must be approved for the area in which it is installed.

4.Only hazardous location approved wiring with temperature ratings greater than 80 C permitted for Class I, Div 2 installations operating at temperatures up to 60 C ambient.

Personnel Qualification Requirements

Only qualified personnel should be allowed to install and work on this equipment. Qualified personnel are defined as individuals who are familiar with the installation, assembly, startup, and operation of this product and who possess the relevant qualifications for their work e.g.:

Training in or authorization for connecting up, grounding, or labeling circuits and devices or systems in accordance with current standards in safety technology.

Training in or authorization for the maintenance and use of suitable safety equipment in accordance with current standards in safety technology.

First aid qualification.

DIN-Rail Mounting

Install the unit on a standard 35mm Din-Rail. When installing the unit in an enclosed cabinet, recess it to allow at least 3” of clearance for fi ber optic cable bend radius, and 2 inches for TX cables and power connections. Please note the 600 Series units must be installed in the vertical orientation for cooling purposes. In this orientation, the power connector is at the top of the unit, and the signal cables exit from the bottom of the unit.

19” Rack Mounting

19” Rack mount kits are available. Please consult with you r local sales representative for price & availability. Order part number: 900-RM

12/15/05

7

Image 7
Contents Hardware Installation Guide Industrial Ethernet Switch Installation Guide 12/15/05 Laser Safety 604/608MFXE Version Only Electrical SafetyKey Features Series Industrial Ethernet SwitchInstallation Package ContentsUnpacking Rack Mounting Series Hazardous Location Installation RequirementsPersonnel Qualification Requirements DIN-Rail MountingApplying Power Ring Manager Connecting the Standard RingSimultaneous Standby and Redundancy Manager Operation Connecting Multiple Rings 608MFX OnlyPort Assignment in the Standby Mode Cannot be used as Ring Couplers608MFX Replacing the Standby Master during operationDisplays and Operating Controls LED’s Fault red LEDPort LED’s Display Mode Meaning State = Port StatusSelect/Set Button Ieee 802.1P, QOS Two-Pin Dip Switch SettingAging Time Ieee 802.1Q, VlanStandby-Sync Port 608MFX Only Serial InterfaceHyperterminal Serial CableFCC Statement Troubleshooting12/15/05 Contact/Support Information Key Specifications Emissions and Safety ApprovalsWarranty Ordering Information DescriptionTron Limited Warranty 12/15/05