4.4.2 System
Click on "System" in the menu.
This menu enables the customisation of the information on the UPS properties pages.
◗UPS Contact: This text field is limited to 49 characters. Enter the name of the person responsible for UPS administration at IT network level and/or electrical maintenance. This field does not appear on any other Web page. By default, its value is "Computer Room Manager".
◗UPS Location: Enter a description (limited to 49 characters) of the location of the UPS in your installation (e.g. Computer room
◗Default Language: Enables initialisation of the browser language at card connection.
Choice of one of the available languages: English, French, German, Spanish, Italian changes the language of the html interface pages (reboot the browser after modification).
◗History log interval: [from 5 to 99999 sec., 60 by default]. Measurement save period.
◗Environment log interval: [from 60 to 99999 sec., 300 by default]. Temperature and humidity measurement save
period. Reset Communication button: performs a remote reboot of the card without modifying the configuration. This action is compulsory for consideration of any changes made on the "Network Settings" page. Security of this operation is ensured by requesting Login and Password.
ENERGIZE YOUR ENTERPRISE |
|
|
Network Management Card – User Manual | 34003991EN/DA | Page 50/120 |