7.2.2 RS485 link configuration and connection

7.2.2.1 RS485 connection

La liaison EIA RS485, en 2 fils ou en 4 fils, doit être polarisée en un point unique de la ligne et adaptée aux deux extrémités de cette ligne pour un fonctionnement correct A TRADUIRE

Normally, the master of the network sets the polarity of the line. The INMC card is a slave equipment and don’t have polarisation resistor.

The two ends of the line must be terminated. Allow for 1 or 2 terminators to avoid mismatching the line when any equipment at the end of the line is disconnected.

The next figure gives the detail of the RS485 connector and the internals drivers:

Pin number

Function

1

R- : Receiver - (input)

2

R+ : Receiver + (input)

3

T- : Transmitter - (output)

4

T+ : Transmitter + (output)

5

0 V

Important notes:

Use twisted pair cable (cable specification 0.3mm2 and capacitance 42pF/m)

The transmission range will increase if a cable with lower capacitance and larger diameter is used. Use shielded cable in heavy industrial environments.

ENERGIZE YOUR ENTERPRISE

 

 

Network Management Card – User Manual

34003991EN/DA

Page 80/120

Image 80
Contents Network Management Card 66102 Energize Your EnterpriseContents Industrial Network Management Card Inmc Option Configuration VIA RS232Server Protection Jbus Table AppendicesMGE MIB GlossaryMGE Office Protection Systems Network Solution General PresentationConnecting the UPS to the Ethernet network Protection of the computers/serversSupervision of the UPSs over the network ConnectionHow to connect UPS / agent / network Setting up the protectionPresentation of the Network Management Card NMC Compatibility with UPSsEnvironment Sensor option Direct sending of E-mailSending text messages SMS Technical data Hardware characteristicsConfiguration EMC CompatibilityAdministration NetworkEnvironment sensor List of ports usedMIB Management Information Base Mgeups Default parametersBOOTP/DHCP Indications InstallationUnpacking and check on contents ACT Installation in the UPSLED Sensor installation option MGE UPS Systems Network Management Card ConfigurationConfigure IP parameters Your network is equipped with a Dhcp server Test after configuration Your network is not equipped with a Dhcp serverSupervision and administration by browser Optimising the performance of your browserUPS UPS propertiesUPS zone general information on the UPS 23/120 24/120 25/120 26/120 UPS status zone Essential information Viewing the modules 29/120 Viewing the alarms Alarm table for modular UPS Viewing the About your UPS window On-line help UPS control 35/120 36/120 UPS weekly schedule programming Shutdown parameters For the main outlet Master by default Measurements Event log System log Notification Email Notification44/120 Mail Message Settings 46/120 Configuration Network settings 49/120 System 51/120 Notified Applications 53/120 Central shutdown configuration Access control 55/120TLS Date and time 58/120 Firmware upload Characteristics Environment Sensor optionEnvironment Status Environment Settings Display in the list of current alarms 4 Log Shutdown criteria managed by the Network Management Card Server protectionSet-up of the shutdown parameters Utility failure Start of the shutdown sequence Shutdown when backup time is less than Shutdown durationLoad shedding or sequential shutdown Controlled outletsProtection of a server connected to a controlled outlet Different server and UPS shutdown sequences Sequential startup70/120 Shutdown Duration SettingsShutdown management with 2 NMC boards Configuration via RS232 Choice 1 Read Network settings Choice 1 Restart / ResetChoice 2 Network Configuration Choice 2 Modify Network settings Choice 3 Set Ethernet speedChoice 3 Lost password / Set Login Password to Default Choice 4 Return to Default Configuration Overview Functions Industrial Network Management Card Inmc optionPresentation Technical characteristics JBUS/MODBUSInstallation 1 RS232 link configuration and connection2 RS485 link configuration and connection 2.1 RS485 connection81/120 2.2 RS485 link configuration for 2 wires connexion 83/120 2.3 RS485 link configuration for 4 wires connexion 85/120 Configuration of the JBUS/MODBUS communication parameters Choice 1 Display Jbus settings Choice 2 Modify Jbus settingsChoice 5 Return to Jbus Default Configuration Choice 3 Display Jbus diagnosticsChoice 4 Reset Jbus diagnostics Choice 6 Display Jbus frames Additional Web pages Status table Jbus tableData for Pulsar 700 / 1000 Measurements table Data for Pulsar M 2200 94/120 Data for Pulsar MX 4000 / 5000 96/120 Data for Pulsar MX frame 15 Modular fault table 99/120 100/120 101/120 Sensor data 5.1 Status table103/120 Read of the personalization table Other data Appendices Tables of alarms and eventsTable of alarms UPS OK Battery fault Battery OK Imminent UPS shutoff Table of UPS events 110/120 Table of system alarms Snmp objects MGE MIB113/120 1yes 2no 1,4,1 Table des Traps MIB Trap116/120 Network Management Proxy GlossaryMIB Management Information Base 118/120 NMS Network Management Station Snmp NSM Network Shutdown ModuleSnmp Simple Network Management Protocol Smtp Simple Mail Transfer Protocol120/120