Utility failure | Start shutdown | Start shutdown main | Utility restore |
output 1 | output | ||
Utility |
|
|
|
|
| Shutdown duration |
|
Main output |
|
|
|
|
| Battery capacity |
|
|
| under: |
|
NSM 1 on main |
|
|
|
output |
|
|
|
| Shutdown |
| |
| duration output 1 |
| |
Output 1 |
|
|
|
|
| Battery capacity |
|
| under: (output 1) |
| |
NSM 2 on output 1 |
|
|
|
5.2.3Case of power restoration before the end of the "shutdown duration" counter
If power is restored before the end of the Shutdown Duration, the UPS is shut off after the Shutdown Duration for a
time equal to the forced reboot delay (10 seconds)
|
|
| Start shutdown | Start shutdown main |
| ||
| Utility failure | output | Utility restore | ||||
| output 1 | ||||||
|
|
|
|
|
|
| |
Utility |
|
|
|
|
|
|
|
|
|
|
|
| Shutdown | Forced Reboot | |
|
|
|
|
| duration |
Main output
Battery capacity under
:
NSM 1 on main output
Shutdown duration output1
Output 1
Batterycapacity
under: (output 1)
NSM 2 on output 1
ENERGIZE YOUR ENTERPRISE
Network Management Card – User Manual | 34003991EN/DA | Page 70/120 |