Maretron Symptom, Troubleshooting Procedure, FPM100 User’s Manual, Page, Revision

Page 18
5 Troubleshooting

FPM100 User’s Manual

5 Troubleshooting

If you notice unexpected operation of the Maretron FPM100, follow the troubleshooting procedures in this section to remedy simple problems.

Symptom

No Pressure data visible on NMEA 2000® network.

Inaccurate pressure output

No Tank Level data visible on NMEA 2000® network.

Inaccurate tank level output

Zero pressure readings when pressurized

Troubleshooting Procedure

1.Ensure that the FPM100 is properly connected to the NMEA 2000® network.

2.Ensure that pressure transducers are properly connected to the FPM100.

3.Ensure that each channel that you wish to monitor is configured as “Pressure/Vacuum”and that instance numbers are configured correctly.

4.Ensure that the FPM100 has the appropriate NMEA 2000 PGNs enabled.

1.Ensure that the “Pressure at 4mA” and “Pressure at 20mA” configuration items are set to appropriate values for the pressure transducer.

2.Check that the vent tube from the pressure transducer (only present on some transducers) is not kinked or blocked.

3.Remove the pressure transducer from the tank opening and ensure that the pressure port on the transducer is not clogged.

1.If operating in the NMEA 2000® Mode, check the connection to the NMEA 2000® interface (see Section 2.5.1) and tighten if necessary.

2.Ensure that power is supplied to the NMEA 2000® network. Proper network power can be checked by measuring the voltage at an open tee between NET-S and NET-C. The voltage should be between 9 and 16 volts.

3.Ensure that both trunk line terminators are in place. Proper network termination can be checked by removing network power and measuring the resistance at an open tee between NET-L and NET-H signals. The resistance should read approximately 60 ohms (two 120 ohm terminators in parallel equals 60 ohms).

1.If operating with a rectangular tank, ensure that the tank depth is programmed properly (see Section Error! Reference source not found.).

2.If using custom calibration, re-calibrate the FPM100 (see Section 3.3.5.2).

3.Check that the vent tube from the pressure transducer is not kinked or blocked.

4.Remove the pressure transducer from the tank opening and ensure that the pressure port on the transducer is not clogged.

1.Ensure that the “Pressure at 4mA” and “Pressure at 20mA” configuration items are set to appropriate values for the pressure transducer.

2.Check the cable connection to the pressure transducer to see whether a wire has become loose, or the cable has been cut.

Page 14

Revision 1.3

Image 18
Contents Revision Copyright 2012 Maretron, LLP All Rights Reserved RevisionPage Maretron, LLP 9014 N. 23rd Ave #10 Phoenix, AZPage Revision HistoryFPM100 User’s Manual RevisionTable of Contents Table of Figures Table of Appendices1.1 Introduction 1.3 Features1 General 1.2 Firmware Revision1.4 FPM100 Accessories 1.5 Quick Install1.6 Theory of Operation 1.6.2 Accuracy of Tank Level Measurement2 Installation 2.1 Unpacking the BoxFigure 1 - Graph of Transducer Accuracy vs. Tank Depth 2.4 Mounting the Pressure Transducer 2.2 Choosing a Mounting Location2.3 Mounting the FPM100 2.4.1 Pressure Measurement Applications2.4.2 Tank Level Measurement Applications Figure 4 - Fluid Level Measurement with Pressure Transducer2.5.1 NMEA 2000 Connection Tank Fitting Ball Valve Pressure TransducerFigure 7 - Pressure Transducer Connection Diagram Figure 6 - NMEA 2000 Connector Face ViewsPin # Signal Name 2.5.2 Pressure Transducer Connections3.2 Configuring a Channel in Pressure/Vacuum Mode 3 Configuring the FPM1003.1 Configuring Channel Mode 3.2.1 Configuring Instance3.2.3 Configuring Pressure at 4mA 3.3 Configuring a Channel in Tank Mode3.2.2 Configuring Label 3.2.4 Configuring Pressure at 20mA3.3.4 Configuring Tank Capacity 3.3.2 Configuring Pressure at 4mA3.3.3 Configuring Pressure at 20mA 3.3.5 Tank Levels Calibration3.3.5.1.3 Fluid Density 3.3.6 Configuring Tank NumberFigure 8 - Empty Tank Depth and Full Tank Depth Parameters 3.3.5.2 Custom Calibration4 Maintenance 3.3.7 Configuring Tank Type3.3.8 Configuring Data Damping Period 5 Troubleshooting SymptomTroubleshooting Procedure Specifications Tank Level Mode 6 Technical SpecificationsFigure 9 - Troubleshooting Guide Specifications Pressure/Vacuum ModeMechanical 7 Technical SupportElectrical Environmental8 Installation Template Figure 10 - Mounting Surface Template9 Maretron 2 Year Limited Warranty Warranty Return ProcedureAppendix A - NMEA 2000 Interfacing Appendix A - NMEA 2000 InterfacingFPM100 NMEA 2000 Periodic Data Transmitted PGNs Page A1