Piping
5.0PIPING
5.1European Union Fluorinated Greenhouse Gas Requirements
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys- tems in the European Community market and operating with fluorinated greenhouse gases
The
Refer to the full regulation for additional details.
5.2System Connection Configuration
If possible, connect the Liebert XDH’s upper and lower refrigeration circuits to Liebert XDPs or Lie- bert XDCs in an interlaced configuration (see Figure 11). Interlacing the connection piping will keep one of the Liebert XDH’s circuits operating should one of the Liebert XDP or Liebert XDC units fail.
However, in a system with just one Liebert XDP or Liebert XDC, connect Liebert XDH modules in a
Figure 11 Typical Liebert XDH piping—interlaced connections
Liebert XDP / Liebert XDC #1
Liebert XDP / Liebert XDC #2
Liebert | Liebert | Liebert | Liebert | ||||||||
| XDH | XDH | XDH | XDH | |||||||
Unit 1 | Unit 2 | Unit 3 | Unit 4 | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Liebert | Liebert | Liebert | Liebert |
XDH | XDH | XDH | XDH |
Unit 5 | Unit 6 | Unit 7 | Unit 8 |
|
|
|
|
Supply
Liebert XDP/
Liebert XDC #1
Return
Liebert XDP/
Liebert XDC #1
Supply
Liebert XDP/
Liebert XDC #2
Return
Liebert XDP/
Liebert XDC #2
Drawing is not to scale. Line sizes do NOT indicate piping sizes.
Equipment racks not shown for clarity.
12