Piping
5.3Connection Methods and Points
Refer to site specific drawings for general locations of the piping connections. For Liebert XDH con- nection locations, refer also to Figure 16.
The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigeration systems. Observe all standard practices during installation and startup to prevent damage and contamination.
Supply piping connection is 1/2" OD copper pipe, and return piping connection is 7/8" OD copper. Both supply and return fittings may be supplied with optional
The Liebert XDH has supply and return piping access on the top of each module.
Figure 15 Hard pipe connection diagram
Return Main (seen from end )
Acceptable Arc
Supply Main (seen from end )
1/2” Refrigerant
Field- Installed
Recommended Arc
7/8”
| Supply |
|
|
| |
| to Cooling | |
Refer to Table 2 for details. | Module |
Rear of
Liebert XDH
Copper Tubing Total length of each line from Liebert XDH to Main; not to exceed 72" (1829mm)
Return from Cooling Module
Top of
Liebert XDH
15