Liebert XDH manual Product/System Description, Checking and Unpacking

Page 8

General product information

3.0GENERAL PRODUCT INFORMATION

3.1Product/System Description

The Liebert XDH is designed for placement within a row of computer cabinets in the data center in a hot-aisle-cold-aisle arrangement to maximize the Liebert XDH’s cooling: The unit takes in hot air through the rear from the hot aisle, cools the air by air-to-fluid heat exchangers and discharges the air through the front of the unit into the cold aisle.

Chilled R-134a refrigerant is provided to the Liebert XDH by a Liebert XD Pumping unit (Liebert XDP) or by a Liebert XD Chiller (Liebert XDC). The Liebert XDH may be installed in a Liebert XD piping system that includes other Liebert XD cooling modules, such as the Liebert XDO, Liebert XDV or Liebert XD CoolFrame.

Replaceable front panels on the Liebert XDH may be customized to match the appearance of various computer manufacturer’s equipment, allowing the Liebert XDH to blend in with adjacent server equipment and enclosures. Air diffusers are available to direct cooling air for more efficient cooling, depending on the Liebert XDH’s positioning in a row or at the end of a row.

The Liebert XDH is not expected to produce any condensation because of its location, usually in the data center. A condensate pan is provided as a precaution. It does not have a drain fitting or other means of being emptied.

A Liebert Liqui-tect moisture detection device and a contact-closure output are available as an option. These options detect condensation in the Liebert XDH’s catch pan and connect to a monitoring or alarm system. A front panel alarm and indicator alert the user to condensation inside the unit.

The complete cooling system consists of Liebert XDH modules, Liebert XDP or Liebert XDC pumped refrigerant distribution units, power and signal cabling and interconnecting piping, see Figure 3 below.

Figure 3 Liebert XDH hydraulic schematic

Liebert XDC

or

Liebert XDP

Liebert XDC

or

Liebert XDP

Pumped

Refrigerant

Pumped

Refrigerant

XD Cooling

Module *

XD Cooling

Module *

XD Cooling

Module *

XD Cooling

Module *

Supply Lines

(2 per unit)

Return Lines

(2 per unit)

*XDCF, XDH, XDO or XDV

3.2Checking and Unpacking

When the Liebert XDH is delivered, inspect all items for either visible or concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representative. If you later find any concealed damage, report it to the shipping company and your local Liebert representative.

Check to be sure all required assemblies and parts have been received.

The Liebert XDH is shipped in protective packaging and secured to a pallet (see Figure 5). Do not remove these protective items from the Liebert XDH before it is at the installation location. When unpacking and handling the Liebert XDH, exercise extra care to prevent damage.

4

Image 8
Contents Liebert XDH General Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Operation MaintenanceSpecifications Example XDH32BK Liebert XDH component locationsPre-Installation Checks Product DescriptionReferences Parts Included With the Liebert XDHInstallation Considerations Room PreparationProduct/System Description Checking and UnpackingEquipment Inspection Recyclable PackagingUnit Handling Unpacking the UnitTaking the Unit off the Pallet Prepare ramp to remove the Liebert XDH from shipping palletAttaching ramp, removing the Liebert XDH from pallet Determining Placement in the Conditioned Space Installing the Liebert XDH Within the Enclosure RowAirflow Direction XDHInstall Air Diffusers for Best Airflow Direction Change airflow directionSystem Connection Configuration European Union Fluorinated Greenhouse Gas RequirementsTypical Liebert XDH piping-non-interlaced connection Indirect system configuration-hydraulic system schematic Hard pipe connection diagram Connection Methods and PointsRear of Liebert XDH Venting the Holding Charge and Connecting to MainsPiping Considerations-Hard-Piped Connections Connecting Methods-One-Shot Connections Connection Methods for Hard PipeRecommended Piping Size Brazing PreparationsDegree Connection Tools Required Connecting Liebert XD Flex Pipes to Liebert XDH ModulesHeader System Liebert XD prefabricated piping assembly Tools Required Return Line Service Valve Supply InsulationConnecting High Voltage Wiring ElectricalConnecting Low Voltage Wiring-Optional Condensate wiring entry pointsChecklist for Proper Installation Charging with Refrigerant and Starting the Liebert XD SystemStart the Liebert XDH OperationInternal Access Fluorinated Greenhouse Gas RequirementsRemove Fan Tray Remove fan traySpecifications Liebert XD Flex Pipe assemblies, supply and return Page Ne t