Liebert GXTTM user manual Starting the UPS, Powering Down the UPS

Page 11

STARTING THE UPS

1.Ensure the load equipment is turned off, and all loads are properly connected to the UPS output.

2.Check that the mains wall isolator is ON. Turn On (Close) the Battery circuit

breaker, the Input and Output circuit breakers in that order. The UPS will now automatically start up and default to BYPASS mode once the UPS is connected to an active AC mains supply and the Battery and Input circuit breakers are closed. At the end of the startup sequence the BYPASS LED should be lit.

3.TO PROTECT YOUR LOAD YOU MUST NOW PRESS THE UPS ON/ALARM /BATTERY TEST BUTTON TO GO TO UPS MODE

4.Press the UPS ON/ALARM /BATTERY TEST button for at least one half second until you hear the audible alarm give a “Beep” to signal acceptance of the command. After a delay of about 10 seconds, the BYPASS LED will extinguish and the UPS ON LED should light. The UPS will then initiate a self-test and a battery test. When these tests are complete, the UPS is ready for NORMAL UPS operation. Connected load equipment may now be started.

POWERING DOWN THE UPS

1.Check to ensure that all connected load equipment is shutdown. Press the OUTPUT OFF/ BYPASS button until a “Beep” is heard. Release the button and then immediately press for at least one second. The UPS ON LED will extinguish and the BYPASS LED will light for a short period then extinguish.

When the AC input LED and the bottom LED of the BATTERY/LOAD array are lit and the UPS ON and BYPASS LED’s extinguish, the output is powered down.

2.If necessary to isolate the UPS, set the input, output and battery breakers on the rear of the UPS to OFF position. Finally for complete isolation turn OFF the wall mounted mains isolator.

9

Image 11
Contents UPStation GXT Important Safety Instructions Glossary of Symbols Major Components Introduction and System DescriptionInverter RECTIFIER/POWER Factor Correction PFC CircuitBattery Charger BatteryControls and Indicators Output OFF/BYPASS Button UPS ON/Alarm Silence/Manual Battery Test ButtonGXT 6 & 10 kVA Operating Modes Normal Mode OPERATION- UPS modeBattery Mode Operation Bypass Mode Operation Starting the UPS Powering Down the UPSOperation in Battery Mode Troubleshooting Problem Cause Solution Audible Alarm ConditionsTroubleshooting Guide Troubleshooting Guide UPS Intellislot Communications UPS MonitoringUPS Intelligent Communications Maintenance Location Installation InstructionsInstallation Considerations InspectionAirflow Dissipation Output Input Current Rating Electrical Installation ConsiderationsElectrical Connections Output connections GXT 6000/10000-X models only Connecting the UPS Power cablesConnection of optional remote battery cabinets Stabilisers/Levelling Feet UPS Remote shutdown option PIN Assignment Collector to EmitterSerial Communications Ferrite Bead InstallationCommissioning the UPS Output Voltage Selector SwitchesBattery Run Times Specifications GXT6000T-230X GXT10000T-230X Life Support Applications Limited WarrantyTechnical Support UPStation GXT