Liebert GXTTM user manual Troubleshooting Guide

Page 15

TROUBLESHOOTING GUIDE

PROBLEM

CAUSE

SOLUTION

Fault and Bypass

UPS overloaded or load

Check load level display and

indicators and all load

equipment is faulty

remove non-essential loads.

level LED's are

 

Recalculate load VA and

illuminated

 

reduce number of loads

 

 

connected to UPS. Check load

 

 

equipment for faults.

Fault and Bypass

UPS internal fan has a

Press Alarm silence button.

indicators and

problem or UPS

Once the temperature is

diagnostic LED A are

shutdown due to

reduced, the UPS will restart

illuminated

temperature condition.

and transfer the connected

 

Load is on bypass

equipment to inverter power

 

power.

automatically.

Fault and Bypass

UPS internal DC bus

UPS requires service. Contact

indicators and

over voltage

your dealer or technical

diagnostic LED B are

 

support.

illuminated

 

 

Fault and Bypass

UPS PFC fault.

UPS requires service. Contact

indicators and

 

your dealer or technical

diagnostic LED D are

 

support.

illuminated

 

 

Fault and Bypass

UPS inverter fault.

UPS requires service. Contact

indicators and

 

your dealer or technical

diagnostic LED E are

 

support.

illuminated

 

 

Fault indicators and

UPS failed the battery

Replace batteries. Contact

diagnostic LED A & C

test.

your dealer or technical

are illuminated

 

support.

Fault indicators and

UPS shutdown due to a

Your UPS has received a

diagnostic LED C & E

command from the

signal or command from the

are illuminated

communications port(s)

attached computer. If this was

 

 

inadvertent, ensure the

 

 

communication cable used is

 

 

correct for your system. For

 

 

assistance, contact your dealer

 

 

or technical support.

13

Image 15
Contents UPStation GXT Important Safety Instructions Glossary of Symbols Major Components Introduction and System DescriptionInverter RECTIFIER/POWER Factor Correction PFC CircuitBattery Charger BatteryControls and Indicators Output OFF/BYPASS Button UPS ON/Alarm Silence/Manual Battery Test ButtonGXT 6 & 10 kVA Normal Mode OPERATION- UPS mode Battery Mode OperationOperating Modes Bypass Mode Operation Starting the UPS Powering Down the UPSOperation in Battery Mode Troubleshooting Audible Alarm Conditions Troubleshooting GuideProblem Cause Solution Troubleshooting Guide UPS Monitoring UPS Intelligent CommunicationsUPS Intellislot Communications Maintenance Location Installation InstructionsInstallation Considerations InspectionAirflow Dissipation Output Input Current Rating Electrical Installation ConsiderationsElectrical Connections Connecting the UPS Power cables Connection of optional remote battery cabinetsOutput connections GXT 6000/10000-X models only Stabilisers/Levelling Feet UPS Remote shutdown option PIN Assignment Collector to EmitterSerial Communications Ferrite Bead InstallationCommissioning the UPS Output Voltage Selector SwitchesBattery Run Times Specifications GXT6000T-230X GXT10000T-230X Life Support Applications Limited WarrantyTechnical Support UPStation GXT