AIRFLOW |
| DISSIPATION |
| OUTPUT |
| INPUT CURRENT | |||
|
| RATING |
| Amps max | |||||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
Cfm | m3h |
| Watts | K Btu/hr |
| VA | Watts |
| Including mains |
|
|
|
|
|
|
|
|
| variation/battery charge |
130 | 221 |
| 504 | 1.7 |
| 6000 | 4200 |
| GXT6000 = 33 amps |
270 | 459 |
| 840 | 2.8 |
| 10000 | 7000 |
| GXT10000= 54 amps |
|
|
|
|
|
|
|
|
|
|
ELECTRICAL INSTALLATION CONSIDERATIONS
This UPS must be installed by competent electrical personnel and wired in accordance with local/national electrical codes.
The following information is provided for your guidance.
WARNING
HIGH EARTH LEAKAGE CURRENT- EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE MAINS SUPPLY. Earth in accordance with local electrical codes.
CAUTION
This UPS is fitted with EMC suppression filters. Earth leakage exceeds 35mA. Transient and steady state earth leakage currents, which may occur when starting the UPS, should be taken into account when selecting instantaneous RCCB or RCCD devices. Note also that the earth leakage currents of the load will be carried by this RCCB or RCCD.
WARNING
This UPS does not incorporate automatic backfeed protection. A warning label must be fitted to all primary power isolators stating:
ISOLATE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS CIRCUIT.
On
The mains input supply cable must be connected to the UPS via a wall mounted double pole circuit breaker, rated to carry the current in table 1 and be capable of breaking the maximum prospective short circuit current of this branch circuit. The breaker is to be mounted within two metres of the UPS and be readily accessible to the operator.
17