Liebert GXTTM user manual RECTIFIER/POWER Factor Correction PFC Circuit, Inverter, Battery Charger

Page 5

RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT

In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to regulated DC power for use by the inverter, while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives: the mains power is used as efficiently as possible by the UPS, and the amount of distortion reflected on the mains is reduced. This results in cleaner power being available to other devices in the building not being protected by the UPStation GXT.

INVERTER

In normal operation, the inverter utilises the DC output of the power factor correction circuit and “inverts” it into precise, regulated sinewave AC power. Upon a mains power failure, the inverter receives its required energy from the battery through the rectifier / PFC. In both modes of the operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.

BATTERY CHARGER

The battery charger utilises energy from the Rectifier / PFC and precisely regulates it to continuously “float” charge the battery system. The battery system charges whenever the UPStation GXT is connected to mains power.

BATTERY

The UPStation GXT employs valve regulated, non-spillable, lead acid batteries. At typical room temperatures and with the UPS float charging, the battery system will last many years. Optional external battery cabinets are available to provide extended run times.

STATIC BYPASS

The UPStation GXT provides an alternate path for mains power to the connected load, in the unlikely event of a UPS malfunction. Should the UPS have an overload, over temperature, or UPS failure condition, the UPS automatically transfers the connected load to BYPASS providing the bypass voltage is within specification. BYPASS operation is indicated by an alarm and an illuminated BYPASS LED (other LED’s may be illuminated to indicate the diagnosed problem). To manually transfer the connected load from the inverter to BYPASS power, press the output OFF button once.

NOTE: The BYPASS power path does NOT protect the connected equipment from disturbances on the mains supply and its range of operation is limited to +/- 15% of the nominal input supply voltage.

AUTO RE-START

Upon restoration of the mains AC power after a mains power outage and complete battery discharge, the UPS will automatically restart and supply power to the critical load and the battery charger automatically recharges the battery.

3

Image 5
Contents UPStation GXT Important Safety Instructions Glossary of Symbols Major Components Introduction and System DescriptionBattery Charger RECTIFIER/POWER Factor Correction PFC CircuitBattery InverterControls and Indicators Output OFF/BYPASS Button UPS ON/Alarm Silence/Manual Battery Test ButtonGXT 6 & 10 kVA Operating Modes Normal Mode OPERATION- UPS modeBattery Mode Operation Bypass Mode Operation Starting the UPS Powering Down the UPSOperation in Battery Mode Troubleshooting Problem Cause Solution Audible Alarm ConditionsTroubleshooting Guide Troubleshooting Guide UPS Intellislot Communications UPS MonitoringUPS Intelligent Communications Maintenance Installation Considerations Installation InstructionsInspection LocationAirflow Dissipation Output Input Current Rating Electrical Installation ConsiderationsElectrical Connections Output connections GXT 6000/10000-X models only Connecting the UPS Power cablesConnection of optional remote battery cabinets Stabilisers/Levelling Feet UPS Remote shutdown option PIN Assignment Collector to EmitterSerial Communications Ferrite Bead InstallationCommissioning the UPS Output Voltage Selector SwitchesBattery Run Times Specifications GXT6000T-230X GXT10000T-230X Life Support Applications Limited WarrantyTechnical Support UPStation GXT