Battery Run Times

Load %

6kVA

6kVA + (1)

6kVA + (2)

 

 

GXT240VBATT

GXT240VBATT

10%

69

250

360

20%

58

197

301

25%

52

174

278

30%

48

155

248

40%

33

117

190

50%

23

88

140

60%

17

73

110

70%

14

60

94

75%

12

54

85

80%

11

50

77

90%

9

42

68

100%

8

37

59

 

 

 

 

Load %

10kVA

10kVA + (1)

10kVA + (2)

 

 

GXT240VLRT

GXT240VLRT

10%

71

480

900

20%

60

390

730

25%

55

345

655

30%

49

305

585

40%

39

230

450

50%

29

164

335

60%

23

129

265

70%

20

105

225

75%

18

93

205

80%

17

85

190

90%

14

70

155

100%

12

60

125

Note: All run times are in minutes, assume fully charged batteries, and are typical at 25OC (77OF) with resistive loads.

24

Image 26
Contents UPStation GXT Important Safety Instructions Glossary of Symbols Introduction and System Description Major ComponentsBattery RECTIFIER/POWER Factor Correction PFC CircuitBattery Charger InverterControls and Indicators UPS ON/Alarm Silence/Manual Battery Test Button Output OFF/BYPASS ButtonGXT 6 & 10 kVA Operating Modes Normal Mode OPERATION- UPS modeBattery Mode Operation Bypass Mode Operation Powering Down the UPS Starting the UPSOperation in Battery Mode Troubleshooting Problem Cause Solution Audible Alarm ConditionsTroubleshooting Guide Troubleshooting Guide UPS Intellislot Communications UPS MonitoringUPS Intelligent Communications Maintenance Inspection Installation InstructionsInstallation Considerations LocationElectrical Installation Considerations Airflow Dissipation Output Input Current RatingElectrical Connections Output connections GXT 6000/10000-X models only Connecting the UPS Power cablesConnection of optional remote battery cabinets Stabilisers/Levelling Feet PIN Assignment Collector to Emitter UPS Remote shutdown optionFerrite Bead Installation Serial CommunicationsOutput Voltage Selector Switches Commissioning the UPSBattery Run Times Specifications GXT6000T-230X GXT10000T-230X Limited Warranty Life Support ApplicationsUPStation GXT Technical Support