Battery Run Times
Load % | 6kVA | 6kVA + (1) | 6kVA + (2) |
|
| GXT240VBATT | GXT240VBATT |
10% | 69 | 250 | 360 |
20% | 58 | 197 | 301 |
25% | 52 | 174 | 278 |
30% | 48 | 155 | 248 |
40% | 33 | 117 | 190 |
50% | 23 | 88 | 140 |
60% | 17 | 73 | 110 |
70% | 14 | 60 | 94 |
75% | 12 | 54 | 85 |
80% | 11 | 50 | 77 |
90% | 9 | 42 | 68 |
100% | 8 | 37 | 59 |
|
|
|
|
Load % | 10kVA | 10kVA + (1) | 10kVA + (2) |
|
| GXT240VLRT | GXT240VLRT |
10% | 71 | 480 | 900 |
20% | 60 | 390 | 730 |
25% | 55 | 345 | 655 |
30% | 49 | 305 | 585 |
40% | 39 | 230 | 450 |
50% | 29 | 164 | 335 |
60% | 23 | 129 | 265 |
70% | 20 | 105 | 225 |
75% | 18 | 93 | 205 |
80% | 17 | 85 | 190 |
90% | 14 | 70 | 155 |
100% | 12 | 60 | 125 |
Note: All run times are in minutes, assume fully charged batteries, and are typical at 25OC (77OF) with resistive loads.