Liebert GXTTM user manual PIN Assignment Collector to Emitter, UPS Remote shutdown option

Page 23

COMMUNICATIONS INTERFACE PORT

The UPStation GXT UPS contains a standard DB-9 socket located on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows:

PIN

 

ASSIGNMENT DESCRIPTION

 

 

 

 

 

 

 

1

 

Low Battery (open collector)

 

 

 

 

 

 

 

2

 

UPS TxD (typical RS-232 levels)

 

 

 

 

 

 

 

3

 

UPS RxD (typical RS-232 levels)

 

 

 

 

 

 

 

4

 

Remote Shutdown (5-12V); battery operation

5

 

Common

 

 

 

 

 

 

 

6

 

Remote Shutdown (short to pin 5)

UPS mode (all modes) of operation

7

 

Low Battery (open emitter)

 

 

 

 

 

 

 

8

 

Mains Fail (open emitter)

 

 

 

 

 

 

 

9

 

Mains Fail (open collector)

 

 

 

 

 

 

 

 

PIN ASSIGNMENT

COLLECTOR TO EMITTER*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Maximum voltage and current on pins 1,7,8,9 is 80V DC; 10.0 mA.

CAUTION: TO MAINTAIN SAFETY (SELV) BARRIERS AND FOR ELECTROMAGNETIC COMPATABILITY, SIGNAL CABLES SHOULD BE SEGREGATED AND RUN SEPARATE FROM ALL OTHER POWER CABLES, BY 25mm WHERE APPLICABLE.

UPS Remote shutdown option.

Shorting pins 5 and 6 on the DB9 connector will shutdown the UPS output in any mode of operation. Removing the short circuit, the UPS will automatically auto- restart.

Where there is a requirement for a remote shutdown of the UPS to meet fire or other local safety codes, it is necessary to interrupt, at the same time with the same pushbutton, all mains input supplies to the UPS. The pushbutton that provides the UPS remote shutdown must be of the stay-down type ( Latching) to keep a short circuit on pins 5 and 6 until mechanically unlatched by hand.

Note ; The wiring for remote stop contacts pins 5 and 6 of the DB9 connector are defined as SELV . When connecting to a stop button interfacing with other mains emergency stop circuits, keep wiring segregated from other power wiring.

21

Image 23
Contents UPStation GXT Important Safety Instructions Glossary of Symbols Major Components Introduction and System DescriptionInverter RECTIFIER/POWER Factor Correction PFC CircuitBattery Charger BatteryControls and Indicators Output OFF/BYPASS Button UPS ON/Alarm Silence/Manual Battery Test ButtonGXT 6 & 10 kVA Operating Modes Normal Mode OPERATION- UPS modeBattery Mode Operation Bypass Mode Operation Starting the UPS Powering Down the UPSOperation in Battery Mode Troubleshooting Problem Cause Solution Audible Alarm ConditionsTroubleshooting Guide Troubleshooting Guide UPS Intellislot Communications UPS MonitoringUPS Intelligent Communications Maintenance Location Installation InstructionsInstallation Considerations InspectionAirflow Dissipation Output Input Current Rating Electrical Installation ConsiderationsElectrical Connections Output connections GXT 6000/10000-X models only Connecting the UPS Power cablesConnection of optional remote battery cabinets Stabilisers/Levelling Feet UPS Remote shutdown option PIN Assignment Collector to EmitterSerial Communications Ferrite Bead InstallationCommissioning the UPS Output Voltage Selector SwitchesBattery Run Times Specifications GXT6000T-230X GXT10000T-230X Life Support Applications Limited WarrantyTechnical Support UPStation GXT